Real Time Automation, Inc.
62
1-800-249-1612
9)
EM Messages: Number of Class 3 Explicit Messages received (it is assumed the gateway always
responds; the log can detect dropped packets)
Note:
Sum of all connections
Common Error Strings
1)
Connection already in use:
a)
The gateway already has a connection in use
2)
More than one guy configuring:
a)
Attempting to open Exclusive Owner/Output Only connection that is already established
3)
Connection size mismatch:
a)
Connection Input / Output Size set up in the scanner does not match what is in the gateway
4)
Connection unconfigured:
a)
The adapter configuration in the gateway is blank
5)
Unsupported RPI:
a)
The RPI value is most likely too small
6)
Invalid Path Segment:
a)
The path specified by the scanner is not valid in the gateway’s adapter