S+S Regeltechnik AERASGARD RFTM- LQ-PS-CO2-Modbus Скачать руководство пользователя страница 14

14

AERASGARD

®

    RFTM - LQ - PS - CO2 - Modbus 

Rev.  2021 - V30

Multifunctional indoor climate sensor 

AERASGARD

® 

RFTM - LQ

 

- PS

 

- CO2 Modbus

 

(maximum expansion level) with Modbus connection, in an elegant 

plastic housing with snap-on lid, base with 4-hole attachment, optionally with ⁄ without display, type variant 

RFTM - CO2 Modbus

 optionally with ⁄ 

without setpoint potentiometer. 
The room sensor is used to detect the measurands air humidity (0...100 %  r.H.), temperature (0...+50°C), air quality (0…100 %  VOC), fine dust (PM) 

(0...1000 µg/m) and CO2

  

content (0...5000 ppm) as well as a room control unit (% setpoint). 

Use just one device to monitor and control the entire indoor climate effectively. This enables energy-saving room ventilation on an as-needed basis, 

thereby reducing operating costs and improving well-being. It is used in offices, hotels, convention centres, apartments, shops, etc. 
A long-term stable, 

digital humidity and temperature sensor

 guarantees exact measurement results. The air quality is determined based on a 

(VOC) 

mixed gas sensor

. The CO2 content of the air is measured using an optical 

NDIR sensor

 (non-dispersive infra-red technology). 

 

An optical 

particulate sensor

 precisely detects 

fine dust (PM)

 of the size category 0.3 to 10 micrometers.  The sensor is factory-calibrated; an  

environmental precision adjustment by an expert is possible. One sensor for every 30 m² of space is recommended.

Modbus sensor

 with galvanically separated RS485 Modbus interface, selectable bus termination resistance, DIP switches for setting the bus parameters 

and bus address in the currentless state, LEDs for telegram status display and two-line display (illuminated; with customised programming in the 

7-segment and dot-matrix range). 

TECHNICAL DATA

Power supply:  

24 V AC ⁄ DC (± 10 %)

Power  consumption:  

typically  <  4.4 W ⁄ 24 V DC;  <  6.4 VA ⁄ 24 V AC;  peak current 200  mA

Data points: 

temperature [°C], relative humidity [% r.H.], air quality (VOC) [%,ppb],  

fine dust (PM) [µg/m

3

], carbon dioxide (CO2) [ppm], setpoint potentiometer [%]

HUMIDITY & TEMPERATURE

  

Sensor (RH / °C): 

digital humidity sensor with integrated temperature sensor,

 low hysteresis, high long-term stability

Deviation (RH):  

typically 

± 2.0 % 

(20...80 %  r. H.)  at  +25 °C,  otherwise  ± 3.0 %

Deviation  (°C):  

typically  ±  0.2 K  at  +25 °C

AIR QUALITY  (VOC)

Sensor (VOC): 

VOC sensor 

(metal oxide) 

with automatic calibration

 

(VOC = volatile organic compounds)

Measuring range (VOC): 

0...100 % air quality; with reference to calibration gas; 

multi-range switching  VOC sensitivity low, medium, high

Measuring accuracy (VOC):  

typically ± 20 % final value  (with reference to the calibration gas) 

Service life (VOC):  

> 60 months  (under normal load conditions)

FINE DUST

  

(PM)

Sensor (PM): 

optical 

fine-dust sensor

 (

PM

 = particulate matter),  

particulate sensor with laser- and soiling-resistant technology

Measuring range (PM):  

0...1000 µg/m

3

Particle size (PM):  

PM

 

2.5

  (0.3...2.5 µm);  

PM

 

10

  (0.3...10 µm)

Measuring accuracy (PM):  

typically  ± 10 µg/m

3

  (± 10 % of measured value)  at PM 2.5 

typically ± 25 µg/m

3

  (± 25 % of measured value)  at PM 10

Long-term stability (PM):  

± 1.25 µg/m

3

  (± 1.25 % of measured value/year)  

Service life (PM):  

> 10  years 

CARBON DIOXIDE  (CO2)

Sensor  (CO2):   

optical 

NDIR sensor

 (non-dispersive infra-red technology) 

with manual calibration (via zero button) 

with automatic calibration (can be deactivated via Modbus) 

Measuring  range  (CO2):  

0…5000  ppm

Measuring accuracy (CO2):  

typically ± 30 ppm  (± 3 % of measured value)

Temperature   

± 5 ppm   ⁄  °C    or    ± 0.5 %  of  measured  value   ⁄  °C

dependence (CO2):  

  (whichever is greater)

Pressure dependence (CO2):   ± 0.13 %  ⁄ mm Hg
Long-term stability (CO2):  

< 2 % in 15 years

Gas exchange (CO2):  

Diffusion

Ambient  temperature:  

0...+ 50 °C     

Permitted humidity: 

0…95 % r. H.  (non-precipitating air)

Warm up time:  

approx. 1 hour 

Response time:  

< 2 minutes

Electrical  connection:  

0.2 - 1.5 mm

2

,  via push-in terminal

Housing:  

plastic, material ABS, colour pure white (similar to RAL 9010) 

Dimensions:  

98   x   98 x   33 mm    (Baldur 2)

Mounting:  

wall mounting or on in-wall flush box, Ø 55 mm, base with 4 holes, for attachment  

to vertically or horizontally installed in-wall flush boxes for rear cable entry,  

with predetermined breaking point for top/bottom cable entry for surface-mounted installation 

Protection class:  

III  (according to EN 60 730)

Protection  type:  

IP 30

  (according to EN 60 529)

Standards:  

CE conformity, electromagnetic compatibility according to EN 61 326,  

EMC Directive 2014 ⁄ 30 ⁄ EU, Low Voltage Directive 2014 ⁄ 35 ⁄ EU 

Optional:  

Display with illumination, 

2-line,  cutout  approx. 36 x 15 mm  (W x H),   

to display actual humidity, actual temperature, air quality, of the fine-dust and CO2 content (cyclic)  

or a selectable parameter (static) or an individually programmable display value

Содержание AERASGARD RFTM- LQ-PS-CO2-Modbus

Страница 1: ...midity temperature air quality VOC fine dust PM and CO2 content calibratable with Modbus connection F Notice d instruction Sonde d ambiance multifonctions resp convertisseur de mesure pour l humidit l...

Страница 2: ...O2 Modbus D G F r T K 6 0 98 98 32 6 T K 6 0 98 98 32 6 34 6 RCO2 Modbus RLQ CO2 Modbus RFTM CO2 Modbus RFTM LQ CO2 Modbus RFTM CO2 Modbus P Ma zeichnung Dimensional drawing Plan cot Ma zeichnung Dime...

Страница 3: ...e Langzeitstabilit t Abweichung RH typisch 2 0 20 80 r H bei 25 C sonst 3 0 Abweichung C typisch 0 2 K bei 25 C LUFTQUALIT T VOC Sensor VOC VOC Sensor Metalloxid mit automatischer Kalibrierung volatil...

Страница 4: ...us Taster Potentio meter RFTM CO2 Modbus P R xx Modbus AERASGARD Rxx Modbus Raumf hler bzw Messumformer f r Feuchte Temperatur Luftqualit t VOC Feinstaub PM und CO2 Gehalt Deluxe Typ WG02 Messbereiche...

Страница 5: ...und damit nicht der werksseitigen Kalibrierung entsprechen vom Kunden eingestellt werden Hierbei ist zu beachten dass die Werkskalibrierung verloren geht und die Einhaltung der technischen Daten nicht...

Страница 6: ...sunterbrechung k rzer 7 Tage kann der Berechnungs algorithmus durch eine manuelle Kalibrierung unterst tzt werden um eine schnellere Anpassung des Korrekturwertes zu erreichen Manuelle Kalibrierung de...

Страница 7: ...Stoppbits OFF inaktiv default OFF inaktiv OFF Die Baudrate bertragungsgeschwindigkeit wird ber Pos 1 und 2 des DIP Schalters B eingestellt Einstellbar sind 9600 Baud 19200 Baud oder 38400 Baud siehe...

Страница 8: ...ich programmiert werden Somit k nnen auch beispielsweise Meldungen von der SPS angezeigt werden F r die individuelle Anzeige muss das Register 4x0001 physikalischer Anzeigewert den Wert 10 enthalten D...

Страница 9: ...ameter Data Type Value Range 3x0001 CO2 Abtastung 4 s Signed 16 Bit 350 5000 350 5000 ppm 3x0002 CO2 Filterung 32 s Signed 16 Bit 350 5000 350 5000 ppm 3x0003 VOC in Abtastung 4 s Signed 16 Bit 0 1000...

Страница 10: ...C Unsigned 8 Bit 0 255 ASCII Zeichen 4x0009 Dot Matrix Zeichen D Unsigned 8 Bit 0 255 ASCII Zeichen 4x0010 Dot Matrix Zeichen E Unsigned 8 Bit 0 255 ASCII Zeichen 4x0011 Dot Matrix Zeichen F Unsigned...

Страница 11: ...er Exception Meldungen Unsigned 16 Bit Fehlerz hler 14 Z hler Slave Telegramme Unsigned 16 Bit Slave Telegramme 15 Z hler Telegramme ohne Antwort Unsigned 16 Bit Broadcastmeldungen Adresse 0 Function...

Страница 12: ...r getrennte Segmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden F r die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferabschirmgefl...

Страница 13: ...nahme der Ger te darf nur durch Fachpersonal erfolgen Es gelten ausschlie lich die technischen Daten und Anschlussbedingungen der zum Ger t gelieferten Montage und Bedienungs anleitung Abweichungen zu...

Страница 14: ...iation C typically 0 2 K at 25 C AIR QUALITY VOC Sensor VOC VOC sensor metal oxide with automatic calibration VOC volatile organic compounds Measuring range VOC 0 100 air quality with reference to cal...

Страница 15: ...TM LQ PS CO2 Modbus RFTM LQ PS CO2 Modbus 0 100 r H 0 50 C 0 1000 g m3 5000 ppm 0 100 1501 2119 6001 500 RFTM LQ PS CO2 Modbus LCD 0 100 r H 0 50 C 0 1000 g m3 5000 ppm 0 100 1501 2119 6021 500 Note T...

Страница 16: ...on site conditions which do not correspond to the function domain and thus the factory calibration Here it should be noted that the factory calibration will be lost and technical data compliance can n...

Страница 17: ...perating period In case of power disruptions of less than 7 days the calculation algorithm may be supported with a manual calibration to adjust the correction value more quickly Manual calibration of...

Страница 18: ...ctive ON ODD numbered OFF Inactive no parity 2 stop bits OFF Inactive default OFF Inactive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 9...

Страница 19: ...e and in the dot matrix range This means that messages such as those from the PLC can be displayed For the individual display the register 4x0001 physical value displayed must contain the value 10 The...

Страница 20: ...ue Range 3x0001 CO2 Sampling 4 s Signed 16 Bit 350 5000 350 5000 ppm 3x0002 CO2 Filtering 32 s Signed 16 Bit 350 5000 350 5000 ppm 3x0003 VOC in Sampling 4 s Signed 16 Bit 0 1000 0 0 100 0 VOC 3x0004...

Страница 21: ...t Matrix Character C Unsigned 8 Bit 0 255 ASCII character 4x0009 Dot Matrix Character D Unsigned 8 Bit 0 255 ASCII character 4x0010 Dot Matrix Character E Unsigned 8 Bit 0 255 ASCII character 4x0011 D...

Страница 22: ...ams Unsigned 16 bit Error counter 14 Counter slave telegrams Unsigned 16 bit Slave telegrams 15 Counter telegrams without answer Unsigned 16 bit Broadcast messages address 0 Function 17 Report Slave I...

Страница 23: ...ubscribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supp...

Страница 24: ...mounting and operating instructions delivered together with the device are exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of tech...

Страница 25: ...typique 2 0 20 80 h r 25 C sinon 3 0 cart C typique 0 2 K 25 C QUALIT DE L AIR COV Capteur COV capteur COV oxyde m tallique avec talonnage automatique volatile organic compounds compos s organiques vo...

Страница 26: ...r 0 50 C 0 1000 g m3 5000 ppm 0 100 1501 2119 6001 500 RFTM LQ PS CO2 Modbus LCD 0 100 h r 0 50 C 0 1000 g m3 5000 ppm 0 100 1501 2119 6021 500 Remarque Ces appareils ne doivent pas tre utilis s comm...

Страница 27: ...les appareils doivent tre r gl s par le client selon les conditions sur place qui ne correspondent pas au champ de d finition et l talonnage d usine Noter que dans ce cas l talonnage d usine est perd...

Страница 28: ...n est calcul e pour la dur e de fonctionnement En cas de coupure de tension inf rieure 7 jours l algorithme de calcul peut tre accompagn par une l talonnage manuel afin que la valeur de correction soi...

Страница 29: ...de Baud vitesse de transfert est r gl via les pos 1 et 2 de l interrupteur DIP B On peut r gler 9600 Baud 19200 Baud ou 38400 Baud voir tableau La parit est r gl e via la pos 3 de l interrupteur DIP B...

Страница 30: ...14 segments que dans la zone de matrice de point Il est ainsi possible par exemple d afficher les messages de l API Pour l affichage librement programmable le registre 4x0001 valeur d affichage physi...

Страница 31: ...re Param tre Data Type Value Range 3x0001 CO2 Balayage 4 s Signed 16 Bit 350 5000 350 5000 ppm 3x0002 CO2 Filtrage 32 s Signed 16 Bit 350 5000 350 5000 ppm 3x0003 COV en Balayage 4 s Signed 16 Bit 0 1...

Страница 32: ...caract re C Unsigned 8 Bit 0 255 Caract res ASCII 4x0009 Matrice de points caract re D Unsigned 8 Bit 0 255 Caract res ASCII 4x0010 Matrice de points caract re E Unsigned 8 Bit 0 255 Caract res ASCII...

Страница 33: ...on s 13 Compteur Messages d exception Unsigned 16 Bit Compteur d erreurs 14 Compteur T l grammes esclaves Unsigned 16 Bit T l grammes esclaves 15 Compteur T l grammes sans r ponse Unsigned 16 Bit Mess...

Страница 34: ...s doit tre r parti en plusieurs segments par l interm diaire de repeaters L adresse des correspondants peut tre fix e de 1 247 Pour la ligne de bus on peut utiliser un c ble avec ligne de donn es alim...

Страница 35: ...urs commises sur cet appareil L installation et la mise en service des appareils doit tre effectu e uniquement par du personnel qualifi Seules les donn es techniques et les conditions de raccordement...

Страница 36: ...24 200 C VOC 1 3 CO2 1 C 2 0 20 80 25 C 3 0 C 0 2 25 C VOC VOC VOC VOC VOC 0 100 VOC low medium high VOC 20 VOC 60 0 1000 3 PM 2 5 0 3 2 5 PM 10 0 3 10 10 3 10 PM 2 5 25 3 25 PM 10 1 25 3 1 25 10 CO2...

Страница 37: ...LCD 0 100 0 50 C 0 1000 3 5000 1 0 100 1501 2119 6021 500 1 2 3 4 1 2 3 4 shield shield U GND A B U GND A B mode address zero offset CO CO VOC VOC r H C 1 2 3 4 5 6 7 8 ON DIPA 1 2 3 4 5 6 ON DIPB DIP...

Страница 38: ...38 r CO2 350 1 0 10 30 50 1 2 3 50 CO2 350 500 1 15 20 Modbus CO2 350 500 1 1 2 ZERO CO2 5 AUTO 0 5 600 3 4 10 350 500 1...

Страница 39: ...39 r VOC 15 20 7 VOC 1 15 2 ZERO VOC 5 AUTO 0 5 60 3 60 VOC...

Страница 40: ...P DIP 1 128 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBUS DIP B 9600 ON...

Страница 41: ...er 68 6 7 14 4x0001 10 4 0002 4 0012 4x0001 0 7 4x0005 0 A 1 B 2 C 3 D 4 DP 5 6 7 8 9 10 11 12 13 14 15 A A B C D E F G B C D 14 1 14 2 DP 14 4x0003 4x0004 0 A 1 B 2 C 3 D 4 E 5 F 6 G 7 G 8 H 9 I 10 J...

Страница 42: ...8 l 109 m 110 n 111 o 112 p 113 q ASCII 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 132 142 148 153 154 223 ASCII 04 Read Input Register 3x0001 CO2 4 16 350 5000 350 5000 1 3...

Страница 43: ...0 255 ASCII 4x0009 D 8 0 255 ASCII 4x0010 8 0 255 ASCII 4x0011 F 8 0 255 ASCII 4x0012 G 8 0 255 ASCII 4x0020 8 0 63 0 100 4x0021 CO2 16 512 511 4x0022 16 512 511 4x0023 16 512 511 4x0024 16 512 511 05...

Страница 44: ...Reset Listen Only Mode 04 Listen Only Mode 10 11 16 12 CRC 16 13 16 14 16 15 16 0 17 Report Slave ID 00 8 6 01 8 AERSGARD MODBUS 17 T H V P C 18 T H V C 19 T H C 20 T H 21 T H P T H V VOC P PM C CO2...

Страница 45: ...bus 32 1 247 100 Profibus Slave n MODBUS RTU Master RS 485 20 n 40 n Slave 1 Slave 2 LA LA A D1 D GND B D0 D MODBUS RTU Master Slave 1 Slave 2 5 B RBIAS RBIAS RAB RAB r AERASGARD RFTM LQ PS CO2 Modbus...

Страница 46: ...46 r VOC 10 95 0 50 C VOC CO2 VOC ZVEI VDE EMV VDE VDI 0 5 g...

Страница 47: ...dge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are us...

Страница 48: ...120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1...

Отзывы: