Operating manual - ChillPAC and LP ChillPAC Mk 3
010823 en 2021.06
31/68
3.2.5
Receiver
The LP ChillPAC (external condenser) is equipped with a receiver. The purpose of the receiver is to ac-
cumulate the liquid coming from the condenser. The receiver has the following connections and sight
glasses all located on the flat end cover:
Fig. 15: LP ChillPAC Mk 3 receiver
Pos. no.
Component
1
Liquid inlet
2
Liquid outlet
3
Equalising line
4
Connection for safety valves
5
Connection for manometer
6
Connection discharge pressure (to oil recovery system)
7
Drain (including stop valve and quick-closing drain valve)
8
Sight glasses for liquid level check
9
Liquid (plugged)
10
Connection for purge valve
The receiver must never be filled completely with liquid. The level can always be checked in the 3 sight
glasses.
Warning!
The level must never rise above the middle of the upper sight glass.
To ensure correct operation of the chiller, the bottom sight glass should always be minimum half full. This
will prevent gas from entering the liquid line.
4
10
5
6
3
8
2
7
9
1
Содержание ChillPAC
Страница 1: ...ChillPAC and LP ChillPAC Mk 3 Chiller unit with reciprocating compressor Operating manual EN ...
Страница 2: ......
Страница 69: ......