Electrical connections  

The power supply 

has to be connected

 

to G+ and G0. G0 is considered as system ground. 

The same 

ground reference has to be used for

 

the 

CF8-D/W-IN 

unit and for any connected device!

  Unless 

different transformers are used, special precautions need to be taken. 

PLEASE NOTE! 

The signal ground is not  galvanically separated from 
the 

CF8-D/W-IN 

power supply! 

The same ground reference has to be used for the 

CF8-D/W-IN 

unit and for any connected device! 

If possible keep the sensor powered up after mounting 
in order to avoid condensation. Connect the analogue 
output before measuring. 

 

When the installation is complete an automatic zero 
point calibration (AZC) must be done. An automatic 
zero point calibration (AZC) must be done at least once 
a year according to warranty limitations. 
 

 

Connection  

Terminal 

 

Function 

 

Electrical Data 

 

Remarks 

G+ 

 
 

G0 

Power (+) 

 
 

Power ground (-) 

24 VAC/DC+  (+-20%), 3W 

 
 

24 VAC/DC 

Brown 
2W without output load 
 
White 

See note 1! 

OUT 1 

 
 
 
 

OUT 2 

 
 

Analogue Output 1 (+) 

 
 
 
 

Analogue Output 2 (+) 

 
 

4-20 mA or 2-10VDC 

 

 
 
 

0-10mA or 0-5VDC 

 

Yellow 
According to positions of 
OUT1 jumper.

 See note 2 

and 3

!

 

 
Green 
According to positions of 
OUT2 jumper.

 See note 2 

and 3

!

 

 

 

Table I.  Electrical terminal connections for 

CF8-D/W-IN 

 

Note 1:   The ground terminal is used as negative power supply DC input or AC phase ground G0 
(halfwave rectifier). The signal ground is the same as power ground G0 (permitting a ”3-wire” 
configuration). A single transformer may be used for the entire system. 

Note 2:

  

CF8-D/W-IN 

can deliver both a voltage or a current loop for OUT1/OUT2. To change between 

voltage and current output mode the hardware jumpers are used. There is one jumper

 

for OUT1 and 

one for OUT2, so that one output can be a voltage output and the other a current output. 

Note 3:  During start up the unit may deliver up to 10 VDC or 20 mA for up to half a second. 

 