3.

Set thermostat to normal operating position.

4.

Restore power to unit.

X - Main te nance

Motor Maintenance

All motors use prelubricated sealed bearings; no further
lubrication is necessary.

Mechanical Inspection

Make visual inspection of dampers, linkage assemblies
and ERV rotating bearings during routine maintenance.
Filters should be checked periodically and cleaned when
necessary. Filter is located in fresh air hoods. 

DO NOT

replace permanent filters with throwaway type filters.

Energy Recovery Wheel Maintenance

Four pie-shaped ERW segments are seated on stops
between the stainless steel spring retainers, secured to
the hub and rim of wheel. Annual inspection of the self
c l e a n i n g   w h e e l   i s   r e c o m m e n d e d .   W i t h   p o w e r
disconnected, remove ERV access panels (rear) and
unplug (J150 & P150). Refer to wiring diagram in this
instruction manual. Each segment is secured in place by a
stainless steel spring retainer located on wheel rim.
Remove one end of the stainless steel spring retainer from
the slot in the wheel rim and remove. Do the same on the
next retainer. Remove segment and wash with water
and/or mild detergent. Replace segment by reversing the
above procedure. 

See Figure 5.

 Discoloration and

staining of ERV segment does not affect its performance.
Only excessive buildup of foreign material need be
removed. If the segment appears excessively dirty, it
should be cleaned to ensure maximum operating
efficiency. Thoroughly spray plastic surface with
household cleaner such as Fantastic

â

 or equivalent

middle detergent and gently rinse with warm water using a
soft brush to remove heavier accumulation. Shake excess
water from segment and replace in reverse of removal
instructions.

XI - WAR RANTY

RSI  Man u fac tured  Parts

In the event that defects in workmanship or materials
originate in any part manufactured by RSI, FOB point of
manufactured, we guarantee to repair or replace that part,
within three (3) months of the shipment date.

Other Sup plied Parts

Additionally, RSI guarantees to replace standard
components purchased new from a RSI vendor, (motors,
controls, etc.) that may be found defective, within twelve
(12) months of the installation date. The components
warranty, however, excludes service call charges and
labor cost for replacing or adjusting the defective part.

Lim i ta tion  of  War ran ties

Misapplication, destruction, negligence or alteration
constitute the warranty and/or the components warranty of
RSI products and/or parts, null and void. This warranty is
provided in lieu of all other written, stated or implied
warranties.

HUB

SEGMENT

Figure 5

SPOKE

SEGMENT RETAINER CATCH

WHEEL RIM

SEGMENT RETAINER

Figure 4

Содержание RRS ROOFTOP YCD/TCD

Страница 1: ...rve energy by mixing warmer air with cooler air in the following manner Recovery Mode The Recovery Mode is accomplished by two blowers providing continuous exhaust of stale indoor air and replacement...

Страница 2: ...s CEC Refer closely to unit wiring diagram in unit and or in these instructions for proper wiring connections Refer to the unit nameplate for minimum circuit ampacity and maximum overcurrent protectio...

Страница 3: ...lators the frost threshold is typically below 15o F Frost threshold is dependent on indoor temperature and humidity The table shows how the frost threshold temperatures vary depending on indoor condit...

Страница 4: ...g of ERV segment does not affect its performance Only excessive buildup of foreign material need be removed If the segment appears excessively dirty it should be cleaned to ensure maximum operating ef...

Страница 5: ...1 27 1 26 1 25 1 23 1 2 1 18 1 17 1 15 1 13 1 12 1 09 1 06 0 99 0 91 1 05 1 02 0 95 0 8 0 65 0 0 2 0 4 0 6 0 8 1 1 2 1 4 700 750 800 850 900 950 1000 1050 1100 1150 1200 SCFM Equation of Line SCFM PD...

Страница 6: ...g Exhaust Air Motor Harness P56 Plug Damper Motor Harness P148 Plug Fresh Air Motor P150 Plug Wheel Motor P151 Plug Exhaust Air Motor P152 Plug Transformer High Voltage P153 Plug Field Harness P160 Pl...

Страница 7: ...tional low ambient switch 5 Optional motorized intake damper 6 Unit may be wired for HI MED or LO speeds Diagram shows the HI speed setup to rewire for MED or LO speed disconnect BK 101 from relays an...

Страница 8: ...PAGE 8...

Отзывы: