Use only the racking tools provided by Powell
for inserting and removing the circuit breaker.
The use of other tools such as electric drills,
impact drill, etc., may damage the racking
mechanism and render it inoperative.
CAUTION
a. Verify that the circuit breaker
open/closed indicator displays
“BREAKER OPEN”
and if not, press the
manual trip operator to open the circuit
breaker.
b. To insert the circuit breaker into the
lower circuit breaker compartment,
open the compartment door and align
the wheels with the floor pan channels
of the compartment. Verify that the
floor pan channels are free of debris
prior to inserting the circuit breaker.
c. Roll the circuit breaker into the
compartment until the position
interlock bar and roller contacts a
positive stop.
Note:
This is the Disconnected Position.
d. Insert the circuit breaker compartment’s
secondary disconnect plug into
the circuit breaker’s secondary
disconnect receptacle. Once the plug
is fully inserted, move the secondary
disconnect latch from left to right until
it has engaged the housing of the
secondary disconnect plug.
Note:
This is the Test Position.
The anti-rollout latch on the lower
right side of the circuit breaker will
engage the block in the compartment,
preventing accidental removal of the
circuit breaker from the compartment.
3) Inserting the Circuit Breaker to the Connected
Position
The preferred method of racking the NDA
circuit breaker is electrically from a remote
location via Sentry remote controller. Refer
to the instruction bulletin provided with the
controller for detailed information on the
automatic racking procedures.
NOTICE
4) Emergency Racking In Procedure
In the event of an emergency, such as loss
of control power, the NDA circuit breaker
is equipped with an emergency racking
mechanism which enables racking the circuit
breaker into or out of the connected position.
NOTICE
The following emergency racking
procedure is intended to be used only in
the event of loss of control power, or failure
of the Sentry remote controller, or circuit
breaker to operate electrically.
For instructions on inserting the circuit
breaker into the compartment refer to
Ch 4 Installation, F. Racking Procedures for
PowlVac-NDA™ Series 4 Circuit Breaker,
2) Inserting the Circuit Breaker to the
a. Verify that the circuit breaker
open/closed indicator displays
“BREAKER OPEN”
and if not, press the
manual trip operator to open the circuit
breaker.