Smart Positioner
YT-3700 / 3750
Product Manual
Ver. 1.03
76
8.11
Device Configuration (dEV CFG)
Followings are the values changeable at the dEV CFG Mode.
1) Action Setting (ACT REVS / dIR)
2) Linear Interpolation (ITP oFF / on)
3) Lock of Parameters (Write Protect, W UNLOCK / LOCK)
4) Actual Position View Mode (View Mode, VI NORM / REVS)
5) Polling address setting (POL AddR 0 ~ 63)
6) Factory Reset (dEFAULT oFF / on)
7) Positioner Self-Test (SELFTEST)
8.11.1 Action Setting (ACT)
Reverse Action (REVS) or Direct Action (dIR) are automatically set by performing “AUTO 2” within
the Auto Calibration function. However, this function is used when the user requires to change ACT
REVS or ACT dIR to other action. Changing the action from Reverse Action (REVS) to Direct Action
(dIR) or Direct Action (dIR) to Reverse Action (REVS) will also change the Signal Direction (SIG),
Position Transmitter Direction (PTM), HART Feedback Direction (HT) and View Mode (VM).
3 seconds
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
<ESC>
3 times