18

BUS ADDRESS

Bus address  

(binary coded, value selectable from 1 to 247)

MODBUS

DIP switch [A]

DIP 1 

DIP 2

DIP 3 

DIP 4 

DIP 5 

DIP 6 

DIP 7

DIP 8 

1 2 3 4 5 6 7 8

ON

DIP A

128

64

32

16

8

4

2

1

O N

O N

OFF

OFF

OFF

OFF

OFF

O N

Example shows  128 + 64 + 1 = 193  as Modbus address.

The device address in the range of 

1 to 247

 is set at DIP switch [A].  

For switch positions 1 to 8 see the table on the back!
Address 0 is reserved for broadcast messages.  
Addresses greater than 247 must not be assigned and are ignored by the device.  
The DIP switches are binary-coded with the following values:
DIP 1 = 

128

 ............  DIP 1 = 

ON

 

DIP 2 = 

64

 ............  DIP 2 = 

ON

 

DIP 3 =  32 ............  DIP 3 = OFF 
DIP 4 =  16 ............  DIP 4 = OFF 
DIP 5 = 

8 ............  DIP 5 = OFF  

DIP 6 = 

4 ............  DIP 6 = OFF  

DIP 7 = 

2 ............  DIP 7 = OFF 

DIP 8 = 

1

 ............  DIP 8 = 

ON

  

The switch positions shown here results in the Modbus address 

128 + 64 + 1 = 193

BUS PARAMETERS

Baud rate 

(selectable)

DIP  

DIP  

2

MODBUS

DIP switch [B]

  9600 baud

O N

OFF

1 2 3 4 5 6

ON

DIP B

19200 baud

O N

O N

38400 baud

OFF

O N

Reserved

OFF

OFF

Parity 

(selectable)

DIP 

3

Parity check 

(on / off)

DIP 

4

8N1 mode 

(on / off)

DIP 

5

Bus termination 

(on/off)

DIP 

6

EVEN   

(numbered)

O N

Active   

(1 stop bit)

O N

Active

O N

Active

O N

ODD   

(numbered)

OFF

Inactive (no parity) 

(2 stop bits)

OFF

Inactive (default)

OFF

Inactive  

OFF

The baud rate (speed of transmission) is set at DIP switches 1 and 2 of DIP switch block [B].  
Selectable are 

9600 baud, 19200 baud,

 or 

38400 baud

 – see table!

Parity

 is set at DIP switch 3 of DIP switch block [B]. 

Selectable are 

EVEN

 or 

ODD

 – see table! 

Parity check

 is activated via DIP switch 4 of DIP switch block [B].  

Selectable are 

active (1 stop bit)

, or i

nactive (2 stop bits)

, i.e. no parity check – see table! 

The 

8N1 mode

 is activated via DIP switch 5 of DIP switch block [B]. 

The functionality of DIP switch 3 (parity) and DIP switch 4 (parity check) of DIP switch block [B] is therefore deactivated. 
Selectable are 8N1

 active

 or 

inactive (default)

 – see table !. 

Bus termination

 is activated via DIP switch 6 of DIP switch block [B].  

Selectable are 

active

 (bus termination resistance of 120 Ohm), or 

inactive

 (no bus termination) – see table!

When bus parameters and bus address are changed at devices with 

display

, the respective settings are shown on the display for 

approx. 30 seconds. 

COMMUNICATION INDICATOR

Communication is indicated via two LEDs. Error-free received telegrams are signalized by the green LED lighting up, regardless of 
the device address. Faulty telegrams or triggered Modbus exception telegrams are depicted by the red LED lighting up.

DIAGNOSTICS

An error diagnostic function is integrated

HYGRASGARD

®

    AFTM-  ⁄  KFTM - LQ - CO

2

 - Modbus

  |  Configuration

 

Rev. 2017 - V14 GB intro

Содержание AERASGARD ACO2-Modbus

Страница 1: ... temperature 0 2 K at 25 C AIR QUALITY VOC VOC sensor VOC sensor metal oxide with automatic calibration VOC volatile organic compounds VOC measuring range 0 100 air quality with reference to calibration gas multi range switching VOC sensitivity low medium high VOC measuring accuracy 20 final value with reference to the calibration gas Service life 60 months under normal load conditions CARBON DIOX...

Страница 2: ...dicates the following measurements with the corresponding units cyclically and consecutively CO2 content in ppm air quality VOC in temperature in C relative humidity in r H Backlighting is provided for improved legibility The Modbus interface allows the display to be individually configured both in the 7 segment range and in the dot matrix range Display standard Display alternative output variable...

Страница 3: ... WG02 Measuring Range Humidity Temperature CO2 Display VOC Item No ACO2 Modbus ACO2 MODBUS 5000 ppm 1501 7110 6001 200 ACO2 MODBUS DISPLAY 5000 ppm 1501 7110 6071 200 ALQ CO2 Modbus ALQ CO2 MODBUS 5000 ppm 0 100 1501 7111 6001 200 ALQ CO2 MODBUS DISPLAY 5000 ppm 0 100 1501 7111 6071 200 AFTM CO2 Modbus AFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 7116 6001 200 AFTM CO2 MODBUS DISPLAY 0 100 r H ...

Страница 4: ...uring Range Humidity Temperature CO2 Display VOC Item No KCO2 Modbus KCO2 MODBUS 5000 ppm 1501 8110 6001 200 KCO2 MODBUS DISPLAY 5000 ppm 1501 8110 6071 200 KLQ CO2 Modbus KLQ CO2 MODBUS 5000 ppm 0 100 1501 8111 6001 200 KLQ CO2 MODBUS DISPLAY 5000 ppm 0 100 1501 8111 6071 200 KFTM CO2 Modbus KFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 8116 6001 200 KFTM CO2 MODBUS DISPLAY 0 100 r H 35 80 C 50...

Страница 5: ...ve default OFF Inactive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 9600 baud 19200 baud or 38400 baud see table Parity is set at DIP switch 3 of DIP switch block B Selectable are EVEN or ODD see table Parity check is activated via DIP switch 4 of DIP switch block B Selectable are active 1 stop bit or inactive 2 stop bits i e no parit...

Страница 6: ...n to be individually configured both in the 7 segment range and in the dot matrix range This means that messages such as those from the PLC can be displayed For the individual display the register 4x0001 physical value displayed must contain the value 10 The registers 4x0002 to 4x0019 contain information about the characters and segments to be displayed The dot matrix area is also programmable in ...

Страница 7: ... K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Sign 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII Sign 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 ü 132 ä 142 Ä 148 ö 153 Ö 154 Ü 223 ASCII characters or control characters are displayed as spaces G HYGRASGARD AF...

Страница 8: ...r H 0 Default setting alternative display static CO2 in ppm 1 1 VOC in 2 2 Temperature in C 3 3 Relative humidity in r H 4 4 Atmospheric pressure in hPa 5 5 Freely configurable display 10 4x0002 7 Segment Value Signed 16 bit 999 9999 999 9999 4x0003 7 Segment Value Signed 8 bit 9 99 9 99 4x0004 4x0005 Segment Pattern Unsigned 16 bit See Binary Pattern 4x0006 Dot Matrix Character A Unsigned 8 bit 0...

Страница 9: ...Echo telegram 04 Activation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 bit All valid bus telegrams 12 Counter communication errors Parity CRC frame errors etc Unsigned 16 bit Faulty bus telegrams 13 Counter exception telegrams Unsigned 16 bit Error counter 14 Counter slave telegrams Unsigned 16 bit Slave telegrams 15 Counter telegrams without an...

Страница 10: ...he number of subscribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply line and copper mesh wire shield must be used Therefore the line capacitance should be less than 100 pF m e g Profibus cable Slave n MODBUS RTU Master RS 485 Line termination Line ter...

Страница 11: ...e devices returned in original packing will be accepted These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded Devices are to be connected under dead voltage condition Devices must only be connected to safety extra low voltage Consequential damages caused by a fault in this device are excluded from war ranty or liability Insta...

Отзывы: