related to the quality of resin. Down-flow regeneration, takes
800~900. Up-flow regeneration, takes 900~1200.
K
——Security factor, always take 1.2~2. It is related to the
hardness of inlet water: the higher the hardness is, the bigger the K is.
⑦
Regeneration time: The whole cycle for regeneration is about two
hours. Please try to set up the regeneration time when you don’t need to
use water according to the actual situation.
The calculation of parameters for each step is only for reference, the
actual proper time will be determined after adjusting by water exchanger
supplier. This calculation procedure of softener is only for industrial
application; it is not suitable for small softener in residential application.
3.5. Parameter Enquiry and Setting
3.5.1. Parameter Enquiry (Take 63615 A-01 mode as a sample)
When
lights on, press and hold both
and
for 5 seconds
to lift the button lock status; then press
and
lights on, enter
program display mode; press
or
to view each value according to
below process.
(
Press
exit and turn back to service status
)