Real Time Automation, Inc.
32
1-800-249-1612
3)
In the Data Mapping page, manually add 2 additional mappings identical to the example below.
4)
Update all your Read Scan Line PLC tags with data.
5)
Nothing should have updated in your ASCII device.
6)
Update the RTA_Opt_Trigger PLC tag to 1.
7)
Now your ASCII device will be updated with the data.
8)
Increment the RTA_Opt_Trigger PLC tag
9)
Your ASCII device will get update again, regardless if data is new or not.
If your product is a Web Interface e.g. 460ETCWI acting only as a Client:
1)
On the WI configuration page change the Update Method to be Triggered.
2)
In the Data Mapping page, manually add 2 additional mappings identical to the example below.
Содержание 460ETCQT-N2E