Description

The Reliance anti legionella valve is designed to be connected 

to a Reliance (Aquasystems) potable water expansion vessel 

with a ¾” connection. It is designed to divert a proportion of the 

water that is flowing through a system into the vessel to cause 

turbulence and encourage an exchange of water within it.

Specification

Nominal size

DN20

Max. inlet temp.

30°C

Medium

Potable Water

Dimensions 

(Vessel Supplied Separately)

Installation

Before installing the anti legionella valve ensure that the water 

system has been flushed and is free from debris and that the 

system pressures and temperatures are within the working 

parameters of the valve.

To install the anti legionella valve onto a vessel follow these 

steps.

1.  First insert the paddle retaining 

tube into the vessel connection as 

shown. This is the small plastic 

tube with a cut down the side. 

To insert it you squeeze the tube 

together and push it into the vessel 

connection and then let it spring 

back into place.  

 

2. Taking 

care not to damage the paddle or 

the paddle retaining clip, screw 

the anti legionella valve onto the 

expansion vessel and tighten up 

with a spanner. Note the valve 

includes a rubber seat so extra 

washers and PTFE tape are not 

needed. 

 

 

2.  Connect the ¾” FBSP tee piece 

onto the anti legionella valve 

and tighten with a spanner, the 

connection is sealed by an oring so 

extra washers and PTFE tape are 

not needed. The tee piece remains 

rotatable through 360° when 

tightened. 

80

100

36

Dimensions in mm unless otherwise stated.