12.3.  Fault current protection switch

The use of a fault current protection switch is not mandatory. If a fault current protection switch is used, only AC/DC sensitive RCD 

protective devices (type B or B+) are permitted.

Even when the device is switched off, voltage is applied to terminals and connections. Do not touch the 

device for 5 minutes after all-pole disconnection from the mains.

13. COMMISSIONING

Commissioning by trained technical personnel may only be performed after any risk has been ruled out. 

The following checks should be performed in accordance with the installation and operating manual and 

the regulations in force:

 

Correctly sealed installation of the unit and duct system.

 

Check the duct system, unit and medium lines, if present, remove any foreign bodies if necessary.

 

The intake opening and inflow into the unit must be clear.

 

Check all mechanical and electrical protection measures (e.g. earthing).

 

Voltage, frequency and type of current must correspond with the rating plate.

14.  MAINTENANCE AND CLEANING

Servicing, troubleshooting and cleaning may only be performed by specialised personnel in accordance 

with this installation and operating manual and the regulations in force.

 

Make sure that no connections or components are loosened unless the device is disconnected from the mains. Make 
sure that the equipment cannot be switched back on again.

 

Individual components must not be interchanged. For example, the components intended for one product may not 
be used for other products.

 

The regular maintenance and care of our devices is designed to ensure proper function, value retention and avoid-
ance of damage. Keep a maintenance log.

 

Perform the specified maintenance on the unit at the specified intervals.
Our devices require little maintenance when operated properly.
The following work should be performed at regular intervals, in accordance with health and safety regulations:

 

Check the operation of the control system and safety devices.

 

Check electrical connections and wiring for damage.

 

Remove any dirt from the fan impeller or impellers and from inside the fan housing in order to prevent any unbal-
ance or reduction in output.

 

– Do not use aggressive or easily flammable products for cleaning (impellers/housing). 

 

– Preferably only water (not flowing water) or mild soapsuds should be used.

 

– The impeller should be cleaned with a cloth or brush.

 

– Never use a high-pressure cleaner.

 

– Balancing clips must not be moved or removed.

 

– The impeller and fittings must not be damaged in any way.

Before putting the unit back into operation after maintenance and servicing work, carry out a visual inspection as described in sec-

tion 12 and 13.

www.ruck.eu |  

13

Содержание MPS 225 E2 21

Страница 1: ...H ERP DIRECTIVE 327 2011 OF THE EUROPEAN PARLIAMENT 8 10 TRANSPORT AND STORAGE 9 11 ASSEMBLY 9 12 ELECTRICAL CONNECTION 12 13 COMMISSIONING 13 14 MAINTENANCE AND CLEANING 13 15 LIFETIME AND DISPOSAL 1...

Страница 2: ...ird parties 2 1 Other applicable documents and information The following documents and information must be observed in addition to the installation operating and maintenance instructions 2 2 Provision...

Страница 3: ...and installations or for combination with other components to form a machinery or installation The product may be commissioned only if it is integrated in the machinery system for which it is designed...

Страница 4: ...sk Identifies the type or source of the hazard Consequences Describes what occurs when the safety instructions are not complied with Precautions States how the hazard can be avoided General warning Fa...

Страница 5: ...and easy accessible 4 4 Indications during operation Only authorized personnel is allowed to operate the setting mechanisms of the components or parts under the provision that the system is used as in...

Страница 6: ...agram Weight V Hz W A C C dB A dB A dB A kg MPS 225 E2 21 137879 230V 50 287 2 3 80 120 69 74 74 137115 28 4 MPS 250 E2 20 126646 230V 50 448 3 3 80 120 71 78 78 127639 46 8 MPS 280 E2 20 126647 230V...

Страница 7: ...4 314 692 540 566 567 494 505 329 344 200 156 137079 700 663 365 354 354 790 590 657 612 602 555 382 405 220 181 138005 832 789 365 354 354 916 590 619 612 734 555 448 477 220 181 126652 832 789 365 3...

Страница 8: ...ibed in the measurement category and not supplied with the fan No special items have been used for determining the fan energy efficien cy except the required connection components according to the mea...

Страница 9: ...ing remove it immediately Storage temperature between 5 C and 40 C Avoid severe temperature fluctuations If the product has been in storage for more than a year check the smooth running of impellers a...

Страница 10: ...available as accessory WSH MPS Weather protection cover available as accessory VM Fast clamps available as accessory Function condensate drain only possible with discharge up A B Mount the mounting ra...

Страница 11: ...ounting rails 4 on the socket silencer ATTENTION Mounting rail with ramp 5 left mounting rail with doorstop 6 right Use of condensate drainage not possi ble here D Discharge right Turn the device comp...

Страница 12: ...e inlets that are not used must be sealed so that it is airtight All cable inlets must have strain relief Create equipotential bonding between the unit and the duct system Check all protective measure...

Страница 13: ...omponents are loosened unless the device is disconnected from the mains Make sure that the equipment cannot be switched back on again Individual components must not be interchanged For example the com...

Страница 14: ...tight fit yearly Measure the voltage yearly 14 2 Maintenance works Undo screws 1 and 2 Swing out fan unit 3 Secure the fan unit in the open position 4 14 3 Impeller installation with Taperlock clampin...

Страница 15: ...ons We rec ommend replacing these fans after reaching about 30 000 operating hours or 5 years 15 2 Decommissioning and disposal When disassembling parts under voltage are exposed which can lead to ele...

Страница 16: ...enance and cleaning Imbalance of the impeller Contact the supplier Connection with intake or exhaust pipe duct causes vibrations oscillations Install fan with vibration dampers Fixing screws released...

Страница 17: ...EN NOTES www ruck eu 17...

Страница 18: ...rint 24 10 2019 mpss_pb_15b_en We reserve the right to make changes Language English ruck Ventilatoren GmbH Max Planck Str 5 D 97944 Boxberg Windischbuch Tel 49 7930 9211 300 Fax 49 7930 9211 166 info...

Отзывы: