S+S Regeltechnik AERASGARD AFTM- LQ-CO2 -Modbus Скачать руководство пользователя страница 1

AERASGARD

® 

AFTM - LQ - CO

2

 - Modbus 

AERASGARD

® 

KFTM - LQ - CO

2

 - Modbus 

D G F r

Herzlichen Glückwunsch!  
Sie haben ein deutsches Qualitätsprodukt erworben.
Congratulations!  
You have bought a German quality product.
Félicitations !    
Vous avez fait l’acquisition d’un produit allemand de qualité.
Примите наши поздравления !   
Вы приобрели качественный продукт, изготовленный в Германии.

D

  

Bedienungs- und Montageanleitung

Multifunktionaler Kanal-/Aufputzfühler bzw. Messumformer, 
für Feuchte, Temperatur, Luftgüte (VOC) und CO

2

 - Gehalt,   

kalibrierfähig, mit 

Modbus

-Anschluss

G

  

Operating Instructions, Mounting & Installation

Multifunctional duct/on-wall sensors and measuring transducers, 
for humidity, temperature, air quality (VOC) and CO

2

 content,  

calibratable, with 

Modbus 

connection

F

  

Notice d’instruction

Sonde (transmetteur) de gaine/en saillie multifonctionnelle, 
pour l'humidité, la température,  
la qualité d'air (COV) et de teneur en CO

2

,  

étalonnable, avec raccordement

 Modbus  

r

  

Руководство по монтажу и обслуживанию

Мультифункциональный канальный датчик ⁄  датчик для  
открытой установки и измерительный преобразователь,  
для измерения влажности, температуры,  
качества воздуха (VOC) и содержания CO

2

,  

калибруемый, с подключением к шине 

Modbus

S+S REGELTECHNIK GMBH 
PIRNAER STRASSE 20 
90411 NÜRNBERG ⁄ GERMANY

FON  +49 (0) 911 ⁄ 5 19  47- 0 
FAX  +49 (0) 911 ⁄ 5 19  47- 70

[email protected] 
www.SplusS.de

6000-3480-0000-1XX   

34800-2019  V103

    05  ⁄  2019

Содержание AERASGARD AFTM- LQ-CO2 -Modbus

Страница 1: ...Multifunctional duct on wall sensors and measuring transducers for humidity temperature air quality VOC and CO2 content calibratable with Modbus connection F Notice d instruction Sonde transmetteur de gaine en saillie multifonctionnelle pour l humidité la température la qualité d air COV et de teneur en CO2 étalonnable avec raccordement Modbus r Руководство по монтажу и обслуживанию Мультифункцион...

Страница 2: ... Габаритный чертеж Tyr 2 202 5 126 112 90 50 ø 20 112 20 4 ø32 3 13 4 M16x1 5 60 87 30 32 62 M4 ø5 2 ø20 M16x1 5 200 126 112 90 50 ø 20 112 20 4 ø32 3 13 4 35 112 90 ø32 3 32 M16x1 5 M16x1 5 60 87 30 32 62 M4 ø5 2 ø20 126 112 90 50 4 20 112 M16x1 5 35 50 126 90 112 20 4 M16x1 5 137 112 4 M16x1 5 ø16 35 50 126 112 20 4 M16x1 5 137 32 112 20 4 M16x1 5 134 ø16 4 M16x1 5 ø16 ...

Страница 3: ...bilität Sensorschutz Kunststoff Sinterfilter Ø 16 mm L 35 mm austauschbar optional Metall Sinterfilter Ø 16 mm L 32 mm Messbereich Feuchte 0 100 r H Arbeitsbereich Feuchte 0 95 r H ohne Betauung Abweichung Feuchte typisch 2 0 20 80 r H bei 25 C sonst 3 0 TEMPERATUR Messbereich Temperatur 35 80 C Arbeitsbereich Temperatur 10 60 C Abweichung Temperatur typisch 0 2 K bei 25 C LUFTQUALITÄT VOC Sensor ...

Страница 4: ...m Display die Mess werte mit den entsprechenden Einheiten zyklisch nacheinander angezeigt CO2 Gehalt in ppm Luft qualität VOC in Temperatur in C relative Feuchte in r H Zur besseren Ablesbarkeit ist eine Hintergrund beleuchtung vorhanden Über die Modbusschnittstelle kann das Display sowohl im 7 Segment Bereich als auch im Dot Matrix Bereich individuell programmiert werden Anzeige Standard Anzeige ...

Страница 5: ...5000 ppm 1501 7110 6001 200 ACO2 MODBUS LCD 5000 ppm 1501 7110 6071 200 ALQ CO2 Modbus ALQ CO2 MODBUS 5000 ppm 0 100 1501 7111 6001 200 ALQ CO2 MODBUS LCD 5000 ppm 0 100 1501 7111 6071 200 AFTM CO2 Modbus AFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 7116 6001 200 AFTM CO2 MODBUS LCD 0 100 r H 35 80 C 5000 ppm 1501 7116 6071 200 AFTM LQ CO2 Modbus AFTM LQ CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 0 ...

Страница 6: ... 5000 ppm 1501 8110 6001 200 KCO2 MODBUS LCD 5000 ppm 1501 8110 6071 200 KLQ CO2 Modbus KLQ CO2 MODBUS 5000 ppm 0 100 1501 8111 6001 200 KLQ CO2 MODBUS LCD 5000 ppm 0 100 1501 8111 6071 200 KFTM CO2 Modbus KFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 8116 6001 200 KFTM CO2 MODBUS LCD 0 100 r H 35 80 C 5000 ppm 1501 8116 6071 200 KFTM LQ CO2 Modbus KFTM LQ CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 0...

Страница 7: ...Stoppbits OFF inaktiv default OFF inaktiv OFF Die Baudrate Übertragungsgeschwindigkeit wird über Pos 1 und 2 des DIP Schalters B eingestellt Einstellbar sind 9600 Baud 19200 Baud oder 38400 Baud siehe Tabelle Die Parity wird über Pos 3 des DIP Schalters B eingestellt Einstellbar sind EVEN gerade oder ODD ungerade siehe Tabelle Die Parity Sicherung wird über Pos 4 des DIP Schalters B aktiviert Eins...

Страница 8: ...ge sowohl im 7 Segment Bereich als auch im Dot Matrix Bereich programmiert werden Somit können auch beispielsweise Meldungen von der SPS angezeigt werden Für die individuelle Anzeige muss das Register 4x0001 physikalischer Anzeigewert den Wert 10 enthalten Die Register 4x0002 bis 4x0019 enthalten Informationen über die darzustellenden Zeichen und Segmente Der Dot Matrix Bereich ist ebenfalls in de...

Страница 9: ...67 C 68 D 69 E 70 F 71 G 72 H ASCII Sign 73 I 74 J 75 K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Sign 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII Sign 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 ü 132 ä 142 Ä 148 ö 153 Ö 154 Ü 223 Nicht in der Tabelle aufg...

Страница 10: ...in C relative Feuchte in r H 0 Default einstellung alternative Anzeige statisch CO2 in ppm 1 1 VOC in 2 2 Temperatur in C 3 3 relative Feuchte in r H 4 4 atm Luftdruck in hPa 5 5 frei konfigurierbare Anzeige 10 4x0002 7 Segment Wert Signed 16 Bit 999 9999 999 9999 4x0003 7 Segment Wert Signed 8 Bit 9 99 9 99 4x0004 4x0005 Segment Muster Unsigned 16 Bit siehe Bitmuster 4x0006 Dot Matrix Zeichen A U...

Страница 11: ...ode Echo Telegramm 04 Aktivierung Listen Only Mode Keine Antwort 10 Lösche Zähler Echo Telegramm 11 Zähler Bustelegramme Unsigned 16 Bit alle gültigen Bustelegramme 12 Zähler Kommunikationsfehler Parity CRC Framefehler etc Unsigned 16 Bit fehlerhafte Bustelegramme 13 Zähler Exception Meldungen Unsigned 16 Bit Fehlerzähler 14 Zähler Slave Telegramme Unsigned 16 Bit Slave Telegramme 15 Zähler Telegr...

Страница 12: ...ere über Repeater getrennte Segmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden Für die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferabschirmgeflecht zu verwenden Der Kapazitätsbelag der Leitung sollte dabei kleiner 100 pF m betragen z B Profibusleitung Slave n MODBUS RTU Master RS 485 Leitungs abschluss Leitungs abschluss Akti...

