Copyright © 2013 Ruckus Wireless, Inc.
Published July 2013, Part Number 800-70544-001 Rev A

Page 2 of 2

Figure 3: Attaching the rear brackets and outer rails

S

TEP

 3: A

TTACH

 

THE

 O

UTER

 R

AIL

 A

SSEMBLIES

 

TO

 

THE

 R

ACK

 P

OSTS

NOTE: 

The two outer rail assemblies are interchangeable.

1

Locate an outer rail assembly in a vacant 2U space the rack 
with the short bracket toward the front of the rack. If the 
measurement in Step 2 was accurate, then the rail assembly 
should fit exactly into the server rack. 

NOTE: 

Only use screws in the top and bottom holes of the front 

brackets. Use three screws in the rear brackets.

2

Get a helper. If you are using factory-supplied fasteners, use 
two factory-supplied screws and a bar nut (E and F in Figure 
1) a
nd loosely attach the front of the outer rail assemblies to 
the front of rack (Figure 4). Use three factory-supplied 
screws and a bar nut and loosely attach the rear of the outer 
rail assemblies to the rear of rack.

If you are using customer-supplied fasteners, loosely attach 
each end of the outer rail assemblies to the rack with five 
customer-supplied fasteners, two on the front and three on 
the rear. 

NOTE: 

Leave the outer rail assembly rack screws loose for now. 

You will tighten them after the SCG or ZD chassis is positioned 
in the rack.

3

Once you have verified the rail assembly length, tighten the 
two screw sets holding the outer rail assemblies together.

Figure 4: Installing the customer-supplied screws and a bar nut

S

TEP

 4: A

TTACH

 

THE

 F

RONT

 L

OCKING

 B

RACKETS

 

TO

 

THE

 S

ERVER

1

Remove the two front locking brackets (D in Figure 1) and 
four #8-32 1/4” pan head screws (H in Figure 1) from the 
package. 

2

Attach one locking bracket to the side of the server as 
shown.

3

Repeat for the other locking bracket.

Figure 5: Attaching a locking bracket

S

TEP

 5: A

TTACH

 

THE

 I

NNER

 R

AILS

 

TO

 

THE

 S

ERVER

1

Attach one inner rail (B in Figure 1) to the side of the server 
chassis, making sure that the narrow end points toward the 
rear of the chassis. 

2

Secure the inner rail to the chassis using two #8-32 1/4” pan 
head screws (H in Figure 1).

3

Repeat these steps for the other side of the chassis, making 
sure that the narrow end of the inner rail points toward the 
rear.

Figure 6: Attaching the inner rails

S

TEP

 6: S

LIDE

 

THE

 I

NNER

 R

AILS

 

INTO

 

THE

 O

UTER

 

R

AILS

 

AND

 S

ECURE

 

TO

 

THE

 R

ACK

WARNING: 

The ZD and SCG servers are heavy (40 lbs/18.14kg). 

Two people should work together to lift and slide the server into 
the rack. Ruckus strongly recommends against one person 
attempting to perform this task alone.

1

Align the inner rails (attached to the server chassis) with the 
outer rail assemblies (loosely attached to the rack). 

2

Engage the matching rails, and then slide the server chassis 
into the rack until the two spring safety locks snap into 
position.

3

Press down the two spring safety locks (one on each side). 
See 1 in Figure 7.

4

Slide the server chassis all the way into the rack. Make sure 
that the rail assemblies slide smoothly. See 2 in Figure 7.

5

Align the rail assemblies and tighten the screws holding the 
rail assemblies to the rack posts.

6

Use two customer-supplied rack screws to secure the chassis 
and front locking brackets into the rack. See 3 in Figure 7.

Figure 7: Securing the server to the rack

NOTE: 

If necessary, make the front of the server flush with the 

rack: (1) Remove the server and inner rails from the rack. (2) 
Leave the front and rear brackets attached to the rack. Loosen 
the screws holding the two outer rails to the front and rear 
brackets (A and C in Figure 1). 
(3) Move the two outer rails back 
in the rack as required. (4) Tighten the screws holding the two 
outer rails to the front and rear brackets. (5) Replace the server 
and inner rails in the rack (Figure 7)
.

Congratulations! You have completed mounting the 
ZoneDirector 5000 or SCG 200 into your server rack.