EVAC v1.24 EN

TECHNICAL DATA ENTRANCE STATION

Power:

24 VDC 
In standby: 40 mA

Active: 120 mA

Inputs:

4 x 24 VDC, max 200 mA in total, optically isolated

Outputs: 

3 x 24 VDC, max 200 mA

Size:

Surface mounted: 418 x 116 x 40 mm (L x W x H)
Flush mounted: 400 x 110 x 40 mm (L x W x H)

Weight:

300 g - without frontplate

IP code:

IP43

TECHNICAL DATA FLOOR STATION/CAR STATION

Power:

24 VDC 
In standby: 30 mA
Active: 60 mA

Inputs:

2 x 24 VDC, max 100 mA, optically isolated

Outputs:

2 x 24 VDC, max 100 mA in total

IP code:

IP43

TECHNICAL DATA BUS CABLE

Max cable length:

200 meters - using 0,5 mm

2

 shield cable (recommended).

TECHNICAL DATA LMS UNIT

Power:

230 VAC

Inputs:

2 x 24 VDC, max 200 mA in total, optically isolated

Relay outputs:

Max. 2 A/30 VDC, 0,5 A/125 VAC potential free relay contacts

PSU:

max. 4 A at 24 VDC

FreeRTOS is used in the product - www.freertoss.org

Содержание EVAC

Страница 1: ...SafeLine EVAC 01 2018 www safeline group com 366 400 110 29 2 5 88 366 383 2 x 4 MANUAL EVAC v1 24 EN Fire communication Evacuation and fire fighting intercom system...

Страница 2: ...H Weight 300 g without frontplate IP code IP43 TECHNICAL DATA FLOOR STATION CAR STATION Power 24 VDC In standby 30 mA Active 60 mA Inputs 2 x 24 VDC max 100 mA optically isolated Outputs 2 x 24 VDC m...

Страница 3: ...tructure 25 OPERATING Menu tree structure 19 Configuring EVAC 21 CONFIGURATION START UP Overview EVAC entrance station ES 8 Overview EVAC floor station FS 10 Overview EVAC car station CS 12 Overview c...

Страница 4: ...liability arising from printing errors mistakes or changes DECLARATION OF CONFORMITY Download The declaration of conformity at our website www safeline group com SAFETY PRECAUTIONS Only trained profes...

Страница 5: ...loor Floor 3 Floor 11 Top floor Floor 2 Main entrance CAN1 CAN2 1 2 3 4 5 6 7 1 2 3 4 5 6 7 Yellow Green Red Blue Brown Black Grey Orange Car 1 or Floor 1 3 Floor 4 optional Car 2 1 2 3 4 5 6 7 1 2 3...

Страница 6: ...CB Connector board 1 2 3 4 5 6 7 1 2 3 4 5 6 7 Yellow Green Red Blue Brown Black Grey Orange Car Station CS Address selector tens Address selector singles 0 0 Termination ON m ipsum Car Station CS 9 9...

Страница 7: ...4 5 6 7 7 6 5 4 3 2 1 Floor Station FS 1 Address selector tens Address selector singles Floor Station FS 2 Address selector tens Address selector singles Floor Station FS 1 Address selector tens Addr...

Страница 8: ...ION ES The master unit of the system All commands and logic is handled by the entrance station There can only be one entrance station in an EVAC system The engraved text on the entrance station is ava...

Страница 9: ...ARD TERM OFF ON SPK BUS IN 4 IN 3 OUT3 SYSTEM BUS CAN CAN ERR CONTR USB IN 1 IN 2 OUT1 OUT2 SD C ARD TERM OFF ON EVAC v1 24 EN Installation ENTRANCE STATION BACKSIDE Output no 3 Input no 3 Input no 4...

Страница 10: ...Installation There can be up to 98 oor stations in one system The engraved text on the oor station is available in english german and swedish OVERVIEW EVAC FLOOR STATION FS Speaker Alarm button with...

Страница 11: ...ed by law CANTerminationSwitch ON OFF EVAC v1 24 EN Installation FLOOR STATION RJ45 for Power and Communication CAN termination switch ON OFF Input no 2 Output no 2 USB for firmware update SD card mic...

Страница 12: ...ion Note Car station will always have the address 0 0 OVERVIEW EVAC CAR STATION CS Speaker Microphone RJ45 for Power and Communication CAN termination switch ON OFF Input no 2 Output no 2 USB for firm...

Страница 13: ...accessories are copyrighted by law 1 2 3 4 5 6 7 7 6 5 4 3 2 1 EVAC v1 24 EN Installation Connection board 1 24 VDC 2 0 V 3 CAN H 4 CAN L 5 GND Shield 6 Audio bus A 7 Audio bus B OVERVIEW CONNECTION B...

Страница 14: ...232 connection to SafeLine telephone If used for LMS Lift Monitoring System 3 USB for updating the firmware 4 CAN LED 4 1 CAN 4 2 CAN ERR 5 Termination switch 5 1 CAN2 Car 5 2 CAN1 Shaft 6 Connectors...

Страница 15: ...the entrance station The EVAC system is powered by the LMS unit For relay information please see page 26 Car station address 0 0 car 1 or 99 car 2 There can only be one car station in the system Floor...

Страница 16: ...d accessories are copyrighted by law 366 400 110 29 2 5 88 366 383 2 x 4 210 90 22 5 25 2 176 17 2 x 6 87 4 56 18 33 7 35 3 226 182 214 54 2 x 9 2 x 5 EVAC v1 24 EN Installation MOUNTING DIMENSIONS Ca...

Страница 17: ...law 10 mm EVAC v1 24 EN Installation CUTTING THE CABLE Make sure that the modular plugs RJ45 on the ends of the cable are facing the opposite way see picture The connection cable is used between the c...

Страница 18: ...system is working and that the bus is working properly When the entrance station receives a heartbeat from a CAN bus node for the first time it sets the node to the current system mode i e EVAC FIRE...

Страница 19: ...24 EN Configuration MENU TREE STRUCTURE EVAC Menu Broadcast soundfile 9 Select sound file Connect to car 9 Connected to node Connect to incoming alarm 9 Connected to node Connect to any node 9 Connect...

Страница 20: ...h 9 English Entrance station 9 Backlight 9 Volume 9 Inputs 9 Input function 9 Outputs 9 Output function 9 Hardware version 9 Software version Car 9 Volume 9 Hardware version 9 Software version 9 Mic L...

Страница 21: ...in the names for the Soundfiles Sound file triggers All floor stations have the possibility to play sound files This is done by either manually triggering broadcast sound file in the EVAC menu the pl...

Страница 22: ...the car station Please note The EVAC system can be configured to operate the lift in any way You can configure an input to trigger the EVAC mode in the setup menu The system will be in EVAC mode as l...

Страница 23: ...n is automatically a fire unit The floor stations that should be fire units need to be configured in the setup menu When in FIRE mode the car station is always connected to the audio bus and all sound...

Страница 24: ...connected floor car station will have the microphone activated and will transmit audio onto the audio bus The entrance station receives audio and the speaker is activated If the PTT input is activated...

Страница 25: ...ween tests Start self test Activate the self test Read config from SD Reads configuraton from the SD card Factory reset Reset all parameters not RTC to factory default The reset is only in RAM so to s...

Страница 26: ...aker volume for the node SoundFiles When in the sound files Press Up key Down key to select another sound file Mode Mode for the sound files Off On Repeat Repeat Delay time s between repeats Indicate...

Страница 27: ...ed LOG on the entrance station s SD card The log file is a txt file and can be opened in any text editor Each log entry consists of ENTRY Serial number starting on 1 TIME Time stamp parsed from the re...

Страница 28: ...e eu SafeLine Norway Solbr veien 49 1383 Asker Norway Tel 47 94 14 14 49 post safeline no SafeLine Headquarters Antennv gen 10 135 48 Tyres Sweden Tel 46 0 8 447 79 32 info safeline se Support 46 0 8...

Отзывы: