59
Card Switch Settings Required To Set Alarm Sequences
Switch Suffix Number
Sequence
Card
Channels
Switch
-S1
-S2
-S3
-S4
-S5
-S6
-S7
Page
ISA-M
Manual Reset
Alarm
1 - 2
SW3
ON ***
ON ***
OFF
OFF
OFF
OFF
OFF
18
3 - 4
SW5
ON ***
ON ***
OFF
OFF
OFF
OFF
OFF
SPR
1 - 2
SPR Card is supplied in Sequence ISA-M ONLY
ISA-A
Automatic Reset
Alarm
1 - 2
SW3
ON ***
ON ***
OFF
OFF
OFF
ON
OFF
3 - 4
SW5
ON ***
ON ***
OFF
OFF
OFF
ON
OFF
ISA-A-4
Non Lock In
Alarm
1 - 2
SW3
ON ***
ON ***
OFF
OFF
ON
ON
OFF
19
3 - 4
SW5
ON ***
ON ***
OFF
OFF
ON
ON
OFF
ISA-R
Ringback
Alarm
1 - 2
SW3
ON
ON
OFF
ON
OFF
OFF
OFF
3 - 4
SW5
ON
ON
OFF
ON
OFF
OFF
OFF
ISA A-5-6
Status Only
Alarm
1 –2
SW3
ON
OFF
OFF
OFF
ON
ON
OFF
3 - 4
SW5
ON
OFF
OFF
OFF
ON
ON
OFF
***
The above Sequences can be set to be FAST or SLOW FLASH using the following
Flash Rate
Card
Channels
Switch
-S1
-S2
Fast Flash
Alarm
1 - 2
SW3
ON
ON
Slow Flash
1 - 2
SW3
OFF
OFF
Fast Flash
3 - 4
SW5
ON
ON
Slow Flash
3 - 4
SW5
OFF
OFF
First-Up Alarm Sequences
ISA-F1A
Alarm
1 - 2
SW3
ON
OFF
OFF
OFF
OFF
ON
ON
20
3 - 4
SW5
ON
OFF
OFF
OFF
OFF
ON
ON
ISA-F2M-1
Alarm
1 - 2
SW3
OFF
ON
OFF
OFF
OFF
OFF
ON
3 - 4
SW5
OFF
ON
OFF
OFF
OFF
OFF
ON
Table 30
Switch Settings Per Alarm Sequence
Содержание UC625 series
Страница 1: ...1 UC625 Compact Alarm Annunciator Rev 17...