MS6 REDUCED VOLTAGE STARTER
Page 26
12
Analog
I/O
1201 Analog
Output
-
This parameter designates what signal will be sent out the analog
output
-
Current reference means the current reference that the Opal is
currently using (0-5volts = 0 – 615% motor nameplate current)
-
Current feedback means that the actual motor current will be sent
(0-5volts = 0-615% motor nameplate current)
-
Overload level means that the present calculated thermal capacity
will be sent (0-5volts = 0-100% of capacity)
-
Phase Angle means that the current phase angle will be sent (0-
5volts = 0-180 degrees)
Current Reference
Current Feedback
Overload Level
Phase Angle
13
Motor
Data
1301
Motor
Amps
- this should be the name plate full load amps of the motor
5 – 1100 Amps
Read\Write
1302
Motor
Volts
- this should be the name plate voltage of the motor
240 – 600 Volts
Read\Write
1303
Service
Factor
- this should be the name plate service factor of the motor
1.00 – 1.30
Read\Write
14
Communications
1401
Modbus Slave Node
-
This is the slave node that the Opal will be seen as
-
This parameter is only accessible if a Modbus Slave card is
installed in the Opal
1 – 7
Read\Write
1402
MB Slv Baud Rate
-
This is the baud rate that the MB Slave card will attempt to
communicate
-
This parameter is only accessible if a Modbus Slave card is
installed in the Opal
300 Kbaud
1200 Kbaud
2400 Kbaud
4800 Kbaud
9600 Kbaud
19200 Kbaud
38400 Kbaud
57600 Kbaud
Read\Write
1403
DeviceNet
MacID
-
This is the DeviceNet MacID that the Opal will be seen as
-
This parameter is only accessible of a DeviceNet Slave card is
installed in the Opal
0 – 31
Read\Write
1404
DeviceNet Slv Baud Rate
-
This is the baud rate that the DeviceNet Slave card will attempt to
communicate
-
This parameter is only accessible of a DeviceNet Slave card is
installed in the Opal
125 Kbaud
250 Kbaud
500 Kbaud
Read\Write
1405
DH+ Station Address
-
This is the station address that the Opal will be seen as
-
This parameter is only accessible if a DH+ card is installed
1 - 32
Read\Write
1406
DH+ Baud Rate
-
This is the baud rate that the DH+ card will communicate at
-
This parameter is only accessible if a DH+ card is installed
57.6 Kbaud
115.2 Kbaud
230.4 Kbaud
Read\Write
Содержание Opal Pro MS6 Series
Страница 3: ...MS6 REDUCED VOLTAGE STARTER Page 2...
Страница 5: ...MS6 REDUCED VOLTAGE STARTER Page 4...
Страница 31: ...MS6 REDUCED VOLTAGE STARTER Page 30 10 2 THREE WIRE CONTROL Enable must be closed for starter to operate...
Страница 32: ...MS6 REDUCED VOLTAGE STARTER Page 31 10 3 THREE WIRE REVERSING Enable must be closed for starter to operate...
Страница 33: ...MS6 REDUCED VOLTAGE STARTER Page 32 10 4 THREE WIRE WITH BY PASS Enable must be closed for starter to operate...