Product documentation THETA NORM/UNIT
5-45
5.6.5
Heat generator level (..2..)
Parameter
Designation
Setting range / Setting values
Fac
tory
set
tin
g
s
Indiv
idua
l
set
tin
g
Link
01
Heat generator type
OFF
without heat generator
1
Oil/Gas 1 stage (..2..)
2
Oil/Gas 2 stage (..22..)
3
Oil/Gas 2 x 1 stage (..22..)
4 variable
burner
5
High efficiency condensing boilers
(..C../..OT..)
1
02**
Start-up protection
OFF
no start-up protection
1
Start-up protection on minim. temp. limit
2
Start-up protection on outdoor reference
3
Start up protection separated
1
03**
Heat generator minimum
temperature limit
5 °C ... Maximum temperature limit
38 °C
04**
Heat generator maximum
temperature limit
Minimum temperature limit ... Set limit maximum
temperature limit H-GEN
80 °C
05**
Heat generator minimum
temperature limiting mode
1
Minimum temperature limit at heat demand
2
Restricted minimum temp. limit
3
Unrestricted minimum temp. limit
1
06**
Heat generator sensor mode
1
Burner switch off in case of defect
2
External burner switch off
3
Burner enabling in case of defect
Consider warning!!!
1
07**
Minimum burner run time
0 ... 20 Min
2 Min
08**
Burner switching differential
I (SD I)
1-stage:
2 ... 30 K
2-stage:
2 ... (SDII - 0,5K)
6 K
09**
Burner switching differential
II (SD II) (..22..)
(SD I + 0,5 K) ... 30 K
8 K
10**
Time delay stage 2 (..22..)
0 ... 60 min (0 = 10 Sec)
0
11**
Enabling mode stage II
(..22..)
1
Unlimited enabling during
start-up release
2
Delay during start-up release
2
12**
DHW charging mode
1- or 2-stage (..22..)
1
unlimited DHW charging stage 2
2
unlimited DHW charging stage 2
3
DHW charging with stage 1 only
1
13**
Pre-run time boiler circuit
pump/ parall. heat generator
release
0 ... 10 Min
2 Min
14**
Extended run time boiler
circuit pump
0 ... 60 Min
2 Min
15**
Extended run time feed
pump or primary pump
0 ... 60 Min
2 Min
16**
Flue gas temperature
monitoring
OFF
only displays flue gas temperature
0...60 min Heat generator locking in case of ex-
ceeding limit for the set time
SLT
Heat generator locking in case of ex-
ceeding limit
OFF
17**
Flue gas temperature limit
50 ... 500 °C
200°C
19*
Modulation P-band Xp
0,1…50 %/K
5 %/K
20*
Modulation sample time Ta
1…600 s
20 s
21*
Modulation reset time Tn
1...600 s/°C
180 s/
°C
22*
Modulation running time
5...600 s
12 s
23*
Modulation starting time
0...900 s
60 s
24*
Modulation starting load
0...100 %
70%
25
Outdoor temp. locking
OFF, -20…+30 °C
OFF
Содержание Controller Series
Страница 2: ......
Страница 8: ...EbV Product documentation THETA NORM UNIT VI...
Страница 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Страница 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Страница 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Страница 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Страница 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Страница 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Страница 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Страница 170: ...EbV Product documentation THETA NORM UNIT 11 8...
Страница 192: ...PD_THETA NURS_EbV_GB_0460017001_0612 23...