3.  For 24V power supply a J2 type connector is supplied. Install 

J2 connector as shown. Remove J4 connector if necessary. 
See Figure 4.

NOTE:     

If rewiring of connectors is required, see Figure 5 or 6 
for wire control power supply terminals. J2 connector is 
for 24V AC/DC, 100 mA and J4 connector is for 120V or 
240V, 100 mA. Use only 18–26 AWG copper wire rated 
for 90°C for connections.

CAUTION

CAUTION. 

All circuits must have a common disconnect 

and be connected to the same pole of the disconnect. 
Electrical ratings stated must not be exceeded. 

Step 1 

Mount thermostat approximately 5' (1.5 m) above the floor where 
average room temperature will be sensed and air circulates freely. 
Keep thermostat away from hot and cold surfaces.

Step 2 

1.  Three types of power supply terminals are supplied. Installed 

on the thermostat is a J4 connector wired for 120V. See 
Figure 1.

2.  A J4 connector is supplied seperately for 240V power supply. 

Simply remove 120V J4 connector and install 240V J4 
connector. See Figure 2 and 3.

Feed-thru Models: XTE-412 SPDT

• 

Resistive: 10 Amps N.C., 20 Amps N.O., 240 VAC Max.;  
24V AC/DC, 120V, 240V

• 

Pilot Duty: 120 VAC, N.O. 470 VA, N.C. 275 VA

• 

Class I, Divisions 1 & 2, Groups C & D; Class II, Division 1, 
Groups E, F & G;

• 

Class II, Division 2, Groups F & G; Class III; Class I, Zones 1 
& 2, Groups IIA & IIB.

Figure 5 

Figure 3 

240V, J4 

connector installed

Figure 4 

J2 

connector

Pin terminals

Figure 6 

Figure 1   

120V, J4 

connector

Figure 2 

240V, J4 

connector

120V, J4 

connector 

removed

Содержание Defender XTE-412

Страница 1: ...rdous atmospheres disconnect equipment from the supply circuits before opening Keep assembly tightly closed when in operation CAUTION CAUTION To reduce the risk of electric shock Do not connect to a circuit operating at more than 150V to ground ISO 9001 Defender XTE 412 Installation Instructions Ruffneck is a registered trademarks of CCI Thermal Technologies Inc Copyright 2017 All rights reserved ...

Страница 2: ...rature will be sensed and air circulates freely Keep thermostat away from hot and cold surfaces Step 2 1 Three types of power supply terminals are supplied Installed on the thermostat is a J4 connector wired for 120V See Figure 1 2 A J4 connector is supplied seperately for 240V power supply Simply remove 120V J4 connector and install 240V J4 connector See Figure 2 and 3 Feed thru Models XTE 412 SP...

Страница 3: ...Install the cover using the 4 bolts supplied and tighten Step 5 Fill any unused conduit opening using plug supplied Resistive Heating Load 240V 20 A Max Heating Load Cooling Load N C Direct Acting N O Reverse Acting Load Switching Relay Neutral Line 240 VAC Max 50 60 Hz Figure 8 Figure 9 Figure 10 N O Terminal Figure 7 Heating Load Cooling Load N C Direct Acting N O Reverse Acting Cooling Load Hea...

Страница 4: ...o warranty applies to paint finishes except for manufacturing defects apparent within 30 days from the date of installation The Company neither assumes nor authorizes any person to assume for it any other obligation or liability in connection with the product s The Purchaser agrees that all warranty work required after the initial commissioning of the product will be provided only if the Company h...

Отзывы: