Real Time Automation, Inc.
66
1-800-249-1612
b.
“Invalid Parameter Data Type” – The BACnet MS/TP Master is not using a data type that the
gateway is expecting.
c.
“Invalid Tag” – The BACnet MS/TP Master did not format the message how the gateway is
expecting.
d.
“Parameter Out of Range” – The BACnet MS/TP Master is asking for information outside of
the gateway's defined range.
4)
BMS: Message Error “XXXXX”- The gateway is sending an error message due to the listed
explanation:
a.
“Inconsistent parameters” -
i.
The BACnet MS/TP Master tried to write a priority that was out of range or reserved
(Priority 6) and was rejected.
ii.
The BACnet MS/TP Master tried to write to ALL, REQUIRED, or OPTIONAL object
property.
b.
“Invalid Data Type” – The BACnet MS/TP Master tried to use a data type with an object that
is not supported.
c.
“Service request denied” – The BACnet MS/TP Master request cannot be processed at this
time because the BACnet MS/TP connection is not established.
d.
“Read access denied” – The BACnet MS/TP Master read request cannot be processed.
e.
“Unknown object” – The BACnet MS/TP Master tried to access an object the gateway does
not support.
f.
“Unknown property” –The BACnet MS/TP Master tried to access a property the gateway
does not support for that object type.
g.
“Unsupported object type” – The BACnet MS/TP Master tried to access an object type the
gateway does not support.
h.
“Value out of range” – The BACnet/IP message could not be completed because the passed
value was not in the valid range.
i.
“Write access denied” – The BACnet MS/TP Master tried to write a non-writeable property
in the gateway.
j.
“Invalid array index” –
i.
The BACnet MS/TP Master tried to write a priority that was out of range or reserved
(Priority 6) and was rejected.
ii.
The BACnet MS/TP Master tried to write an array for an object or property that
doesn’t have an array index.
k.
“Unknown device” – Gateway is trying to send a message to a device we have not had
previous communication with on the network.
l.
“Timeout” – BACnet MS/TP message timed out.
m.
“Resources busy” – BACnet MS/TP message cannot be processed at this time.
n.
“Segmentation not supported” – BACnet MS/TP message is too large to send in one
message.
o.
“Service not supported” – The BACnet MS/TP Master tried to perform a service that the
gateway does not support.
p.
“Abort Other” – BACnet MS/TP message is aborted for an unknown reason.
q.
“Invalid Tag” – BACnet MS/TP message is not how we expect.
r.
“Unknown” – BACnet MS/TP message error for an unknown reason.