c.
“Invalid Tag” – BACnet/IP message is not how the gateway expects the message.
d.
“Parameter Out of Range” – The BACnet/IP Client is asking for information outside of the
gateway's defined range.
4.
BS: Message Error “XXXXX”- The gateway is sending an error a message due to the listed
explanation:
a.
“Inconsistent parameters” -
i.
BACnet/IP Client tried to write a priority that was out of range or reserved (Priority 6) and
was rejected.
ii.
BACnet/IP Client tried to write to ALL, REQUIRED, or OPTIONAL object property.
b.
“Invalid Data Type” – BACnet/IP Client tried to use a data type with an object that is not
supported.
c.
“Service request denied” – BACnet/IP request cannot be processed at this time because the
BACnet/IP connection is not established.
d.
“Read access denied” – BACnet/IP read request cannot be processed.
e.
“Unknown object” – BACnet/IP Client tried to access an object our gateway does not
support.
f.
“Unknown property” – BACnet/IP Client tried to access a property our gateway does not
support for that object type.
g.
“Unsupported object type” – BACnet/IP Client tried to access an object type our gateway
does not support.
h.
“Value out of range” – BACnet/IP message could not be completed because the passed
value was not in the valid range.
i.
“Write access denied” – BACnet/IP Client tried to write a non-writeable property in our
gateway.
j.
“Invalid array index” –
i.
BACnet/IP Client tried to write a priority that was out of range or reserved (Priority 6) and
was rejected.
ii.
BACnet/IP Client tried to write an array for an object or property that doesn’t have an
array index.
k.
“Unknown device” – Gateway is trying to send a message to a device we have not had
previous communication with on the network.
l.
“Timeout” – BACnet/IP message timed out.
m.
“Resources busy” – BACnet/IP message cannot be processed at this time.
n.
“Segmentation not supported” – BACnet/IP message is too large to send in one message.
o.
“Service not supported” – BACnet/IP Client tried to perform a service that our gateway does
not support.
p.
“Abort Other” – BACnet/IP message is aborted for an unknown reason.
q.
“Invalid Tag” – BACnet/IP message is not how we expect.
r.
“Unknown” – BACnet/IP message error for an unknown reason.
Real Time Automation, Inc.
54
1-800-249-1612