F24 - Low temperature alarm:

It is the temperature below that which the instrument will visually display the low temperature alarm 

[atlo]

 as well as the audible alarm (Buzzer). The differential for switching off the alarm is fixed at 

0.1°C / 1°F. This alarm considers the temperature shown on the display, thus being influenced by the 
temperature indication that was locked during the defrost 

[,f18]

. To disable this alarm, simply set this 

function to the minimum value until 

[,,no] 

is displayed.

F25 - High temperature alarm :

It is the temperature above that which the instrument will visually display the high temperature alarm

  

[athi]

 as well as the audible alarm (Buzzer). The differential for switching off the alarm is fixed at 

0.1°C / 1°F. This alarm considers the temperature shown on the display, thus being influenced by the 
temperature indication that was locked during the defrost 

[,f18]

. To disable this alarm, simply set this 

function to the maximum vale until 

[,,no]

 is displayed.

Note:

 For safety, output OUT1 is switched off if the controller is configured for heating and a high 

temperature  alarm 

[athi]

  occurs,  or  if  it  is  configured  for  cooling  and  a  low  temperature  alarm 

[atlo]

 occurs, therefore, you must set the alarm limits above (if heating) or below (if cooling) the 

desired temperature (setpoint of output OUT1).

F26

 

- Output Operating Mode OUT2:

Select the operating mode of the OUT2 output.

[,,,1]

- Extra alarm-absolute range

: It considers the values defined in

[,F24]

 and 

[,F25]

as 

minimum and maximum values to trigger the alarm output.

[,,,2]

- Extra alarm-setpoint range: 

It considers the active receipt setpoint 

[Rc1,]

 or 

[Rc2,]

 

and the absolute values defined in

[,F24]

 and 

[,F25]

, that is, the positive value of these functions 

as minimum and maximum values to trigger the alarm output.

For example:

Desired temperature

 [SP,,]

: - 5ºC

Low temperature alarm 

[,F24]

: 2ºC

High temperature alarm 

[,F25]

: 2ºC

City Limits: (

[SP,,]

-

 [,F24]

 and 

[SP,,]

[,F25]

).

The low temperature alarm will go off at -7°C (-5-2) and the high temperature alarm at -3°C (-5+2).

[,,,3]

- Electric defrost (using resistances): 

Where only the OUT2 output is activated during the 

defrost process.

[,,,4]

- Hot gas defrost 

: Where the compressor outputs OUT1 and OUT2 are activated during the 

defrost process.

[,,,5]

- Output OUT2 as NF

 

of output OUT1

: In this option, the OUT2 output is activated when the 

OUT1 output is deactivated, regardless of the state (cooling / heating or defrost), except when the 
sensor is in error 

[,F20]

.

[,,,6]

- OUT2 output as ventilation

: In this mode, the output will be used to activate a fan that will 

remain on during the defrost interval. While the controller is cooling, the output will remain in operation 
according to the configuration selected in function

 [,F27]

- Fan Operation Mode during cooling. 

[,,,7]

- OUT2 output as an auxiliary compressor

: The output will be used to start a seconds 

compressor. Output OUT2 will be activated immediately after output OUT1 is activated, according to the 
value  configured  in  function

 [,F31]

-  Delay  between  the  activation  of  compressors,  and  always 

switched off together with output OUT1.

Note 1:

 

If the OUT2 output is configured to work different than an alarm, the absolute alarm indications 

are still visual (messages on the display) and audible (if the buzzer is enabled)

Note 2:

 If the OUT2 output is configured for defrost (electric or hot gas), after the defrost time has 

elapsed, a fixed time of 2 minutes is counted for drainage. This time is necessary for dripping, that is, for 
the last drops of water to drain from the evaporator. During this period, outputs OUT1 and OUT2 remain 
off.

Note 3:

 If output OUT2 is configured for ventilation, and if a sensor error occurs, output OUT2 will be 

activated  and  deactivated  together  with  output  OUT1,  that  is,  if  OUT1  is  activated  OUT2  remains 
activated,  and  will  continue  to  work  together  according  to  the  configuration  selected  in  function 

[,F20]

 - Compressor status with the sensor disconnected.

F27 - Fan operation mode during cooling:

Selects the operating mode of the OUT2 output when 

[,F26]

 = 6.

[,,,0]

 - OUT2 output remains activated as long as OUT1 output (compressor) is activated. When the 

compressor is off by setpoint, the OUT2 output will be cyclically activated according to the values 
configured in the functions 

[,F28]

 - Fan Time On and 

[,F29]

 - Fan Time Off;

[,,,1]

 - Output OUT2 will remain on regardless of output OUT1;

[,,,2]

 - OUT2 output will remain on as long as OUT1 output is on and off when OUT1 output is turned 

off.

F28 - Fan On Time:

F29 - Fan Off Time:

Define fan on time 

[,F28]

 and fan off time

[,F29]

 when the controller is in refrigeration mode 

(

[,F04]

 = 0) with output OUT1 turned off by temperature (setpoint) and OUT2 configured for fan 

control (

[,F26]

 = 6) and operating in cyclic mode (

[,F27]

 = 0)

F30 - Fan Delay:

Defines the time (delay) before activating the OUT2 output (if configured as fan 

[,F26]

 = 6) after the 

start of a new refrigeration cycle.

F31 - Delay between compressors being turned on:

Defines  the  time  (delay)  before  activating  the  OUT2  output  (if  configured  as  auxiliary  compressor 

[,F26]

 = 7). Every time the OUT1 output is activated, the time configured in this function will elapse 

before activating the OUT2 output.

F32 - Alarm inhibition time when energizing the controller:

 

This is the time during which the alarm remains off even under conditions of alarm during the instrument 
start-up. This time will be counted after elapsing of the time configured in 

[,F19]

. This function can be 

switched off by setting it at the minimum value 0 

[no,,]

.

F33 -Alarm inhibition time by temperature:

 

With this configuration active, the temperature will need to remain in the alarm condition during the 
inhibition time set, for the alarm to be indicated. That way one can prevent alerts resulting from specific 
temperature variations, and after defrost.

F34 - Enable buzzer (0-Disabled/1-Enabled):

Allows enabling and disabling of the internal buzzer for alarm signaling.

F35 - Digital input operation mode: 

Select the operatiing mode of the digital input.

[no,,]

- Disabled 

[,,,1]

- Digital input: Door open (active when closing contact)

[,,,2]

- Digital input: Door open (active when opening contact)

[,,,3]

- Digital input: External alarm / power failure (active when closing contact)

[,,,4]

- Digital input: External alarm / power failure (active when opening contact)

[,,,5]

- Digital input: Door open and power failure (active when closing contact)

[,,,6]

- Digital input: Door open and power failure (active when opening contact)

[,,,7]

- Digital input: Push-button type switch (button) to manually start/stop defrost

[,,,8]

- Digital input: Push-button type switch (button) to switch the control functions off or on

F36 - Output on time in OUT2 alarm status:

F37 - Output off time in OUT2 alarm status:

Selects the cycling time in seconds of the alarm output when it is active. If any of those functions are set 
with a value of 

[,,,0]

 the output will be permanently active.

 

F38 - Open door time for alarm:

 

If the door remains open for a time equal to, or greater than, the one configured in this parameter, the 
controller will set off a visual open door alarm

 

[AOPn]

 and the audible alarm (Buzzer).

The alarms are suspended upon the door closing. The audible alarm may be inhibited through the 

>

 

key (pressed for 2s). This function can be switched off by setting it at the minimum value 0 

[no,,]

.

Note 1:

 In order for the open door alarm to operate, the function “Digital input operating mode” 

[,F35]

 

must be configured as open door contact.
The audible alarm is activated only if the buzzer is enabled in the function “Enable Buzzer (0-Disabled 
/1-Enabled)” 

[,F34]

.

Note 2:

 If the function “Digital input operating mode” 

[,F35]

 is configured as open door contact, the 

open door indication 

[OPEn]

 will be displayed every time the door is open, except for the cases of 

alarm.

F39 - Operating mode of the digital filter:

[,,,0]

- The filter acts both on the rise as on the decrease temperature.

[,,,1]

- The filter acts only in the temperature rise ramp. When the temperature falls, your response 

will be immediate.

F40 -Digital filter intensity applied to the sensor:

This filter has the purpose of simulating increase in thermal mass at the sensor thereby increasing its 
response time (thermal inertia). The higher the value set in this function, the more time the sensor takes 
to respond.
This function can be switched off by setting it at the minimum value 0

[no,,]

.

F35 =

[,,,3]

1

5 6

2 3 4

SENSOR

NC

NC

Vca

A1

A2

F35 =

[,,,4]

1

5 6

2 3 4

SENSOR

NO

NO

Vca

A1

A2

Examples of connection for detecting open door alarm:

This configuration may be used for the

 

MT-514

e

 Faston

 

to detect whether the door has been left 

open for a time above the value set up in “

[,F33]

 - Time with open door to trigger alarm”. In this 

configuration, the message 

[AOPn]

 is displayed when an open door alarm is detected. To that end, the 

user may use the NO or NC pushbuttons (not supplied) connected to the digital input, as shown in 
examples below:

F35 =

[,,,1]

1

5 6

2 3 4

SENSOR

NC

Door contact

F35 =

[,,,2]

1

5 6

2 3 4

SENSOR

NO

Door contact

Examples of connection for power outage detection:

This configuration may be used when 

MT-514

e

 Faston

 is being energized by a 12/24 V DC 

battery (common in vaccine refrigerators) and one wants to detect when a power outage occurred 
(115/230 V AC). In this configuration, the message

[AVoL]

 is displayed when alarm is detected for 

power outage. To that end, the user may utilize a contactor or auxiliary contact (not supplied), where NC 
(

[,F30]

=

[,,,3]

)  or  NO  (

[,F30]

=

[,,,4]

)  contacts  are  connected  to  the  digital  input  and 

contacts A1 and A2 (contactor coil) are connected to the power system, as shown in examples below:

Example of connections for detecting open door and power outage:

This configuration may be used to detect power outage alarm (115/230 V AC) and also to detect that the 
door has been left open (either one event).
In those configurations, the messages 

[AVoL]

 and 

[AOPn]

are displayed alternately when alarm 

event is detected (power outage or open door alarm).
For this purpose, the user may use the pushbuttons (not supplied) and a contactor or auxiliary contact 
(not supplied) connected in series or in parallel, as shown in examples below:

F35 =

[,,,6]

Serial connection

1

5 6

2 3 4

SENSOR

NO

NO

Vca

A1

A2

NO

Door contact

F35 =

[,,,5]

Parallel connection

1

5 6

2 3 4

SENSOR

NC

NC

Vca

A1

A2

NC

Door contact

Содержание LogiTemp MT-514E FASTON

Страница 1: ...LogiTemp Electronic Controller System Operations Manual Full Gauge Version MT514 PN 171571 REV 3 22 ...

Страница 2: ...bles can be increased by user himself to up to 200 meters using a PP2x24 AWGcable 5 3 Recommendations of IEC60364 standard a Installoverloadprotectorsinthecontrollersupply b Install transient suppressors suppressor filter RC in the circuit to increase the service life of the controllerrelay Seeconnectioninstructionsofthefilteronthepreviouspage c The sensor cables may be together but not in the sam...

Страница 3: ...ck touch maximum and minimum temperature display Hold down for 2 seconds inhibit audible alarm buzzer Pressed for 5 seconds turn on turn off the control functions Vinylprotector ImageIX item13 Protects the controller should when installed in a place with splashing water such as in refrigerated counters Thisadhesivevinylaccompaniestheinstrument onthepackaging IMPORTANT Applyonlyaftercompletingelect...

Страница 4: ...state when powering up the instrument Temperature indication locked during defrost Delay in powering up the instrument delay Compressor status with sensor disconnected Time the compressor was on in case of an error Time the compressor was off in case of an error Max Time the compressor was on without reaching the setpoint Low temperature alarm High temperature alarm Output Operating Mode OUT2 Fan ...

Страница 5: ... if configured as auxiliary compressor F26 7 Every time the OUT1 output is activated the time configured in this function will elapse beforeactivatingtheOUT2output F32 Alarminhibitiontimewhenenergizingthecontroller This is the time during which the alarm remains off even under conditions of alarm during the instrument start up This time will be counted after elapsing of the time configured in F19 ...

Страница 6: ...of end of defrost process Control functions off Contact Full Gauge Controls Reconfigure the values of the functions OFF eCAL pppp Low temperature alarm Atlo inib LOC On LOC OFF AVoL AOPn OpEn Power outage alarm indication Open door alarm indication Open door indication Functions lockdown Unlocking of functions Buzzer inhibited Athi ALrC High temperature alarm Compressor reached maximum time on lim...

Страница 7: ...t covered either natural wear and tear of parts external damage caused by falls or inadequate packaging of products LOSS OF WARRANTY Products will automatically lose its warranty in the following cases The instructions for assembly and use found in the technical description and installation procedures in Standard IEC60364 are not obeyed The product is submitted to conditions beyond the limits spec...

Страница 8: ... U Hudson WI 54016 800 955 5253 Norlake Foodservice Sales 800 477 5253 Norlake Scientific Sales 800 388 5253 Norlake Parts Service 800 647 1284 Master Bilt Sales 800 684 8988 Master Bilt Parts Service Email rsgservice refsg com PN 171571 REV 3 22 ...

Отзывы: