8. POSSIBLE MALFUNCTIONS AND THEIR CAUSES :

Malfunction:

Cause:

Remedy:

WAH does not start

No room thermostat connected or
no bridge on the thermostat jack

(Item 20)

Room thermostat incorrectly set

Gas hookup

Connect the room thermostat
or bridge to the thermostat
jack

Check setting

Check

WAH starts, ignition present
but solenoid valve does not
open ………….fault shutdown.

Safety thermostat triggered or is
defective (

Item 15

)

Automatic gas firing unit
defective 

(Item 16 )

Reset or replace

Replace

WAH starts, no ignition,
solenoid valve opens,
gas flows in….fault shutdown.

Ignition electrode defective

(Item 12)

Ignition gap too large

Ignition cable defective

 (Item 7)

Automatic gas firing unit
defective 

(Item 16 )

Replace

Reduce

Replace

Replace

WAH starts, ignition present,
solenoid valve opens, gas
flows in, is ignited …………
after several seconds fault
shutdown occurs.

Automatic gas firing unit
defective 

(Item 16 )

Ionization cable dirty or defective
(

Item 23

)

Ionization electrode dirty or
defective (

Item 17

)

Replace

Clean or replace

Clean or replace

WAH starts, ignition present,
solenoid valve opens, no gas
flows in………fault shutdown.

Gas regulator defective

 (Item 14)

Gas pressure

Nozzle clogged

Solenoid or gas line clogged

(Item 9)

Replace

Check

Clean, replace

Clean by blow-through

WAH occasionally goes to fault.

Ionization ignition electrode

(Item 17 )

Ignition

Switch box

Gas pressure

Check

Check

Check for loose contacts

Check

Содержание NG-15

Страница 1: ...0 Betriebsanleitung Operating Instructions Mode d utilisation NG 15 35 50 75 100 Gustav Nolting GmbH Neuzeitliche Heiztechnik...

Страница 2: ...stellung Montage Seite 3 4 5 Inbetriebnahme Seite 4 6 Ausserbetriebnahme Seite 4 7 Wartungsarbeiten Seite 4 8 M gliche St rungen und deren Ursachen Seite 5 9 Ersatzteillisten und Bauteile bersicht Sei...

Страница 3: ...druck bar 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 Anschlu wert kg h 0 54 1 09 1 41 2 73 1 95 3 91 2 73 5 47 3 91 7 81 Stromaufnahme A 0 48 0 48 0 48 0 60 0 92 L nge mm 500 500 650 800 1 000 Breit...

Страница 4: ...onisationselektrode dient als Flammen berwachung und ist an einen Gas feuerungsautomaten angeschlossen der die Gesamtfunktion des WLE steuert und berwacht 4 AUFSTELLUNG MONTAGE Um Personen und Sachsch...

Страница 5: ...ebungstemperatur einge stellt werden Mit dem Ventilator wird die Z ndung automatisch eingeschaltet und nach einer kurzen Vorsp lzeit das Magnetventil Pos 9 ge ffnet Nach der Flammenbildung wird die Z...

Страница 6: ...lt zu gro Z ndkabel defekt Pos 7 Gasfeuerungsautomat defekt Pos 16 Austauschen Verkleinern Austauschen Austauschen WLE l uft an Z ndung ist vor handen Magnetventil ffnet Gas str mt ein wird entz ndet...

Страница 7: ...11 Thermostromunterbrecher 102814 12 Z ndelektrode 103314 103312 103312 103311 103311 13 Piezoz nder 103315 14 Ger teregler 103040 103040 103040 103040 103040 15 Sicherheitstemperaturbegrenzer STB 100...

Страница 8: ...7 NG 15 35 50...

Страница 9: ...8 NG 75 100...

Страница 10: ...9 11 ELEKTRISCHER SCHALTPLAN Ger tetyp NG 15...

Страница 11: ...10 11 ELEKTRISCHER SCHALTPLAN Ger tetyp NG 35 50...

Страница 12: ...11 11 ELEKTRISCHER SCHALTPLAN Ger tetyp NG 75 100...

Страница 13: ...sembly Page 14 15 5 Initial operation and further start ups Page 15 6 Placing out of service Page 15 7 Maintenance Page 15 8 Possible malfunctions and their causes Page 16 9 Spare Parts List and Compo...

Страница 14: ...on pressure bar 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 Connected load kg h 0 54 1 09 1 41 2 73 1 95 3 91 2 73 5 47 3 91 7 81 Power consumption A 0 48 0 48 0 48 0 60 0 92 Length mm 500 500 650 80...

Страница 15: ...he automatic gas firing unit that controls and monitors the overall function of the WAH 4 INSTALLATION ASSEMBLY In order to prevent personal injury and property damage the relevant local building fire...

Страница 16: ...om thermostat the thermostat must be set using room temperature With fan ignition is automatically turned on and after a short pre purge time the solenoid Item 9 is opened After establishing the flame...

Страница 17: ...nition gap too large Ignition cable defective Item 7 Automatic gas firing unit defective Item 16 Replace Reduce Replace Replace WAH starts ignition present solenoid valve opens gas flows in is ignited...

Страница 18: ...l 102661 102389 102389 11 Thermo circuit breaker 102814 12 Ignition electrode 103314 103312 103312 103311 103311 13 Piezo igniter 103315 14 Device controller 103040 103040 103040 103040 103040 15 Safe...

Страница 19: ...18 NG 15 35 50...

Страница 20: ...19 NG 75 100...

Страница 21: ...20 11 ELECTRICAL CIRCUIT DIAGRAM Device Type NG 15...

Страница 22: ...21 11 ELECTRICAL CIRCUIT DIAGRAM Device Type NG 35 50...

Страница 23: ...22 11 ELECTRICAL CIRCUIT DIAGRAM Device Type NG 75 100...

Страница 24: ...llation Assemblage Pages 25 26 5 Mise sous tension Page 26 6 Mise hors tension Page 26 7 Maintenance Page 26 8 Les dysfonctionnements possibles et leurs causes Page 27 9 Liste des pi ces de rechange e...

Страница 25: ...n du gaz l entr e bar 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 2 5 10 0 D bit de gaz kg h 0 54 1 09 1 41 2 73 1 95 3 91 2 73 5 47 3 91 7 81 Consommation de courant A 0 48 0 48 0 48 0 60 0 92 Longueur mm 50...

Страница 26: ...er des dommages personnels et mat riels les r gulations en vigueur relatives la construction la protection contre les incendies ainsi que les stipulations des associations professionnelles sont respec...

Страница 27: ...p rature ambiante L allumage est enclench en m me temps que le ventilateur et apr s un bref d lai de pr rin age la vanne lectromagn tique s ouvre pos 9 Lorsque la flamme est allum e l allumage s teint...

Страница 28: ...trop grande C ble d allumage d fectueux pos 7 Br leur gaz automatique d fectueux pos 16 Remplacez R duisez Remplacez Remplacez Le GAC d marre l allumage s enclenche la vanne lectromagn tique s ouvre l...

Страница 29: ...Disjoncteur de courant thermo lectrique 102814 12 Electrode d allumage 103314 103312 103312 103311 103311 13 Pi zoallumage 103315 14 R glage de l appareil 103040 103040 103040 103040 103040 15 Limitat...

Страница 30: ...29 NG 15 35 50...

Страница 31: ...30 NG 75 100...

Страница 32: ...31 11 SCHEMA DES CONNEXIONS ELECTRIQUES Type d appareil NG 15...

Страница 33: ...32 11 SCHEMA DES CONNEXIONS ELECTRIQUES Type d appareil NG 35 50...

Страница 34: ...33 11 SCHEMA DES CONNEXIONS ELECTRIQUES Type d appareil NG 75 100...

Страница 35: ...derger tebau Blechbearbeitung Our Comprehensive Supply Program Warm Air Heaters System Construction Air Ducts Fans for air supported domes and other flexible structures Control Systems Construction Li...

Отзывы: