FOCUS 250 Owner's Manual
18
RSF Woodburning Fireplaces
CHASE ENCLOSURE
If the chimney runs up the outside of the house, we
recommend that it be enclosed in a chase structure. The
chase should be constructed in such a way that it is an
extension of the home (see Figure 13). It should be well
insulated between the footings and the floor of the home to
prevent heat loss. If the climate in your area is mild, insulate
the chase at least to the first firestop. If the climate in your
area is very cold, insulate the chase to the top to keep the
chimney warmer, increase the draft, and reduce creosote
buildup. We also recommend insulating the ceiling of the
chase just as if it were in the attic space. This will prevent
cold air from dropping down through the chase and into the
room where the fireplace is installed (see Figure 13).
Some local codes require that the walls be insulated, vapor
sealed and sheathed with a fire rated gypsum board (see
Figure 13). We strongly recommend this procedure for all
installations to prevent cold drafts from originating in the
fireplace enclosure. If you follow this procedure, we
recommend that you do not insulate the wall above the front
of the fireplace.
REMEMBER:
Check local codes concerning installation
requirements and restrictions in your area.
MASONRY CHIMNEY
Installing your FOCUS 250 fireplace with a masonry chimney
still requires using EXCEL chimney from the top of the
fireplace to where it will connect to a listed liner that will run
up inside the masonry chimney (see Figure 14).
The stainless steel liner should be fitted inside the clay liner all the way to the top of the masonry chimney. It is not
meant to replace the clay liner. You can use either the EXCEL liner or any other listed liner to ULC-S635, ULC-
S640 or UL-1777.
Special care is to be taken to make sure that you have a good solid connection between the EXCEL chimney and
the liner. A masonry adaptor (FO-FDM7) was designed specifically for that purpose and is available from your RSF
dealer. It will attach to the liner with 3 stainless steel rivets (provided) and to the EXCEL chimney with 3 screws
(provided).
After mortaring in place, the connection
between the EXCEL chimney and the liner
should not be visible in order to isolate the
heat released through the liner from the
fireplace enclosure.
As depicted in Figure 14, you must install
at least one 18" length of EXCEL chimney
after the EXCEL chimney elbow. The
uppermost part of the EXCEL chimney -
where it enters the masonry chimney -
must be a minimum of 12" from the ceiling.
NOTE:
If the ceiling is high enough, you
can install one or more EXCEL chimney
lengths directly on the fireplace before the
elbow.
If you use a flexible liner, make sure to be
careful when cleaning to ensure that the
stainless steel flexible liner is not
dislodged in any way.
Figure 13 Chimney Installed with a Chase
Enclosure Example
Figure 14 Connection to a Masonry Chimney
10'
2' min.
Optional
Decorative
Shroud
Insulation
Chase liner of fire rated
gypsum board is
recommended (may be
required by local authorities)
Radiation
Shield,
with Storm
Collar in
the Attic
RS
F
Fi
re
pl
ac
e
Mortar
Mortar
Clearances as per
NBC or NFPA 211
EXCEL liner or other listed liner to
ULC-S635, ULC-S640 or UL-1777
12" min. to
combustible ceiling
EXCEL chimney
lenght: 18" min.
EXCEL chimney
elbow
Masonry Adaptor
FO-FDM7
Metal
Firestop
Liner
Elbow
RS
F
Fi
re
pla
ce