5
Specifications
Module Safety Integrity Level:
SIL-2 with termination modules 3099/17-100 or 3099/24-100
SIL-3 with termination modules 3099/18
Card Address:
Determined by the slot of the controller backplane
Number of channels:
16
Common Points between Channels: All channels are isolated from each other
Isolation Voltage:
500 Volts Field Output to Chassis Ground
250 Volts Channel to Channel
Type of protection:
Optically isolated and fuse protected on termination modules
Maximum Peak Voltage:
600 Volts
Maximum permanent allowed
voltage (no damage):
240 VAC
Maximum Closed Circuit Current:
2 A per channel, fuse protected to 2 A slow acting
Total Output Current per Card:
32 A
Output Configuration:
One non-latching Triac per channel
Maximum Power Per Channel:
480 VA
Minimum Load per Channel:
50 mA
Maximum Leakage Current
per Channel:
1.5 mA
Maximum Voltage Drop:
1.6 Volts at 2 A
Surge Current:
25 A peak for 25 ms repeated no more than 2 times per
second
Zero Switching Point:
0 ± 5 Volts, typical at 60 Hz
0 ± 20 Volts, maximum at 60 Hz
Critical Rate of Rise of
500 V/
s minimum
OFF-State Voltage:
750 V/
s typical
(Voltage transients with slopes lower than this specification
will not cause the triacs to turn on)
Critical Rate of Rise of
20 A/
s repetitive
ON-State Current:
100 A/
s non-repetitive
Critical Rate of Removal of
12 A/ms minimum
ON-State Current:
25 A/ms typical
Channel Self Tests:
All channels are tested within 10 seconds.
Output Test Pulses:
A channel is turned OFF for half an AC cycle.
Output behavior:
During interruptions of MPU control, voltage dips and
interruptions and power up/down sequences, all channels
will be de-energized to the OFF state.