1.  Waterflow detectors may not work or operate properly if sprinkler piping being monitored is 

plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should be 

checked regularly for such blocking material, following the instructions in Chapter 5 of NFPA 

Standard 13A.

2.  Alarms generated by the activation of waterflow detectors may not be received by a central 

station if telephone or other communication lines to the detector are out of service, disabled, 

or open.

WARNING

THE LIMITATIONS OF WATERFLOW ALARM DEVICES

3.  Vane-type waterflow detectors have a normal service life of 10-15 years. Hard water systems, 

however, may substantially reduce waterflow detector service life.

4.  Waterflow detectors are not a substitute for insurance. Building owners should always insure 

property and lives being protected by sprinkler systems.

5.  If valves controlling the water supply to a sprinkler system are closed, vane-type waterflow 

detectors will not work. All valves controlling a sprinkler water supply should be sealed or 

locked in the normally open position. The normally open position should be monitored by a 

sprinkler supervisory switch.

THREE-YEAR LIMITED WARRANTY

SAFE SIGNAL warrants that the equipment herein shall conform to said descriptions as to all af-

firmation of fact and shall be free from defects of manufacture, labeling, and packaging for a pe-

riod of three (3) years from the invoice date to the original purchaser, provided that representative 

samples are returned to SAFE SIGNAL for inspection. Upon a determination by SAFE SIGNAL 

that a product is not as warranted, SAFE SIGNAL shall, at its exclusive option, replace or repair 

said defective product or parts thereof at its own expense except that Purchaser shall pay all   

shipping, insurance, and similar charges incurred in connection with the replacement of the 

defective product or parts thereof. This Warranty is void in the case of abuse, misuse, abnormal 

usage, faulty installation, or repair by unauthorized persons, or if for any other reason SAFE 

SIGNAL determines that said product is not operating properly as a result of causes other than 

defective manufacture, labeling, or packaging.

  

I56-4044-E 

 

 4/21

Содержание WFDTNRN

Страница 1: ...vided for each size of the threaded sweat or plastic tee See Figure 1 and approximate tee depth chart Each paddle has an indication that shows the pipe size and type of tee to be used with FIGURE 1 MOUNTING DIMENSIONS 3 1 2 2 5 8 4 TEE DEPTH DESIGNEDTO FITWITHIN 2 X 4 STUDWALL CONSTRUCTION PLASTICVANE TEE FITTING INSTALLATION GAUGE END OF PADDLETREE MUST FIT BETWEENTOP OFTEE AND BOTTOM OF FLANGE T...

Страница 2: ...h provided Move the ac tuator lever back and forth to check for binding If the vane binds remove the detector and correct the problem before proceeding CAUTION Be sure the direction of flow arrow and directional cover points in the correct direc tion otherwise a waterflow condition will go unreported See Figure 3 FIGURE 3 DIRECTIONAL COVER OPERATIONAL TESTING Always notify a central station monito...

Страница 3: ...ty having jurisdiction for leaks and replace if leaks occur Test detectors at least quarterly as described in Operational Testing to insure proper operation Test more often if required by the authority having jurisdiction Under normal conditions Safe Signal waterflow detectors should provide years of trouble free service However if the switch enclosure becomes faulty request Part No FS RT and ensu...

Страница 4: ...sprinkler water supply should be sealed or locked in the normally open position The normally open position should be monitored by a sprinkler supervisory switch THREE YEAR LIMITED WARRANTY SAFE SIGNAL warrants that the equipment herein shall conform to said descriptions as to all af firmation of fact and shall be free from defects of manufacture labeling and packaging for a pe riod of three 3 year...

Отзывы: