I - SHIP PING AND PACK ING LIST

Package 1 of 2 contains:

1 - Energy Recovery Wheel Assembly
1 - Outdoor Fresh Air Hood with Filter
1 - Outdoor Exhaust Hood with Filter
1 - Platform Support Rail
1 - Bag Assembly

- Gasketing.
- Foot pads
- Hardware for standoff legs.
- Wiring harness
- Hardware for attachment to economizer.

Package 2 of 2 contains:

1 - Balancing Damper Assembly
2 - Side Filler Panels
4 - Hat Sections

II - SHIP PING DAM AGE

Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is
found.

III - GEN ERAL

These instructions are intended as a general guide and do
not supersede local codes in any way. Authorities having
jurisdiction should be consulted before installation.

IV - RE QUIRE MENTS

When installed, the unit must be electrically wired and
grounded in accordance with local codes or, in absence of
local codes, with the current National Electric Code,
ANSI/NFPA No. 70.

V  -  AP PLI CA TION

Energy Recovery Ventilators (

ERV) are 

used with units

equipped 

with a return damper assembly.

 These wheels 

conserve energy by mixing warmer air with cooler air in the
following manner:

Re cov ery  Mode

The Re 

cov 

ery Mode is ac 

com 

plished by two blow 

ers

pro vid ing  con tin u ous  ex haust  of  stale  in door  air  and
re 

place 

ment by equal amount of out 

door air. En 

ergy

re 

cov 

ery is achieved by slowly ro 

tat 

ing the En 

ergy

Re cov ery Wheel (ERW) within the cas sette frame work. In
win 

ter, the ERW ad 

sorbs heat and mois 

ture from the

ex haust air stream dur ing one half of a com plete ro ta tion
and gives them back to the cold, drier in take air sup ply

PAGE 1

dur ing the other half ro ta tion. In sum mer, the pro cess is
au to mat i cally  re versed.  Heat  and  mois ture  are  ab sorbed
from in 

com 

ing fresh air sup 

ply and trans 

ferred to the

ex 

haust air stream. This pro 

cess al 

lows out 

door air

ven ti la tion rates to be in creased by fac tors of three or more
with out ad di tional en ergy pen alty or increase in size of
heating or air conditioning systems.

VI - RIG GING UNIT FOR LIFT ING

1.

Maximum weight of unit is — 600 Lbs. (Crated)

2.

Remove crating. Then remove access panel (

See

Figure 1

) to retrieve bag assembly. Replace access

panel.

3.

All panels must be in place for rigging.

4.

Lifting lugs are supplied with the unit. Loosen machine
bolts and rotate lifting lug as shown in 

Figure 1

VII  -  IN STAL LA TION

1.

Disconnect all power to rooftop unit.

ACCESS PANEL

LIFTING LUGS (4)

Figure 1

INSTALLATION INSTRUCTIONS

EN ERGY  RE COV ERY  WHEEL

INSTALLATION INSTRUCTIONS FOR ENERGY RECOVERY VENTILATOR (FIXED) USED

WITH TRANE ROOFTOP UNIT MODELS YCD/TCD 15 TO 25 TON UNITS

R46A-11TDW

MAY 2, 2005

SUPERCEDES 11-14-02

ETL Certified per UL 1995
and CSA 22.2

Energy recovery COMPONENT
certified to the AHRI Air-to-Air
E n e r g y   R e c o ve r y  V e n t i l a t i o n
Equipment Certification Program in
accordance with AHRI Standard
1060-2000. Actual performance in
packaged equipment may vary.

Содержание RRS Systems YCD

Страница 1: ...ing the Energy Recovery Wheel ERW within the cassette frame work In winter the ERW adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to t...

Страница 2: ...in place 16 Seal if required along face top and sides of ERV unit where it meets rooftop unit to insure no air leakage 17 All electrical connections must conform to any local codes and current Nationa...

Страница 3: ...how the frost threshold temperatures vary depending on indoor conditions FROST THRESHOLD TEMPERATURE INDOOR RH AT 70o F FROST THRESHOLD TEMPERATURE 20 0o F 30 5o F 40 10o F Because Energy Recovery Ve...

Страница 4: ...with water and or mild detergent To install wheel segments follow steps A through E See Figure 5 Reverse procedure for segment removal A Unlock two segment retainers one on each side of the selected...

Страница 5: ...25 1 18 1 10 1 20 1 20 1 19 1 18 1 16 1 13 1 10 1 03 0 98 0 93 0 85 0 78 0 60 0 91 0 90 0 89 0 88 0 85 0 80 0 75 0 69 0 65 0 57 0 48 0 37 0 22 0 00 0 20 0 40 0 60 0 80 1 00 1 20 1 40 1 60 2200 2400 26...

Страница 6: ...0 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness J152 Jack Tran...

Страница 7: ...ambient switch 2 Step down transformer assembly for 460 volt units 3 Selective voltage terminal for proper unit voltage 4 Optional low ambient switch 5 Optional motorized intake damper 6 Optional sto...

Страница 8: ...PAGE 8...

Отзывы: