3.5.5
Fire Alarm
Fire alarm verification is an available option on fire zones. When used the
system begins and Alarm Transmission Sequence once the conditions for fire
alarm verification are met.
The Fire Verify setting double checks the state of the fire detectors.
When there is a fire sensor alarm signal, a siren is heard immediately. A 60-
second retard-reset period starts during which every additional fire alarm signal
is ignored. After this period, an additional timeout of 60 seconds starts, which is
the confirmation period, during which a fire sensor alarm signal causes an event
transmission to the monitoring station.
When the confirmation period expires, the fire zone is automatically restored
and ready for a new fire alarm session.