AC-425 Hardware Settings
32
AC-425 Hardware Installation and User Manual
Power off the access control panel before changing the DIP switch settings.
After changes have been made, reboot the panel. The new settings are
automatically defined after power up.
5.2
AC-425 Panel Baud Rate
The AC-425 panel serial port baud rate, set in DIP switches 1 and 2, defines
the communication speed for connecting with a PC in a network connection.
The default baud rate is set to 9600 bits per second.
Figure 17: DIP Switch with Baud Rate Setting
Table 2 lists the status of Switches 1 and 2 and the baud rate:
Table 2: Switch Baud Rates
Switch 1
Switch 2
Baud Rate
Off
Off
9600
Off
On
19200
On
Off
115200
On
On
57600
The access control panel baud rate must be identical to the AxTraxNG Network
configuration of baud rate.
5.3
AC-425 Panel Type
The AC-425 panel type is defined using the third DIP switch. There are two
panel types: a panel with one reader per each door or a panel with two
readers per each door. This DIP switch setting influences the number of readers
per door in the panel.
The default AC-425 panel setting is for two readers per each door.
Figure 18: DIP Switch for Door Setting
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8