SURGE Series Lightning and Transient Protector 

Installation Manual 

 
 

ELM0100A 

 

Page 5 

 

 

F

IGURE 

3-2

  

L

OOSENING THE CABLE GLAND

 

 

 

2

 

Remove the black cable plug from the cable gland. 

3

 

Loosen the 4 Phillips screws on the top of the NEMA-4X enclosure. Lift the cover off. 

4

 

Insert the cables with stripped wire ends through the cable glands and into the 
enclosure. Ensure the cable sheathes are inside the enclosure. 

5

 

Loosen the screws on the terminal with a small flat-head screwdriver. 

6

 

Wire the leads to the terminal. Table 3-1 provides a recommended wiring scheme. It 
is important to note that, aside from the shield, the order of the wires does not matter. 
However, it is critical that the order of the wires is maintained on both sides of the 
surge protector (for example, if the red wire is connected to 1 on the line side of the 
surge protector, the red wire MUST be connected to 1 on the protected side).  

T

ABLE 

3-1

  

R

ECOMMENDED WIRING SCHEME

 

Protected Side 

Line Side 

Red 

Red 

 Black 

Black 

Green 

Green  

White 

White 

Shield 

SH 

SH 

Shield 

 

CAUTION:

 

E

NSURE THE ENTIRE NUT BODY DOES NOT LOOSEN

.

 

L

OOSEN ONLY THE 

GLAND

Содержание SURGE 16N

Страница 1: ...this document RST Instruments Ltd reserves the right to change the information at any time and assumes no liability for its accuracy Copyright 2019 RST Instruments Ltd All rights reserved Document Num...

Страница 2: ...SURGE Series Lightning and Transient Protector Installation Manual ELM0100A Page i REVISION HISTORY Rev Revision History Date Prepared By Approved By A Initial release 2019 Oct 02 MP CB...

Страница 3: ...ETY 2 3 INSTALLATION 3 3 1 Pre Installation 3 3 2 Tools 4 3 3 Installation Procedure 4 4 GROUNDING 6 5 SERVICE AND REPAIR 7 SPECIFICATIONS 8 LIST OF FIGURES Figure 1 1 4N 4 wire and shield stand alone...

Страница 4: ...instruments and loggers are susceptible to transient electrical fields which can be destructive to both sensors and data loggers RST s SURGE Series lightning and transient protectors can be installed...

Страница 5: ...stand alone transient protector in a NEMA 4X enclosure Figure 1 2 Both models are designed to be installed directly on the cable with the sensor or instrument wired to the Protected Side of the surge...

Страница 6: ...uld not be submerged and should be placed slightly above the ground Figure 3 1 illustrates a typical installation Please note that site specific conditions may require adaptations Contact RST with any...

Страница 7: ...ewdriver Wire strippers and Utility knife 3 3 INSTALLATION PROCEDURE The following instructions outline the steps for successfully installing a surge protector Though the instructions feature the SURG...

Страница 8: ...lat head screwdriver 6 Wire the leads to the terminal Table 3 1 provides a recommended wiring scheme It is important to note that aside from the shield the order of the wires does not matter However i...

Страница 9: ...been planted into the ground The following instructions detail the steps necessary to correctly ground stand alone units 1 Select a location to install the grounding rod 2 Plant the grounding rod fir...

Страница 10: ...Secure the cable to the grounding rod with the clamp by tightening the bolt Please contact RST directly with any questions pertaining to the installation of the grounding stake 5 SERVICE AND REPAIR Th...

Страница 11: ...eld Maximum transient current per line 1 event 8 20 s 20 000 Amps Minimum conduction threshold voltage 58 Volts Peak pass through voltage common or normal mode 77 Volts Output clamp voltage 4 Volts Se...