14
1. For zero point setting, the device must be in operation for at least
60 minutes.
2. Connect pressure inputs P (+) and P (–) with a hose.
(Pressure difference between the inputs = 0 Pa).
3. Precondition: DIP switch 6 is in OFF position.
4. For zero point setting, press pushbutton uninterrupted for 10
seconds.
By pressing the pushbutton, a countdown of ca. 10 seconds is
started. The yellow LED is blinking and the countdown is shown on the
display (optional).
Zero point calibration takes place after the countdown period. This is
indicated by continuous LED light and at the display (optional) by
switching from "AUTO 0" to "PROG 0".
Note: By releasing the pushbutton during the countdown
(counter > 0), zero point setting is immediately cancelled!
Automatic offset setting:
Pushbutton
DIP- switches
V+
Pa
GND
GND
1 2 3 4
1 2 3 4 5 6
Offset
Offset
ON
DIP auto
zero
LED
Plug for display
Plug for
display
Offset correction
see graph
ca. ± 10%
Zero point setting
(auto zero)
min. max.
Contact
pin side
PREMASGARD
®
114x
In the display in the 1
st
line the actual pressure is indicated up to
the measuring range limit.
Switching between the units Pa and hPa (100 Pa = 1 hPa) happens
automatically. Characters displayed:
Pa = pascal
hP = hectopascal
PREMASREG
®
114x
In the display in the 1
st
line the actual pressure is indicated up to
the measuring range limit.
Switching between the units Pa and hPa (100 Pa = 1 hPa) happens
automatically. Characters displayed:
Pa = pascal
hP = hectopascal
In the 2
nd
line information regarding the relay switching status is
visible (in form of a circle) as well as an indication of the pressure
switchpoint in Pa (adjustable via set potentiometer).
○
Circle empty = relay in idle state
●
Circle solid = relay activated
PREMASGARD
®
114x / PREMASREG
®
114x
Indication of range exceedance respectively underrunning
When the pressure range is exceeded or underrun, the limit
exceedance is indicated in the 2
nd
display line.
The exceeded pressure range is depicted blinking in Pa, showing
the direction of overrunning.
Display readout:
DIP switches for
pressure range setting, output attenuation and zero compensation:
Pressure range
(adjustable, maximum measuring range depending on type of device)
PREMASGARD
®
114x
DIP switch 5
is not assigned!
0...1000 Pa
0...5000 Pa
–100...+100 Pa
–1000...+1000 Pa
–5000...+5000 Pa
DIP 1 DIP 2
0...100 Pa
0...1000 Pa
–50...+50 Pa
–100...+100 Pa
–1000...+1000 Pa
OFF
OFF
0...300 Pa
0...2000 Pa
–100...+100 Pa
–300...+300 Pa
–2000...+2000 Pa
O N
OFF
0...500 Pa
0...3000 Pa
0 ... +50 Pa
–500...+500 Pa
–3000...+3000 Pa
OFF
O N
0...1000 Pa
0...5000 Pa
0 ...+100 Pa
–1000...+1000 Pa
–5000...+5000 Pa
O N
O N
Measuring range mode
(Mode selectable)
DIP 3
Output damping
(Strength and length-adjustable)
DIP 4
Zero point calibration
(Function adjustable)
DIP 6
Unidirectional ( 0 ...+MR )
OFF
Long (10 s)
OFF
Pushbutton (auto zero)
OFF
Bidirectional (–MR ...+MR )
O N
Small (1 s)
O N
Potentiometer (offset)
O N