Installation & Operating Procedures

Opal LT 

Series

RVS-AX Analogue Soft Starter

8-170A, 220V-600V

Manufactured By SOLCON

Содержание Solcon Opal LT Series

Страница 1: ...eplies given within 24 hours 18 Neville Street Unit C New Hamburg ON N3A 4G7 Tel 519 662 6489 Fax 1 866 280 5247 www opalstarters com Installation Operating Procedures Opal LT Series RVS AX Analogue Soft Starter 8 170A 220V 600V Manufactured By SOLCON ...

Страница 2: ...1 O OP PA AL L L LT T R RV VS S A AX X A An na al lo og gu ue e S So of ft t S St ta ar rt te er r 8 8 1 17 70 0A A 2 22 20 0 6 60 00 0V V I In ns st tr ru uc ct ti io on n M Ma an nu ua al l Ver 3 2 04 ...

Страница 3: ...A equipment 2 Use of the product in domestic environments may cause radio interference in which case the user may be required to employ additional mitigation methods 3 Utilization category is AC 53a or AC53b Form1 4 For further information see Technical Specification Warnings Internal components and P C B s are at Mains potential when the RVS AX is connected to mains This voltage is extremely dang...

Страница 4: ...epth Weights Kg A1 120 232 105 2 6 A2 129 275 185 5 A3 129 380 185 8 4 A4 172 380 195 11 8 The starter should be selected in accordance with the following criteria 1 Motor Current Starting Conditions Select the starter according to motor s Full Load Ampere FLA as indicated on its nameplate even if the motor will not be fully loaded The RVS AX is designed to operate under the following maximum cond...

Страница 5: ...factory for further details Short Circuit Protection The RVS AX should be protected against a short circuit by Thyristor Protection fuses The recommended I2 t values are RVS AX type I t A S Ferraz Fuses RVS AX 8 400 6 6 URS 35 RVS AX 17 2 000 6 6 URS 45 RVS AX 31 3 000 6 6 URS 63 RVS AX 44 6 000 6 6 URB 100 RVS AX 58 12 000 6 6 URB 150 RVS AX 72 18 000 6 6 URB 160 RVS AX 85 40 000 6 6 URD 200 RVS ...

Страница 6: ...or Activating a valve after a compressor has reached full speed Loading a conveyor after the motor has reached full speed Fault contact Terminals 7 8 Voltage free N O 8A 250VAC 2000VA max The contact closes upon operation of any fault The contact returns to its original position after the fault has been removed upon reset or upon disconnection the Mains voltage Warning Do not use the Fault contact...

Страница 7: ...ing The motor should start revolving immediately after Start signal Current Limit Determines motor s highest current during starting Range is 100 400 of FLC as set on starter s FLC adjustment Too high of a setting will allow higher currents to be drawn from Mains resulting in faster acceleration Too low of a setting may prevent the motor from completing the acceleration process and reaching full s...

Страница 8: ... the Fault contact closes To reset the starter after the fault has been removed press Reset button on starter s front panel or disconnect Mains voltage Heatsink Over temperature Protection A thermal sensor mounted on the heatsink trips the starter when its heatsink temperature rises above 85ºC Warning The Over temperature Protection is designed to operate under normal conditions and will operate i...

Страница 9: ...ort increase Ramp Up time setting When Soft stop is required set Ramp Down Potentiometer to the required time minimum deceleration time is recommended Check that soft stopping process is as required Note If Ramp Down potentiometer is not in the minimum setting Emergency stop may be performed by disconnecting the mains voltage Examples of Starting Curves Light Loads Pumps Etc Current limit set to 3...

Страница 10: ...the RVS AX Ramp Up Ramp Down Yellow Lights upon start signal or during soft stopping RUN Green Lights upon end of starting When the internal bypass relays close Overload Red Inverse time electronic overload becomes operational after the End Of Acceleration process see page 7 Phase loss Red Lights when one or two phases are missing for more than 1 sec Over temperature Red Lights on and trips the st...

Страница 11: ...Dimensions SOLSRV1 Data Catalogs and Marketing materials Instruction Manuals RVS AX Instruction Manual 4 5 03 doc ...