Страница 13: ... gemachten Hinweise sind zu beachten Die Geräte sind im spannungslosen Zustand anzuschließen Der Anschluss der Geräte darf nur an Sicherheitskleinspannung er folgen Folge schäden welche durch Fehler an diesem Gerät entstehen sind von der Gewährleistung und Haftung ausgeschlossen Montage und Inbetriebnahme der Geräte darf nur durch Fachpersonal erfolgen Es gelten ausschließlich die technischen Date...

Страница 14: ...otection plastic sinter filter Ø 16 mm L 35 mm exchangeable optional metal sinter filter Ø 16 mm L 32 mm Measuring range humidity 0 100 r H Operating range humidity 0 95 r H without dew formation Deviation of humidity typically 2 0 20 80 r H at 25 C otherwise 3 0 TEMPERATURE Measuring range temperature 35 80 C Operating range temperature 10 60 C Deviation temperature typically 0 2 K at 25 C AIR QU...

Страница 15: ...icates the following measurements with the corresponding units cyclically and consecutively CO2 content in ppm air quality VOC in temperature in C relative humidity in r H Backlighting is provided for improved legibility The Modbus interface allows the display to be individually configured both in the 7 segment range and in the dot matrix range Display standard Display alternative output variables...

Страница 16: ...O2 Modbus ACO2 MODBUS 5000 ppm 1501 7110 6001 200 ACO2 MODBUS LCD 5000 ppm 1501 7110 6071 200 ALQ CO2 Modbus ALQ CO2 MODBUS 5000 ppm 0 100 1501 7111 6001 200 ALQ CO2 MODBUS LCD 5000 ppm 0 100 1501 7111 6071 200 AFTM CO2 Modbus AFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 7116 6001 200 AFTM CO2 MODBUS LCD 0 100 r H 35 80 C 5000 ppm 1501 7116 6071 200 AFTM LQ CO2 Modbus AFTM LQ CO2 MODBUS 0 100 r...

Страница 17: ...odbus KCO2 MODBUS 5000 ppm 1501 8110 6001 200 KCO2 MODBUS LCD 5000 ppm 1501 8110 6071 200 KLQ CO2 Modbus KLQ CO2 MODBUS 5000 ppm 0 100 1501 8111 6001 200 KLQ CO2 MODBUS LCD 5000 ppm 0 100 1501 8111 6071 200 KFTM CO2 Modbus KFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 8116 6001 200 KFTM CO2 MODBUS LCD 0 100 r H 35 80 C 5000 ppm 1501 8116 6071 200 KFTM LQ CO2 Modbus KFTM LQ CO2 MODBUS 0 100 r H 3...

Страница 18: ...ive default OFF Inactive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 9600 baud 19200 baud or 38400 baud see table Parity is set at DIP switch 3 of DIP switch block B Selectable are EVEN or ODD see table Parity check is activated via DIP switch 4 of DIP switch block B Selectable are active 1 stop bit or inactive 2 stop bits i e no pari...

Страница 19: ...to be individually configured both in the 7 segment range and in the dot matrix range This means that messages such as those from the PLC can be displayed For the individual display the register 4x0001 physical value displayed must contain the value 10 The registers 4x0002 to 4x0019 contain information about the characters and segments to be displayed The dot matrix area is also programmable in th...

Страница 20: ...5 K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Sign 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII Sign 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 ü 132 ä 142 Ä 148 ö 153 Ö 154 Ü 223 ASCII characters or control characters are displayed as spaces G HYGRASGARD A...

Страница 21: ...r H 0 Default setting alternative display static CO2 in ppm 1 1 VOC in 2 2 Temperature in C 3 3 Relative humidity in r H 4 4 Atmospheric pressure in hPa 5 5 Freely configurable display 10 4x0002 7 Segment Value Signed 16 bit 999 9999 999 9999 4x0003 7 Segment Value Signed 8 bit 9 99 9 99 4x0004 4x0005 Segment Pattern Unsigned 16 bit See Binary Pattern 4x0006 Dot Matrix Character A Unsigned 8 bit 0...

Страница 22: ...Echo telegram 04 Activation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 bit All valid bus telegrams 12 Counter communication errors Parity CRC frame errors etc Unsigned 16 bit Faulty bus telegrams 13 Counter exception telegrams Unsigned 16 bit Error counter 14 Counter slave telegrams Unsigned 16 bit Slave telegrams 15 Counter telegrams without an...

Страница 23: ...e number of subscribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply line and copper mesh wire shield must be used Therefore the line capacitance should be less than 100 pF m e g Profibus cable Slave n MODBUS RTU Master RS 485 Line termination Line term...

Страница 24: ... to be regarded Devices are to be connected under dead voltage condition Devices must only be connected to safety extra low voltage Consequential damages caused by a fault in this device are excluded from warranty or liability Installation of these devices must only be realized by author ized qualified personnel The technical data and connecting conditions shown on the device labels and in the mou...

Страница 25: ...umidité numérique avec capteur de température intégré petite hystérésis stabilité à long terme Protection du capteur Filtre fritté en matière synthétique Ø 16 mm L 35 mm remplaçable en option filtre fritté en métal Ø 16 mm L 32 mm Plage de mesure humidité 0 100 h r Plage de service humidité 0 95 h r sans condensation Incertitude de mesure humidité typique 2 0 20 80 h r à 25 C sinon 3 0 TEMPÉRATURE...

Страница 26: ...es sont affichées de manière cyclique les unes après les autres dans l écran avec les unités correspondantes Teneur en CO2en ppm qualité de l air COV en température en C humidité relative en h r Un écran rétro éclairé est disponible pour une meilleure lisibilité Via l interface Modbus l écran peut aussi bien être programmé de manière individuelle dans la zone à 7 segments que dans la zone de matri...

Страница 27: ...écran COV référence ACO2 Modbus ACO2 MODBUS 5000 ppm 1501 7110 6001 200 ACO2 MODBUS LCD 5000 ppm 1501 7110 6071 200 ALQ CO2 Modbus ALQ CO2 MODBUS 5000 ppm 0 100 1501 7111 6001 200 ALQ CO2 MODBUS LCD 5000 ppm 0 100 1501 7111 6071 200 AFTM CO2 Modbus AFTM CO2 MODBUS 0 100 h r 35 80 C 5000 ppm 1501 7116 6001 200 AFTM CO2 MODBUS LCD 0 100 h r 35 80 C 5000 ppm 1501 7116 6071 200 AFTM LQ CO2 Modbus AFTM...

Страница 28: ...CO2 écran COV référence KCO2 Modbus KCO2 MODBUS 5000 ppm 1501 8110 6001 200 KCO2 MODBUS LCD 5000 ppm 1501 8110 6071 200 KLQ CO2 Modbus KLQ CO2 MODBUS 5000 ppm 0 100 1501 8111 6001 200 KLQ CO2 MODBUS LCD 5000 ppm 0 100 1501 8111 6071 200 KFTM CO2 Modbus KFTM CO2 MODBUS 0 100 h r 35 80 C 5000 ppm 1501 8116 6001 200 KFTM CO2 MODBUS LCD 0 100 h r 35 80 C 5000 ppm 1501 8116 6071 200 KFTM LQ CO2 Modbus ...

Страница 29: ...ux de Baud vitesse de transfert est réglé via les pos 1 et 2 de l interrupteur DIP B On peut régler 9600 Baud 19200 Baud ou 38400 Baud voir tableau La parité est réglée via la pos 3 de l interrupteur DIP B On peut régler EVEN paire ou ODD impaire voir tableau La protection par parité sécurité par parité est activée via la pos 4 de l interrupteur DIP B On peut régler une correction d erreur sécuris...

Страница 30: ...ran peut aussi bien être programmé dans la zone à 7 segments que dans la zone de matrice de point Il est ainsi possible par exemple d afficher les messages de l API Pour l affichage librement programmable le registre 4x0001 valeur d affichage physique doit contenir la valeur 10 Les registres 4x0002 à 4x0019 contiennent des informations sur les caractères et segments à afficher La zone de matrice d...

Страница 31: ...64 65 A 66 B 67 C 68 D 69 E 70 F 71 G 72 H ASCII Sign 73 I 74 J 75 K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Sign 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII Sign 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 ü 132 ä 142 Ä 148 ö 153 Ö 154 Ü 223 Les caractèr...

Страница 32: ... COV en 2 2 Température en C 3 3 Humidité relative en r H 4 4 Pression atmosph en hPa 5 5 Affichage librement configurable 10 4x0002 Valeur 7 segments Signed 16 Bit 999 9999 999 9999 4x0003 Valeur 7 segments Signed 8 Bit 9 99 9 99 4x0004 4x0005 Modèle du segment Unsigned 16 Bit voir le modèle binaire 4x0006 Matrice de points caractère A Unsigned 8 Bit 0 255 Caractères ASCII 4x0007 Matrice de point...

Страница 33: ... écho 04 Activation Listen Only Mode mode Écoute seule Pas de réponse 10 Efface compteur Télégramme d écho 11 Compteur Télégrammes de bus Unsigned 16 Bit Tous les télégrammes de bus valides 12 Compteur Erreur de communication Parité CRC erreur Frame etc Unsigned 16 Bit Télégrammes de bus erronés 13 Compteur Messages d exception Unsigned 16 Bit Compteur d erreurs 14 Compteur Télégrammes esclaves Un...

Страница 34: ...dants le bus doit être réparti en plusieurs segments par l intermédiaire de repeaters L adresse des correspondants peut être fixée de 1 à 247 Pour la ligne de bus on peut utiliser un câble avec ligne de données alimentation tension câblées par paire et treillis de blindage en cuivre La capacité linéique de la ligne doit rester inférieure à 100 pF m p ex ligne Profibus Slave n MODBUS RTU Master RS ...

Страница 35: ...notice et toutes les consignes qui y sont précisées Les raccordements électriques doivent être exécutés HORS TENSION Veillez à ne brancher l appareil que sur un réseau de très basse tension de sécurité Nous déclinons toute responsabilité ou garantie au titre de tout dommage consécutif provoqué par des erreurs commises sur cet appareil L installation des appareils ne doit être effectuée que par du ...

Страница 36: ...5 мм сменный элемента опционально металлокерамический фильтр Ø 16 мм L 32 мм Диапазон измерения влажности 0 100 относительной влажности Рабочий диапазон влажности 0 95 относительной влажности без конденсата Погрешность измерения влажности обычно 2 0 20 80 отн влажности при 25 C иначе 3 0 ТЕМПЕРАТУРА Диапазон измерения температуры 35 80 C Рабочий диапазон температур 10 60 C Погрешность измерения те...

Страница 37: ...очередно и циклично отображаются следующие измеренные значения с соответствующими единицами измерения содержание углекислого газа млн 1 качество воздуха VOC температура C относительная влажность отн влажн Улучшенная считываемость благодаря фоновой подсветке Посредством шинного интерфейса дисплей можно индивидуально программировать как в 7 сегментном поле так и в поле с точечной матрицей Индивидуал...

Страница 38: ...VOC Арт ACO2 Modbus ACO2 MODBUS 5000 млн 1 1501 7110 6001 200 ACO2 MODBUS LCD 5000 млн 1 1501 7110 6071 200 ALQ CO2 Modbus ALQ CO2 MODBUS 5000 млн 1 0 100 1501 7111 6001 200 ALQ CO2 MODBUS LCD 5000 млн 1 0 100 1501 7111 6071 200 AFTM CO2 Modbus AFTM CO2 MODBUS 0 100 отн вл 35 80 C 5000 млн 1 1501 7116 6001 200 AFTM CO2 MODBUS LCD 0 100 отн вл 35 80 C 5000 млн 1 1501 7116 6071 200 AFTM LQ CO2 Modbu...

Страница 39: ...bus KCO2 MODBUS 5000 млн 1 1501 8110 6001 200 KCO2 MODBUS LCD 5000 млн 1 1501 8110 6071 200 KLQ CO2 Modbus KLQ CO2 MODBUS 5000 млн 1 0 100 1501 8111 6001 200 KLQ CO2 MODBUS LCD 5000 млн 1 0 100 1501 8111 6071 200 KFTM CO2 Modbus KFTM CO2 MODBUS 0 100 отн вл 35 80 C 5000 млн 1 1501 8116 6001 200 KFTM CO2 MODBUS LCD 0 100 отн вл 35 80 C 5000 млн 1 1501 8116 6071 200 KFTM LQ CO2 Modbus KFTM LQ CO2 MO...

Страница 40: ...й без чётности 2 стоповых бита OFF неактивный по умолчанию OFF неактивная OFF Скорость передачи данных в бодах настраивается с помощью поз 1 и 2 DIP переключателя B Можно настроить 9600 бод 19 200 бод или 38 400 бод см таблицу Чётность настраивается с помощью поз 3 DIP переключателя B Можно настроить EVEN чётные или ODD нечётные см таблицу Контроль чётности включается с помощью поз 4 DIP переключа...

Страница 41: ...измерения гПа Индекс 5 Посредством шинного интерфейса дисплей можно программировать как в 7 сегментном поле так и в поле с точечной матрицей Так например можно отображать сообщения получаемые от ПЛК Для индивидуальной индикации регистр 4x0001 физическое значение должен содержать значение 10 Регистры от 4х0002 до 4х0019 содержат сведения об отображаемых символах и сегментах При настройке по умолчан...

Страница 42: ...A 66 B 67 C 68 D 69 E 70 F 71 G 72 H ASCII Символ 73 I 74 J 75 K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Символ 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII Символ 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 ü 132 ä 142 Ä 148 ö 153 Ö 154 Ü 223 Неуказанные ...

Страница 43: ...ислого газа млн 1 температура C относительная влажность отн влажн 0 Настройка по умолчанию Альтернативная индикация статичная Содержание углекислого газа млн 1 1 1 Качество воздуха VOC 2 2 Температура C 3 3 Относительная влажность отн влажн 4 4 Атмосферное давление воздуха гПа 5 5 Настраиваемая индикация 10 4x0002 7 сегментное значение Со знаком 16 бит 999 9999 999 9999 4x0003 7 сегментное значени...

Страница 44: ...Сброс счетчиков Телеграмма эхо 11 Счетчик телеграмм шины Без знака 16 бит Все действительные телеграммы шины 12 Счетчик ошибок связи четность циклическая проверка четности с избыточностью CRC ошибка фрейма и т д Без знака 16 бит Телеграммы шины с ошибками 13 Счетчик исключительных сообщений Без знака 16 бит Счетчик ошибок 14 Счетчик телеграмм ведомого устройства Без знака 16 бит Телеграммы ведомог...

Страница 45: ...настраивать от 1 до 247 Для линии шины следует использовать кабель с парной скруткой электропитанием и медным экраном Емкость линии на единицу длины должна составлять при этом меньше 100 пФ м напр линия Profibus Slave n MODBUS RTU Master RS 485 Оконечная нагрузка шины Оконечная нагрузка шины Активное ответвление Пассивное ответвление Тупиковая линия ответвитель ный кабель Магистральная линия магис...

Страница 46: ...лжны быть учтены все приведенные в нем указания Приборы следует устанавливать в обесточенном состоянии Подключение должно осуществляться исключительно к безопасно малому напряжению Повреждения приборов вследствие несоблюдения упомянутых требований не подлежат устранению по гарантии ответственность производителя исключается Установка приборов должна осуществляться только авторизованным персоналом Д...

Страница 47: ...de modifications techniques Toutes les informations correspondent à l état de nos connaissances au moment de la publication Elles servent uniquement à informer sur nos produits et leurs possibilités d application mais n offrent aucune garantie pour certaines caractéristiques du produit Etant donné que les appareils sont soumis à des conditions et des sollicitations diverses qui sont hors de notre ...

Страница 48: ...1 1 0 1 1 1 120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1 130 1 0 0 0 0 0 1 0 131 1 0 0 0 0 0 1 1 132 1 0 0 0 0 1 0 0 133 1 0 0 0 0 1 0 1 134 1 0 0 0 0 1 1 0 135 1 0 0 0 0 1 1 1 136 1 0 0 0 1 0 0 0 137 1 0 0 0 1 0 0 1 138 1 0 0 0 1 0 1 0 139 1 0 ...