Operation & Maintenance
m
a i n t e n a n c e
& c
l e a n i n g
Your Runtal Electric Wall Panel (EWP) has been designed to require the absolute minimum maintenance and
care under normal use. However, care should be taken when cleaning the surface of the panel. Periodically
vacuum across the top of the grille to remove dust from the grille. A slight odor may be noticeable during
initial operation and will dissipate within a few hours.
The EWP’s powder coated finish provides an elegant yet durable finish to a welded steel product.
Occasional cleaning of this finish is best done with a water dampened cloth.
Under no circumstances should
abrasive cleaner be used. Before cleaning make sure the power has been turned off at the circuit breaker
panel, and the heating element is cool.
Be sure to restore power when cleaning and maintenance is complete.
All other servicing should be performed by qualified service personnel.
For installation of multiple electric wall panel radiators, the following chart should be used.
The chart indicates supply voltage, circuit breaker rating, minimum wire size, and maximum total
wattage of electric radiators on the circuit.
m
a x i m u m
W
at tag e
o n
a
c
i R c u i t
Voltage A.C.
Circuit Breaker Size
Maximum Wattage Minimum
Wire Size
120
15 Amp
1440
14/2 with Ground
120
20 Amp
1920
12/2 with Ground
120
30 Amp
2880
10/2 with Ground
208
15 Amp
2496
14/2 with Ground
208
20 Amp
3328
12/2 with Ground
208
30 Amp
4992
10/2 with Ground
240
15 Amp
2880
14/2 with Ground
240
20 Amp
3840
12/2 with Ground
240
30 Amp
5760
10/2 with Ground
IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS