background image

13 

 

2008 RuggedCom Inc. All rights reserved 

 

Rev101

 

3.4

 

Fiber Optical Specifications 

Parameter 

Ports 1 to 4 

10Mbps Ports 

Uplink 

100Mbps Port 

 

Multi-Mode 

Single-Mode* 

Multi-Mode 

Single-Mode* 

Speed Standard 

10BaseFL 

100BaseFX 

Connector Type 

ST 

MTRJ 

LC 

Segment Length 

2 km 

15 km 

2 km 

15 km 

Optical Wavelength 

820nm 

1310nm 

1300nm 

1310nm 

Cable Size 

Core/Cladding 

62.5/125

µ

9/125

µ

62.5/125

µ

9/125

µ

Optical Tx Power 

Min/Max (dBm Peak) 

-13.5/-7.6 

-23/-15 

-16/-11 

-15/-8 

Optical Rx Sensitivity

 

(dBm Average) 

-34.4 

-38 

-33.5 

-31 

Max Optical Rx Power 

(dBm Peak) 

-8.2 

-3.0 

-11 

-5 

Typical Optical 

Power Budget (dB) 

22 

18 

17 

16.5 

* Available as an option 

 

3.5

 

Networking Performance Specifications 

 

Parameter 

10Mbps Ports 

(10BaseFL) 

100Mbps Ports 

(100BaseFX) 

Notes 

Latency 

16us + frame time 

5us + frame time 

 

Filtering Rate 

14 880  

148 800 

Frames/sec 

MAC Address Table 

8192 

 

VLAN Address Table 

4096 

 

 

Содержание RuggedSwitch RS500

Страница 1: ...itch RS500 RS500 RS500 RS500 Installation Guide Installation Guide Installation Guide Installation Guide RuggedCom Inc 30 Whitmore Road Woodbridge Ontario Canada L4L 7Z4 Web www ruggedcom com Tel 905 856 5288 Fax 905 856 1995 Toll Free 888 264 0006 ...

Страница 2: ...erence in which case the user will be required to correct the interference on his own expense Warning Changes or modifications not expressly approved by RuggedCom Inc could void the user s authority to operate the equipment Trademarks Ethernet is a trademark of Xerox Corporation RuggedSwitch is a registered trademark of RuggedCom Inc Important The RS500 contains no user serviceable parts Attempted...

Страница 3: ...rounding 8 2 2 1 Power Supply DC Input 9 2 3 HIPOT Dielectric Strength Testing 10 2 4 Failsafe Output Wiring and Specifications 11 3 Technical Specifications 12 3 1 Power Supply Specifications 12 3 2 Failsafe Relay Specifications 12 3 3 Networking Standards Supported 12 3 4 Fiber Optical Specifications 13 3 5 Networking Performance Specifications 13 3 6 Type Test Specifications 14 3 7 Operating En...

Страница 4: ...substation automation network Because the RS500 was designed to meet the demands of the substation environment it is also ideally suited for industrial automation networks based on Industrial Ethernet The reliability of the RS500 exceeds that of commercial Ethernet switches by having no rotating mechanical parts such as cooling fans and by utilizing high temperature solid state components 1 2 Feat...

Страница 5: ...Once per second Tx Rx Activity Tx LED Red Blinking Tx Transmit Activity Rx LED Green Blinking Rx Receive Activity POWER LED Red Solid Power On Safety Ground Stud Power Failsafe Output Relay LED Indicators 10BaseFL Ports ST Connectors Reset Front Panel View Surge Ground DC DC Normally Open Common Normally Closed LINK Activity Tx Transmit Rx Receive POWER LED 100BaseFX Port MTRJ Connector ...

Страница 6: ...00 Top and Bottom View Fig 1 4 1 RS500 Top and Bottom View Surge Ground DC DC Safety Ground Stud Failsafe Output Relay Bottom View Top View DIN Rail Mounting Bracket 100BaseFX Port MTRJ Connector 10BaseFL Ports ST Connectors Reset DIN Rail Mounting Bracket ...

Страница 7: ...eserved Rev101 2 Installation 2 1 DIN Rail Mounting Fig 2 1 1 RS500 Rail Mounting DIN RAIL DIN RAIL Mounting Latch Screw Driver Release Action Release Slot Release Direction RS500 DIN Rail Mounting Release Side View Front View DIN RAIL ...

Страница 8: ...AC 2 DC is connected to the negative terminal if the power source is DC or to the Neutral terminal if the power source is AC 3 Surge Ground is used as the ground conductor for all surge and transient suppression circuitry internal to the RS500 Surge Ground is connected directly to the safety ground terminal internally NOTE Since the Chassis Ground is connected to the equipment ground bus internall...

Страница 9: ...ghts reserved Rev101 2 2 1 Power Supply DC Input Fig 2 2 2 Power Supply DC Input Note Ground bus can either be connected to the Ground Stud on the rear of the RS500 chassis or the Surge Ground port on the screw in terminal block ...

Страница 10: ...c Strength Testing HIPOT Dielectric strength testing cannot be performed in the field due to transient surge suppression circuitry connected to the RS500 Surge Chassis Ground All RuggedSwitch products are HIPOT tested according to IEC 60255 5 Section 6 during final test ...

Страница 11: ...put relay is provided to signal critical error conditions that may occur on the RS500 The contacts are energized upon power up of the unit and remain energized until a critical error occurs Normally Closed Common Normally Open RS500 Failsafe Relay Outputs Normal contact state prior to power being applied to unit ...

Страница 12: ...0 VDC 3 15A T 10 W NOTES 1 T denotes time delay fuse 2 For continued protection against risk of fire replace only with same type and rating of fuse 3 2 Failsafe Relay Specifications Parameter Value Resistive Max Switching Voltage 30VAC 80VDC Rated Switching Current 0 3A 30VAC 1A 30VDC 0 3A 80VDC 3 3 Networking Standards Supported Parameter 10Mbps Ports 100Mbps Ports Notes IEEE 802 3 10BaseT 10Base...

Страница 13: ...310nm Cable Size Core Cladding 62 5 125µm 9 125µm 62 5 125µm 9 125µm Optical Tx Power Min Max dBm Peak 13 5 7 6 23 15 16 11 15 8 Optical Rx Sensitivity dBm Average 34 4 38 33 5 31 Max Optical Rx Power dBm Peak 8 2 3 0 11 5 Typical Optical Power Budget dB 22 18 17 16 5 Available as an option 3 5 Networking Performance Specifications Parameter 10Mbps Ports 10BaseFL 100Mbps Ports 100BaseFX Notes Late...

Страница 14: ... for 2s ANSI IEEE C37 90 1 IEC 60255 22 1 IEC Surge 4 kV 2 kV IEC 61000 4 5 Level 4 IEC Fast Transient 2 kV 1 kV IEC 61000 4 4 Level 4 ANSI IEEE Fast Transient 4 kV ANSI IEEE C37 90 1 IEC Radiated RFI Immunity 10 V m IEC 61000 4 3 ANSI IEEE Radiated RFI Immunity 35 V m ANSI IEEE C37 90 2 ESD Electrostatic Discharge 15 kV air discharge 8 kV contact IEC 61000 4 2 Level 4 Atmospheric Environment Leve...

Страница 15: ...t Parameter Range Comments Ambient Operating Temperature 40 to 85 C Ambient Temperature as measured from a 30cm radius surrounding the center of the R500 enclosure Ambient Relative Humidity 5 to 95 Non condensing Ambient Storage Temperature 40 to 85 C 3 8 Physical Dimensions ...

Страница 16: ...of purchase For warranty details visit http www ruggedcom com or contact your customer service representative Should this product require warranty or service contact the factory at RuggedCom Inc 30 Whitmore Road Woodbridge Ontario Canada L4L 7Z4 Phone 905 856 5288 Fax 905 856 1995 Parameter Value Comments Dimensions 8 0 x 6 84 x 2 43 inches 203 20 x 173 74 x 61 72 mm Length x Width x Height with m...