![S+S Regeltechnik RHEASGARD KLGF-U Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/s-s-regeltechnik/rheasgard-klgf-u/rheasgard-klgf-u_operating-instructions-mounting-and-installation_3549555018.webp)
18
F
RHEASGARD
®
KLGFxx ⁄ RHEASREG
®
KLSW xx
Rev. Data - V32
Schéma de connexion
KLGF
/
KLSW-xx LCD
KLGFT-W
/
KLGFVT-W LCD
thershold
rel.
sb
zero
set
2
1
3 4
12 11 13
sb
offset
up down
OUT1
+UB
OUT2 GND
NC M NO
SET potentiometer
thershold
= switching point (min. 0.1m/s ... max. 20m/s)
sb
= start bridging
(min. 0s ... max. 120s)
offset
= temperature (± 5K)
Relay
LEDs
(on = aktiv)
rel.
= relay / switching point exceeded
sb
= start bridging
Pushbutton
zero point setting (0m/s)
LEDs
Pushbutton
Plug for
display
Schéma de raccordement
Schéma de raccordement
Schéma de raccordement
KLGF-U LCD
KLGFVT-W LCD
KLGFT-W
KLSW-W24 LCD
12
11
13
1
2
3
4
+UB 24V AC/DC
NC
Normally Closed
NO
Normally Open
M
Common
–UB GND
free
free
1
2
3
4
+UB 24V AC/DC
–UB GND
Output 0-10V Flow velocity
free
*
KLGFVT-W LCD:
le passage de la grandeur mesurée « débit » au
paramètre alternatif
« débit volumétrique »
est commandé par menu à l’écran.
12
11
13
1
2
3
4
+UB 24V AC/DC
NC
Normally Closed
NO
Normally Open
M
Common
–UB GND
Output 0-10V / 4...20mA Flow velocity
Output 0-10V / 4...20mA Temperature
thershold
rel.
sb
zero
set
2
1
3 4
12 11 13
sb
offset
up down
OUT1
+UB
OUT2 GND
NC M NO
SET potentiometer
thershold
= switching point (min. 0.1m/s ... max. 20m/s)
sb
= start bridging
(min. 0s ... max. 120s)
offset
= temperature (± 5K)
Relay
LEDs
(on = aktiv)
rel.
= relay / switching point exceeded
sb
= start bridging
Pushbutton
zero point setting (0m/s)
LEDs
Pushbutton
Plug for
display
Содержание RHEASGARD KLGF-U