WFDNFS Vane-type Waterflow Detectors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

SPECIFICATIONS

Contact Ratings: 

Two sets of SPDT (Form C); 10 A @ 125/250 VAC 

; 2.5 A @ 12/24 VDC 

Triggering Threshold Bandwidth (Flow Rate): 

4 – 10 GPM

Static Pressure Rating: 

175 PSI (Max.)

Dimensions, Installed: 

WFDNFS – 4 in H x 3½

 

in W x 6¾ in D

Operating Temperature Range: 

32°F to 150°F (0°C to 66°C)

Enclosure Rating: 

WFDNFS – NEMA 4/IP54, as tested by Underwriters Laboratories, Inc. (UL)

The WFDNFS can be installed between 2×4 stud wall construction. 

IMPORTANT

Please Read Carefully And Save
This instruction manual contains important information about the installation and 

operation of waterflow detectors. Purchasers who install waterflow detectors for use 

by others must leave this manual or a copy of it with the user. Read all instructions 

carefully before beginning.

CAUTION

The model WFDNFS is a vane-type waterflow detector for use in wet-pipe fire sprin-

kler systems only. Vane-type waterflow detectors shall not be used as the sole initiat-

ing device in both deluge and preaction systems; waterflow detectors used in these 

types of systems may result in an unintended discharge caused by a surge, trapped air 

or a short retard time. 

WARNING

Installation must be performed by qualified personnel and in accordance with all na-

tional and local codes and ordinances.
Shock hazard: Disconnect power source before servicing. Serious injury or death 

could result.
Risk of explosion: Not for use in hazardous locations. Serious injury or death could 

result.

PRINCIPLES OF OPERATION

Vane-type waterflow detectors mount to water filled pipes in fire sprinkler systems. 

Waterflow in the pipe deflects a vane. Deflection of the vane produces a switched 

output, usually after a specified delay.
All WFDNFS detectors have a pneumatically controlled mechanical delay mecha-

nism. Delays do NOT accumulate; they reset if the flow of water stops or drops below 

minimum triggering flow rate before the entire delay has elapsed. All detectors will 

activate on a sustained flow of water of 10 gallons per minute (gpm) or greater down-

stream of the device.

COMPATIBLE PIPE TEES/RISERS

The WFDNFS is supplied with 6 paddles. One paddle is provided for each size of 

CPVC tee. See Figure 1 and approximate tee depth chart. Each paddle has an indica-

tion that shows the pipe size and type of tee to be used. 

INSTALLATION GUIDELINES

Before installing any waterflow alarm device, be thoroughly familiar with:

NFPA 72:  National Fire Alarm Code

NFPA 13:  Installation of Sprinkler Systems

NFPA 13D:  Standard for 1 and 2 Family Dwellings and Manufactured Homes

NFPA 13R:  Standard for Multi-family Dwellings
Also, follow other applicable NFPA standards, local codes and the requirements of the 

authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report a water-

flow condition. Safe Signal is not responsible for devices that have been improperly 

installed, tested or maintained.
1.   Mount the detector where there is adequate clearance for installation and re-

moval and a clear view of it for inspection. See Figure 1 for mounting dimen-

sions.

2. 

 Locate the detector 6 to 7 feet above the floor to protect from accidental 
damage. 

3.   On horizontal runs, position the detector on top or side of the pipe. Do not 

mount it upside down because condensation may collect in the housing and 

impair the operation of the detector.

 

 For vertical flow applications, mount detector on pipe where upflow conditions 

exist. Failure to do so may prevent unit from operating properly.

4.   Mount detector at least 6 inches from a fitting which changes the direction of 

the waterflow, or no less than 24 inches from a valve or drain.

5.   BE SURE DIRECTION-OF-FLOW ARROW AND DIRECTIONAL COVER 

MATCHES ACTUAL DIRECTION OF FLOW IN THE PIPE. See Figure 5.

I56-4262-B

W0399-00

FIGURE 1. MOUNTING DIMENSIONS AND APPROXIMATE TEE DEPTH 

REQUIREMENTS

3-1/2"

2-5/8"

4-1/2"

TEE

DEPTH

PLASTIC VANE

LOCKING

 COLLAR

TEE 

ADAPTER

TEE FITTING

APPROXIMATE TEE DEPTH REQUIREMENTS

Tee Depth

SPEARS

TYCO

NIBCO

IPEX

1 × 1 × 1"

2

3

/

8

"

2

5

/

16

"

2

11

/

32

"

2

5

/

8

"

1

1

/

4

 × 1

1

/

4

 × 1"

2

29

/

32

"

2

9

/

16

"

2

3

/

4

"

3"

1

1

/

2

 × 1

1

/

2

 × 1"

3

1

/

8

"

3

5

/

32

"

3

1

/

16

"

3

1

/

4

"

2 × 2 × 1"

3

11

/

16

"

3

11

/

16

"

3

1

/

2

"

3

3

/

4

"

This waterflow detector has been evaluated for use with UL Listed CPVC fittings manufac-

tured by the following companies: Tyco, Nibco, Ipex, and Spears Manufacturing Company. 

The Model WFDNFS is required to be installed in accordance with the Listing limitations 

specified by the manufacturer of the tee fitting.  

  