Depth of
discharge(%)
Charge current of
constant current
charge(A)
Time for changing constant
current charge to constant
voltage charge(h)
Charge voltage of
constant voltage
charge(V)
Charge time(h)
20
0.1C
10
1.6
2.33
8
0.15C
10
1.2
2.33
6
50
0.1C
10
4.3
2.33
14
0.15C
10
3.3
2.33
12
80
0.1C
10
6.8
2.33
16
0.15C
10
5.5
2.33
14
100
0.1C
10
8.7
2.33
18
0.15C
10
6.8
2.33
16
Operation
Table 4-3 Required charge time in different depth of discharge
12
Storage
The battery should be stored in clean and dry environment .
Storage time: battery is ex-work in fully charged,storage time should be limited,for ensuring battery
performance,storage time please do not exceed following time:
Under 25
℃
, six months
Under 30
℃
, three months
Under 40
℃
, six weeks
The battery supplemental charge method during the storage is: charge battery with 2.35V/cell for 8
to 12 hours.
It is necessary to limit the current, and the optimum limiting value is within 0.2C10 ( A ) .
Testing of the open circuit with the storage battery can decide whether it shall be supplemental
charged. If the voltage drops to 2.10V/cell, the battery shall be supplemental charged in time.
Improper maintenance will shorten the battery service life or decrease the service performance.