background image

                                                            

                                   

 

RuggedCom Inc. 

I

 30 Whitmore Road, Woodbridge, Ontario, Canada L4L 7Z4  

Tel:

 (905) 856-5288 I 

Fax:

 (905) 856-1995 

I

 

Toll Free:

 (888) 264-0006

 

    
    

RuggedSwitch

RuggedSwitch

RuggedSwitch

RuggedSwitch

    RS900

RS900

RS900

RS900L

L

L

L    

8-Port Managed Ethernet Switch with EoVDSL Uplinks 

 

 

Installation Guide 

www.ruggedcom.com 

All manuals and user guides at all-guides.com

all-guides.com

Содержание RuggedSwitch RS900L

Страница 1: ... I Fax 905 856 1995 I Toll Free 888 264 0006 RuggedSwitch RuggedSwitch RuggedSwitch RuggedSwitch RS900 RS900 RS900 RS900L L L L 8 Port Managed Ethernet Switch with EoVDSL Uplinks Installation Guide www ruggedcom com All manuals and user guides at all guides com a l l g u i d e s c o m ...

Страница 2: ...rk of Xerox Corporation RuggedSwitch RuggedRated ROS and eRSTP are trademarks of RuggedCom Inc Caution This product contains a laser system and is classified as a CLASS 1 LASER PRODUCT Use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure This product contains no user serviceable parts Attempted service by unauthori...

Страница 3: ...14 3 2 RJ45 Ethernet Ports 17 3 3 Fiber Optic Ethernet Ports 19 4 Technical Specifications 20 4 1 Operating Environment 20 4 2 Power Supply Specifications 20 4 3 Failsafe Relay Specifications 20 4 4 RJ11 Ethernet over VDSL Port Specifications 21 4 5 RJ45 Ethernet Port Specifications 21 4 6 Fiber Optic Ethernet Port Specifications 22 4 7 Communication Standards 22 4 8 Mechanical Specifications 23 5...

Страница 4: ...echanical Specifications 23 Table of Tables Table 1 Status LEDs 6 Table 2 RS232 Female DCE pin out 13 Table 3 RJ11 port pin out 14 Table 4 RJ11 port LED description 14 Table 5 Typical Performance on 24 AWG PIC twisted pair 15 Table 6 RJ45 port pin out 17 Table 7 RJ45 port LED description 17 Table 8 Operating Environment 20 Table 9 Power Supply Specifications 20 Table 10 Failsafe Relay Specificatio...

Страница 5: ...ters over any combination of telephone and fiber optic cable It is the perfect solution for bringing Ethernet networking to applications where telephone wiring is already present and saving the considerable cost of installing new fiber 1 2 Feature Highlights Ethernet Ports o 1 EoVDSL port o 6 10 100Base TX ports o 2 Optional Fiber Optic ports EoVDSL port characteristics o Software selectable to be...

Страница 6: ...ase TX Ports 7 8 10 100Base TX or 100Base FX Port 9 Ethernet over VDSL Power Alarm Reset Figure 1 Front Panel Description Status LED Colour Activity Comments Power LED Green Solid Power On Alarm LED Red Solid Alarm condition exists Table 1 Status LEDs All manuals and user guides at all guides com a l l g u i d e s c o m ...

Страница 7: ...ll rights reserved Rev101 1 4 Bottom Panel Description Failsafe Relay Console Port Power Port Chassis Ground Optional Din Rail Mounting Bracket Figure 2 Bottom Panel Description All manuals and user guides at all guides com ...

Страница 8: ... 2 Installation 2 1 Din Rail Mounting An optional DIN rail mounting bracket is available for the unit The figure below details mounting instructions for the standard 1 DIN Rail Figure 3 DIN Rail Mounting All manuals and user guides at all guides com ...

Страница 9: ...nding wire Surge Ground is used as the ground conductor for all surge and transient suppression circuitry internal to the unit 4 Chassis Ground must be connected to the AC ground terminal NOTES 1 Equipment must be installed according to the applicable country wiring codes 2 All line to ground transient energy is shunted to the Surge Ground terminal In cases where users require the inputs to be iso...

Страница 10: ...unit 2 Surge Ground should be connected to the Chassis Ground via a braided cable or other appropriate grounding wire Surge Ground is used as the ground conductor for all surge and transient suppression circuitry internal to the unit 3 Chassis Ground must be connected to the protective earth NOTES 1 Equipment must be installed according to the applicable country wiring codes 2 All line to ground t...

Страница 11: ...n the unit The contacts are energized upon power up of the unit and remain energized until an alarm condition or power loss occurs The behavior of the failsafe relay is configurable via the RuggedSwitch Operating System Consult the RuggedSwitch Users Guide for details Figure 6 Failsafe Output Relay All manuals and user guides at all guides com a l l g u i d e s c o m ...

Страница 12: ...strength testing HIPOT testing done in the field must have the braided ground cable disconnected during the test This is required in order to prevent the surge suppression circuitry which is connected to surge ground from being activated Figure 7 Dielectric Strength Testing All manuals and user guides at all guides com ...

Страница 13: ...ignals from the PC side since this has been done internally as is shown below Figure 8 RS232 Female DCE pin out Pin Signal 1 No Connection 2 Transmit Data 3 Receive Data 4 No Connection 5 Ground 6 No Connection 7 No Connection 8 No Connection 9 No Connection Table 2 RS232 Female DCE pin out NOTE This port is not intended to be a permanent connection and the cable shall be less than 2m 6 5 ft in le...

Страница 14: ...e used interchangeably for the Slave Configuration of Master or Slave mode is done through the RuggedSwitch Operating System The unit contains one EoVDSL data port that allows connection to Category 3 CAT 3 unshielded twisted pair UTP cable with RJ11 male connectors The figure below shows the RJ45 port pin out and LEDs Figure 9 RJ11 port pin out and LEDs Pin Signal 3 Ring 4 Tip Table 3 RJ11 port p...

Страница 15: ...n arrow to select either Master or Slave Press Enter 6 Press Control and A together to apply the changes Once configured as master and slave and connected together the units will then attempt to achieve the maximum speed based on the line length and conditions The unit s link LED may flash on and off several times before settling on a final link speed and declaring the port up Please see the Rugge...

Страница 16: ...fy the user of the reduced SNR If the line conditions degrade such that the unit is unable to maintain the current link the unit will restart the scan process NOTES 1 This port is designed to be used on private communications lines and is not to be connected to the Public Switched Telephone Network PSTN 2 To reduce the risk of fire use only No 26 AWG or larger telecommunication line cord All manua...

Страница 17: ...st be taken to ensure the shielded cables do not form a ground loop via the shield wire and the RJ45 receptacles at either end The figure below shows the shows the RJ45 port pin out and LEDs Figure 10 RJ45 port pin out and LEDs Pin Signal 1 Rx 2 Rx 3 Tx 4 No Connection 5 No Connection 6 Tx 7 No Connection 8 No Connection Case Shield Chassis Ground Table 6 RJ45 port pin out Status LED Colour Activi...

Страница 18: ...age from electrical transients and to ensure IEC 61850 3 and IEEE 1613 Class 1 conformance This means that during the transient event communications errors or interruptions may occur but recovery is automatic RuggedCom also does not recommended to use these ports to interface to field devices across distances which could produce high levels of ground potential rise i e greater than 2500V during li...

Страница 19: ...ections of each port must be properly connected and matched for proper link and operation The drawings in the following figures show each fiber optical connector style with a side and top view to allow the user to identify the proper cable connection orientation Figure 11 100FX MTRJ connector Figure 12 100FX ST connector Figure 13 100FX SC connector Figure 14 100FX LC connector All manuals and use...

Страница 20: ...VDC 10 VDC 36 VDC 3 15 T 1 5 kV DC 24 VDC 18 VDC 36 VDC 3 15 T 1 5 kV DC 48 VDC 36 VDC 72 VDC 3 15 T 1 5 kV DC HI 125 250 VDC 1 HI 110 230 VAC 1 88 VDC 85 VAC 300 VDC 265 VAC 3 15 T 4 kV AC 5 5 kV DC 10W Table 9 Power Supply Specifications NOTES 1 This is the same power supply for both AC and DC 2 F Denotes fast acting fuse T denotes time delay fuse 3 For continued protection against risk of fire ...

Страница 21: ...nector Type VDSL CAT 3 UTP or STP 2500m RJ11 Table 11 RJ1 Ethernet over VDSL Port Specifications 4 5 RJ45 Ethernet Port Specifications Data Port Media Distance Connector Type 10 100 Mbps CAT 5 UTP or STP 100m RJ45 Table 12 RJ45 Ethernet Port Specifications All manuals and user guides at all guides com a l l g u i d e s c o m ...

Страница 22: ...ase FX SM ST 1310 9 125 15 8 32 7 20 16 5 100Base FX SM SC 1310 9 125 13 5 31 4 20 20 100Base FX SM LC 1310 9 125 15 8 31 5 15 16 5 Table 13 Fiber Optic Port Specifications NOTES 1 Maximum segment length is dependent on factors such as fiber quality and number of patches and splices Please consult RuggedCom sales associates when determining maximum segment distances 2 To convert from average to pe...

Страница 23: ...cal Specifications Figure 15 Mechanical Specifications Table 15 Mechanical Specifications Parameter Value Dimensions 16 8 x 11 7 x 6 6 cm 6 6 x 4 6 x 2 6 inches Weight 1 2 kg 2 7 lbs Enclosure 20 AWG Galvanized Steel All manuals and user guides at all guides com ...

Страница 24: ...0 A m for 1 s N A D C Power ports 30 for 0 1s 60 for 0 1s 100 for 0 05s N A IEC 61000 4 29 30 for 1 period 60 for 50 periods N A IEC 61000 4 11 Voltage Dips Interrupts A C Power ports 100 for 5 periods 100 for 50 periods 2 N A Signal ports 2 5kV common 1kV differential mode 1MHz 3 D C Power ports 2 5kV common 1kV differential mode 1MHz 3 IEC 61000 4 12 Damped Oscillatory A C Power ports 2 5kV comm...

Страница 25: ...elay D C Power ports 2kV AC IEEE C37 90 Dielectric Strength A C Power ports 2kV AC Table 17 IEEE 1613 Type Tests NOTE If the unit contains copper ports the IEEE 1613 conformance is Class 1 During disturbance errors may occur but recovery is automatic If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 During disturbance no errors will occur 5 3 IEC Environmental Type Tests Te...

Страница 26: ...se For warranty details visit http www ruggedcom com or contact your customer service representative Should this product require warranty or service contact the factory at RuggedCom Inc 30 Whitmore Road Woodbridge Ontario Canada L4L 7Z4 Phone 905 856 5288 Fax 905 856 1995 All manuals and user guides at all guides com a l l g u i d e s c o m ...

Отзывы: