8
heating requirements, you can reduce the current to reduce the heat of the generator, but
the output torque of the motor will be reduced at the same time. If you do not require
continuous operation of the motor, you can increase the operating current appropriately to
obtain greater torque, but be careful not to exceed 1.5 times the rated current of the motor.
4.2 Automatic Half Flow Settings
SW4 sets the driver's automatic current reduction percentage. When the switch is set
to OFF, the idle current will be reduced to 50% of the running current; when the switch is
set to ON, the idle current will be reduced to 100% of the running current.
After the driver stops receiving the pulse for 2 seconds, it enters the idle state.
The time to enter the idle state and the percentage of standby current can be set
through the USB port.
4.3 Subdivision Settings
Phase current peak A
SW1
SW2
SW3
0.5
ON
ON
ON
0.7
OFF
ON
ON
1.0
ON
OFF
ON
1.5
OFF
OFF
ON
2.0
ON
ON
OFF
2.5
OFF
ON
OFF
3.0
ON
OFF
OFF
3.5
OFF
OFF
OFF
Pulse number / turn
SW5
SW6
SW7
SW8
500
ON
ON
ON
ON
1000
OFF
ON
ON
ON
1250
ON
OFF
ON
ON
2000
OFF
OFF
ON
ON
2500
ON
ON
OFF
ON
4000
OFF
ON
OFF
ON
5000
ON
OFF
OFF
ON
10000
OFF
OFF
OFF
ON
12500
ON
ON
ON
OFF