14 

 

Compliance with CE Mark 

 

This section describes how to install and operate RTP equipment for use in the European Union 
(EU) to comply with the requirements of the CE Mark and its referenced standards.  The 
procedures in this section apply also to ot

her environments where provisions of the EU’s EMC 

and Low Voltage Directives are either required or desirable. 

RTP Corporation has successfully tested and reviewed its products to the stringent requirements 
of the European Union’s EMC Directives (2004/108/EC) and Low Voltage Directive (2006/95/EC).  

In order for the equipment to meet the requirements of these directives, the equipment 
must be installed and operated in accordance with these instructions

These tests and reviews are in accordance to EN 61131-2:2007 as listed in the next section. 

Information on the tests performed and the standards involved is available from RTP Corporation. 

To comply with the requirements of the CE Mark and its referenced standards, the system 
integrator, installer, and end user must store, integrate, install, and operate this equipment in 
accordance with the following guidelines. 

1.  Compliance with all product specific instructions (including but not limited to storage 

instructions, installation instructions, operating instructions, maintenance instructions, 
disposal instructions, and specifications) is required. 

2.  RTP equipment is rated for use in Installation Category (Overvoltage Category) II and 

Pollution Degree 2 environments in accordance with standard IEC 664. 

3.  To assure that an 

Operator

 is not exposed to electrical hazards, all equipment capable of 

electrical hazards must be housed in a grounded enclosure (equipment cabinet/rack) that 
limits access to the equipment only to 

Service Personnel

.  Limited access may include 

enclosure doors and side panels, which are locked or require a tool to open.  To assure 
compliance with the EMC requirements, the equipment must be housed in an enclosure 
(equipment cabinet/rack) that provides EMC shielding.  Compliance testing was 
performed in a shielded equipment rack provided by Hoffman Concept® Wall Mounted 
Enclosure model number CSD242420.  To assure compliance, the equipment must be 
installed in this style cabinet, or one with similar or greater RF attenuation characteristics.  
The cabinet should be outfitted with continuous copper finger gasketing and copper foil 
along all seams and joints. 

4.  The 

Service Personnel 

must be trained to operate the equipment and must be aware of 

the potential of electrical hazards of the equipment and of the field I/O signals connected 
to the equipment. 

5.  Hazardous voltage warning labels must be applied to the enclosure doors adjacent to the 

locking mechanisms to warn the 

Service Personnel

 that hazardous voltages are 

contained within the enclosure, if modules carrying 120 V and above are used. 

6.  Hazardous voltage warning labels also must be applied to the termination modules 

(which carry 120 V and above), adjacent to the external connectors, to warn the 

Service 

Personnel

 that hazardous voltages are present at the module's terminal blocks. 

7.  To assure compliance with the EMC requirements, the equipment must have all 

communications, power, and field signal cabling exiting the enclosure enclosed in metal 
conduits or shielded wireways.  These conduits must provide EMI/RFI shielding and must 
be terminated at the enclosure shell.  There must be no uncovered openings in the 
cabinet.  Connections between the cabinet and conduit must be made with conduit 
connectors making good (low impedance) electrical contact to the enclosure.  Input 
mains power to the enclosure and mains power fed to switching digital output I/O cards 
and modules must be filtered by AC mains filters with attenuation characteristics of 

Содержание SC3015

Страница 1: ...Technical Manual SC3015 32 Channel Digital Input Cards...

Страница 2: ...ectual property of RTP Corp unless otherwise indicated and are to be considered RTP Corp confidential This intellectual property is made available solely for the direct use of potential or licensed RT...

Страница 3: ...8 NETARRAYS CONFIGURATION 9 Card Properties 9 Mode 9 Proof Testing 9 Float Cal High 00 9 Float Cal High 01 10 Float Cal High 02 10 Integer Error Detection 10 Integer Channel Error Status 00 11 Integer...

Страница 4: ...are necessary after the initial factory setup I O bus checking diagnostics card address tests and configuration tests are performed each time the controller accesses the card All data and control tra...

Страница 5: ...1 98 mA Common Points between Channels All channels share a single common return Type of Digital Input Type 1 Logic 1 Signal Detection 79 VDC Logic 0 signal Detection 46 VDC Sample Repetition Rate 1...

Страница 6: ...annel 8 15 Channel 6 16 Channel 4 17 Channel 2 18 Channel 0 19 Not Used 20 Common Return 21 Channel 31 22 Channel 29 23 Channel 27 24 Channel 25 25 Channel 23 26 Channel 21 27 Channel 19 28 Channel 17...

Страница 7: ...gic 0 signal Detection 10 5 VDC Sample Repetition Rate 1 millisecond 1000 scans per second Sample Duration Settling Time 21 5 microseconds Input Filter characterization Order First Order Transition 3...

Страница 8: ...Channel 8 15 Channel 6 16 Channel 4 17 Channel 2 18 Channel 0 19 Not Used 20 Common Return 21 Channel 31 22 Channel 29 23 Channel 27 24 Channel 25 25 Channel 23 26 Channel 21 27 Channel 19 28 Channel...

Страница 9: ...igh 00 is a floating point voltage equal to 9 0 volts 0 09V It is derived from a fixed calibration voltage source on the card This input can be used to test the card s calibration and performance NetA...

Страница 10: ...used bits will always equal zero 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 ERR LTCH FAULT ERR DATA ERR DATA INV CARD ID CARD ERR CAL HIGH CAL LOW CH FAIL TIME OUT Bit 14 Card Error Latch This status bit i...

Страница 11: ...gh 15 For the SC3015 this register is always zero Integer Channel Error Status 01 The channel Error Status 01 is an Int Variable that returns fault indications for channels 16 through 31 For the SC301...

Страница 12: ...iable as shown below This input value is accessed by the Int Variable object with the same Tag Reconfigure the Tag as required to match the Module Form Int Value object that is used to monitor the car...

Страница 13: ...up the assigned Tag I O Tag Each input point value is accessed by the Bool Variable object NetArrays assigns a Tag to each input channel when the card is added to the I O configuration Reconfigure the...

Страница 14: ...enclosure doors and side panels which are locked or require a tool to open To assure compliance with the EMC requirements the equipment must be housed in an enclosure equipment cabinet rack that prov...

Страница 15: ...vironment These materials may include but are not limited to lead in solder and lithium in batteries 11 Prior to storage or shipping the equipment must be packaged in accordance with the following gui...

Страница 16: ...thernet Line Surge Immunity 2 kV IEC 61000 4 5 Ethernet Line Conducted RF Immunity 150 kHz to 80 MHz at 10 V IEC 61000 4 6 Pulsed Magnetic Field 300 A m IEC 61000 4 9 Modules can be ordered with optio...

Страница 17: ...in creating a hazard SERVICE PERSONNEL are assumed reasonably careful in dealing with obvious hazards CE Conformit Europ enne EMC Electro Magnetic Compatibility EMI Electro Magnetic Interference EC Eu...

Отзывы: