background image

2

Warnings

The  enclosure  is  used  to  protect  UL/cUL  listed  1638  and  1971  visual
notification  appliances  at  temperatures  down  to  -70˚F  (-57˚C).    It  is  the
installer’s responsibility to comply with NEC 70 Articles 502 and 503, NFPA72,
and other applicable fire and electrical codes. Conduit or raceway paths need
to  be  sealed  as  near  to  the  enclosure  as  possible.    Installer  should  have
maintained  supervision  over  the  low  temperature  thermostat.    The  low
temperature  monitoring  thermostat  makes  the  circuit  at  +32°F  (0°C)  and
clears  the  circuit  at  +50°F  (+10°C).    This  listing  requires  that  the  fire  alarm
supervisory  control  module  be  only  of  the  latching  type.    On  the  appliance
mounting plate is a label where you should record the installation date.  Also
include below the serial number and installation date on the instruction sheet
for quick reference.

Serial Number ____________________________________

Installation Date __________________________________

!

Installation Notes

1. The  enclosure  is  rated  to  protect  signaling  appliances  indoors  and

outdoors and in areas of direct weather exposure. 

2. When  covering  fire-signaling  appliances  with  the  enclosure,  some  light

loss occurs.  Please follow the guidelines listed during installation.

3. Strobe light loss values for respective manufacturers are shown on page

3.  To determine the new composite candela value of the use with the
guard  refer  to  the  sample  calculation  shown  on  page  3  for  a
manufacturer’s strobe.

4. Record the manufacturer’s candela value as “A” and the light loss value

as “B” and the assembly value as “C”.  Example: A 60 candela strobe with
a 30% light loss transmission value.  Value “A” is now 60.  Value “B” is
(60 times 30% or 0.30) in this case 18.

5. Now value “C” is value “A” minus value “B” or 60-18 = 42 candela light

source.    Now  refer  to  NFPA  tables  for  proper  room  size  that  newly
established value “C” will work in.  Then submittal installation drawings
must show the composite candela value in this example 42.

6. On a multiple candela value strobe such as 15/30/75 a calculation must

be  done  for  each  value  and  the  drawing  notation  composite  value  for
each number on the strobe.

7. All  field  wiring  within  this  enclosure  must  be  rated  for  a  minimum

operating range of 0ºC - 110ºC.

Содержание STI-1229HTR-HAZ

Страница 1: ...mperature or environmental conditions exceed the operating range of fire strobe signaling devices Unit requires 24 VDC continuous for fan operation and 110 VAC or 240 VAC for heater as well as power f...

Страница 2: ...ng appliances indoors and outdoors and in areas of direct weather exposure 2 When covering fire signaling appliances with the enclosure some light loss occurs Please follow the guidelines listed durin...

Страница 3: ...ecognized Component Life 5 Years Continuous Duty WARNING The polarity of the circulating fan is important as it only rotates in one direction with red lead being positive Gasket Material Neoprene Life...

Страница 4: ...naling wires must enter thru top conduit and remain separated per NFPA 70 NEC and local codes HIGH VOLTAGE WIRING Refer to Fig 2 5 Connect high voltage Make sure 110 or 240 VAC power is OFF Refer to h...

Страница 5: ...h wire under heater assembly Fan must be mounted toward top of enclosure 10 Wire strobe using Teflon coated wire provided White Positive Black Negative and attach to the strobe mounting bosses on heat...

Страница 6: ...E PWR FAN PWR TEMP WARNING SUPERVISOR _ _ FAN LOW TEMP WARNING STROBE 16 33VDC 600mA S LOW VOLTAGE CIRCUIT HIGH VOLTAGE CIRCUIT TERMINAL BLOCK TERMINAL BLOCK CHASSIS HEATER EOL DEVICE SUPPLIED BY CUST...

Страница 7: ...T 1 PROVIDED SOLID CLEAR COVER WASHER 6 PROVIDED 8 32 x 3 4 in SOCKET CAP SCREW 6 PROVIDED LOW VOLTAGE ELECTRICAL ENTRY IN AREAS WHERE FREQUENT WASH DOWNS OCCUR WASHERS MAY BE USED TO STAND OFF ENCLOS...

Страница 8: ...International Europe Ltd Unit 49G Pipers Road Park Farm Industrial Estate Redditch Worcestershire B98 0HU England Tel 44 0 1527 520 999 Fax 44 0 1527 501 999 Freephone 0800 085 1678 UK only E mail in...

Отзывы: