ROXELL -
031 - 0516
FLEX- AUGER - INSTALLATION INSTRUCTIONS
III- 77
MAXIMUM CABLE LENGTHS TO THE MOTORS
Calculation method:
IEC-HD 60364-5
Cable type:
PVC – XLPE – Silicon
Placing:
Open cable trough
Materials used:
Schneider Electric GV2 motor protections
Please be aware that you have to follow the local regulations for your country!
Motor Power (kW)
Net voltage
Protection
Max. cable length (m)
Wire gauge (mm²)
0.18
1x230V 50Hz
GV2ME07
0 - 110
1.5
111 - 185
2.5
186 - 297
4
3x230V 50Hz
GV2ME06
0 - 174
1.5
175 - 290
2.5
291 - 464
4
3x400V 50Hz
GV2ME05
0 - 492
1.5
493 - 821
2.5
822 - 1314
4
0.22
3x220V 60Hz
3x230V 60Hz
GV2ME06
0 - 167
1.5
168 - 279
2.5
280 - 446
4
3x380V 60Hz
3x400V 60Hz
GV2ME05
0 - 471
1.5
472 - 785
2.5
786 - 1257
4
0.25
1x230V 50Hz
GV2ME07
0 - 110
1.5
111 - 185
2.5
186 - 297
4
3x230V 50Hz
GV2ME06
0 - 174
1.5
175 - 290
2.5
291 - 464
4
3x400V 50Hz
GV2ME05
0 - 492
1.5
493 - 821
2.5
822 - 1314
4
0.37
1x230V 50Hz
GV2ME08
0 - 69
1.5
70 - 116
2.5
117 - 185
4
3x230V 50Hz
GV2ME07
0 - 111
1.5
112 - 185
2.5
186 - 297
4
3x400V 50Hz
GV2ME06
0 - 308
1.5
309 - 513
2.5
514 - 821
4
0.45
3x220V 60Hz
3x230V 60Hz
GV2ME07
0 - 107
1.5
108 - 178
2.5
179 - 285
4
3x380V 60Hz
3x400V 60Hz
GV2ME06
0 - 294
1.5
295 - 491
2.5
492 - 785
4
0.55
3x230V 50Hz
GV2ME08
0 - 69
1.5
70 - 116
2.5
117 - 185
4
3x230V 50Hz
GV2ME07
0 - 111
1.5
112 - 185
2.5
186 - 297
4
3x400V 50Hz
GV2ME07
0 - 197
1.5
198 - 328
2.5
329 - 525
4
3x400V 50Hz
GV2ME06
0 - 308
1.5
309 - 513
2.5
514 - 821
4
Содержание FLEX-AUGER FA 125
Страница 6: ......
Страница 11: ...I 1 PART I INSTRUCTIONS FOR THE USER ...
Страница 12: ...FLEX AUGER INSTRUCTIONS FOR THE USER ROXELL 031 0516 I 2 ...
Страница 24: ...ROXELL 031 0516 FLEX AUGER COMPONENTS II 2 FIGURE 1 GENERAL VIEW ...
Страница 86: ...ROXELL 031 0516 FLEX AUGER COMPONENTS II 64 GENERAL LAY OUT OVERHEAD SYSTEM FIGURE 5 A B C ...
Страница 96: ......
Страница 97: ...III 1 PART III INSTALLATION INSTRUCTIONS ...
Страница 98: ...ROXELL 031 0516 FLEX AUGER INSTALLATION INSTRUCTIONS III 2 ...
Страница 100: ...ROXELL 031 0516 FLEX AUGER INSTALLATION INSTRUCTIONS III 2 FIGURE 1 GENERAL VIEW ...
Страница 108: ...ROXELL 031 0516 FLEX AUGER INSTALLATION INSTRUCTIONS III 10 FLEX AUGER FROM HOPPER TO HOUSE FIGURE 7 1 1 2 2 3 4 ...
Страница 110: ...ROXELL 031 0516 FLEX AUGER INSTALLATION INSTRUCTIONS III 12 FIGURE 10 LOCATION OF THE OUTLETS CDS STANDARD ...
Страница 111: ...ROXELL 031 0516 FLEX AUGER INSTALLATION INSTRUCTIONS III 13 FIGURE 11 LOCATION OF THE OUTLETS CDS BROILER CAGE ...
Страница 132: ...ROXELL 031 0516 FLEX AUGER INSTALLATION INSTRUCTIONS III 34 FIGURE 59 MODEL 125 Max 45º pellets Max 30º meal FIGURE 60 ...
Страница 166: ...ROXELL 031 0516 FLEX AUGER INSTALLATION INSTRUCTIONS III 68 FIGURE 135 ...
Страница 167: ...ROXELL 031 0516 FLEX AUGER INSTALLATION INSTRUCTIONS III 69 GENERAL LAY OUT OVERHEAD SYSTEM FIGURE 136 A B C ...
Страница 170: ...ROXELL 031 0516 FLEX AUGER INSTALLATION INSTRUCTIONS III 72 FIGURE 140 Caulking 03000904 2x 22x B ...
Страница 177: ......