Product documentation THETA NORM/UNIT
8-2
8.1.2
Heat Generator Minimum Temperature Limit (..2.., ..22.., ..C..)
Function:
In order to protect the heat generator against agressive condensate the minimum
temperature limit documented by the manufacturer of the heat generator is to be set.
The heat generator switches on when the temperature falls below the set value, while
it switches off when the set value plus the burner switching differential is exceeded.
During heating the limit temperature will be maintained
This setting is used only for the reaction of the heat generator (burner) to reaching
the set minimum temperature (
KT
min
-H-GEN
). The function for the H-GEN remains
unchanged.
The mode of operation of the set limit is defined via the heat generator parameter
"H-GEN start-up protection".
Function
Minimum temperature
limit H-GEN:
There are three different modes of operation for the minimum temperature limit:
Minimum temperature limit at heat requirement
If there is no demand from the heating or DHW, the boiler will be switched off. The
minimum limit is deactivated. If the temperature in the heat generator drops below
the heat generator frost protection temperature of +5°C, the burner will be switched
on and the heat generator is heated to the minimum temperature limit.
Conditional minimum limit
The boiler minimum temperature serves as the lower limit value and is also
maintained without demand. The boiler is only switched off when summer switch-off
is activated.
Permanent minimum limit
The boiler temperature is limited according to the set minimum temperature
regardless of the demands or the switched-off operating modes.
8.1.3
Heat circuits minimum temperature limit
• If the boiler temperature
BT
act
<= parameter 27
(
BT
min
-HC
) the heating circuit pumps (HC-P, SOL-P, MC-P) are switched off. The
mixer valves are closed.
• If
BT
act
>
BT
min
-HC
+ SD
min-
HC
(H-GEN parameter 28) the heating circuit pumps
and mixer valves are enabled again.
Operation:
Note on operation
Key / parameter tree
Parameter
Setting minimum temperature
HEAT GENER.
PARAMETER 03
Function minimum temperature limit
HEAT GENER.
PARAMETER 05
Содержание Controller Series
Страница 2: ......
Страница 8: ...EbV Product documentation THETA NORM UNIT VI...
Страница 10: ...EbV Product documentation THETA NORM UNIT 1 2...
Страница 16: ...EbV Product documentation THETA NORM UNIT 2 6...
Страница 18: ...EbV Product documentation THETA NORM UNIT 3 2...
Страница 20: ...EbV Product documentation THETA NORM UNIT 4 2...
Страница 70: ...EbV Product documentation THETA NORM UNIT 5 50...
Страница 78: ...EbV Product documentation THETA NORM UNIT 6 8...
Страница 162: ...EbV Product documentation THETA NORM UNIT 10 10...
Страница 170: ...EbV Product documentation THETA NORM UNIT 11 8...
Страница 192: ...PD_THETA NURS_EbV_GB_0460017001_0612 23...