Operating manual - HPC Mk 4 LL & Mk 5 (including ATEX)
26/48
001752 en 2023.05
2.5
Sound measurement and noise data
2.5.1
Noise data
Noise data is stated in:
SWL
: A-weighted
s
ound po
w
er
l
evel
SPL
: A-weighted
s
ound
p
ressure
l
evel, in free field over reflecting plane (1 m distance).
•
Noise data is based on measurements according to ISO 9614-2.
•
The stated SPL values are calculated using the formula 8.3 in ISO 3744.
•
The stated values are for a complete unit operating in 100% capacity.
2.5.2
Noise data for HPC
Evaporating temperature, TE
+35°C [95°F]
Condensing temperature, TC
+74°C [165°F]
Refrigerant
R717
Speed
1500 rpm
Compressor block
SWL
SPL
HPC 104 S
97
82
HPC 106 S
99
83
HPC 108 S
100
84
Table 3: Noise data for HPC and HPX, 1500 rpm
Evaporating temperature, TE
+35°C [95°F]
Condensing temperature, TC
+74°C [165°F]
Refrigerant
R717
Speed
1800 rpm
Compressor block
SWL
SPL
HPC 104 S
100
84
HPC 106 S
101
85
HPC 108 S
102
86
Table 4: Noise data for HPC and HPX, 1800 rpm
Evaporating temperature, TE
0°C [32°F]
Condensing temperature, TC
+55°C [131°F]
Refrigerant
R717
Speed
1500/1800 rpm
Compressor block
Rpm
SWL
SPL
HPC 112 S
1500
100
85
HPC 106 S
1800
103
87
Table 5: Noise data for HPC, 1500 and 1800 rpm
Noise data for other operating conditions can be provided by Johnson Controls Denmark on
request.
Note: