31
en
Store (1 / 2 / 3 / 4)
Solar / Basic settings / Store (1 / 2 / 3 / 4)
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
∆
Ton
Switch-on temperature difference
1.0 … 20.0 K
6.0 K
∆
Toff
Switch-off temperature difference
0.5 … 19.5 K
4.0 K
∆
Tset
Set temperature difference
1.5 … 30.0 K
10.0 K
Stset
Store set temperature
4 … 95 °C
45 °C
Stmax
Maximum store temperature
4 … 95 °C
60 °C
Priority
Store priority
1
1 … 4
(system-dependent)
HysSt
Hysteresis maximum store
temperature
0.1 … 10.0 K
2.0 K
Rise
Rise value
1.0 … 20.0 K
2.0 K
tMin
Minimum runtime
0 … 300 s
30 s
Min. speed
Minimum speed
(20) 30 … 100 %
30 %
Deactivated Blocked for solar loading
Yes, No
No
In systems with 2 or more stores, the corresponding number of separate menu
items (Store 1 to Store 4) is displayed instead of Store.
For each store, an individual
∆
T control, a set and a maximum temperature, the
priority, a hysteresis, a rise value, a minimum runtime and a minimum pump speed
can be adjusted.
In multi-store-systems with differing Store set / Maximum store temperatures, all
stores are loaded up to their Stset temperatures fi rst (according to their priority
and the store sequence control). Only when all stores have exceeded Stset will
they be loaded up to their Stmax temperatures, again according to their priority
and the store sequence control.
Loading logic
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Load. break Loading break time
1 … 5 min
2 min
Circ.
Circulation time
1 … 60 min
15 min
Break speed Loading break pump speed control option Yes, No
No
Speed
Loading break pump speed
(20) 30 … 100 %
30 %
Pump delay Pump delay
Yes, No
No
Delay
Delay time
5 … 600 s
15 s
Solar / Basic settings / Load. logic
In systems with 2 or more stores, loading logic adjustments can be made in this
menu.
Note:
In systems 1 and 2, only the menu item Pump delay will be available.