AC-425 Hardware Installation and User Guide
5.
AC-425 Hardware Settings
Each AC-425 panel controls an entrance. The behavior of the panel is controlled by DIP
switch settings.
Select the appropriate DIP switch setting to operate the panel as either a single door, a
double door, or four doors (see Section 5.3).
Access control panels, configured as either single door or double door controllers, have
two readers, IN or OUT. Access control panels configured with the MD-D04 expansion as
either double door or four-door controllers have four readers.
Connectors Description
Setup
Two readers per door:
Outputs
Door 1 Lock output
(OUT 1)
Door 2 Lock output
(OUT 2)
General purpose output
(OUT 3)
General purpose output
(OUT 4)
Inputs
Door 1:
Request to exit
(IN 1)
Door monitor input
(IN 3)
Door 2:
Request to exit
(IN 2)
Door monitor input
(IN 4)
Readers
Reader1 – Door1
Door Entry or Exit
Reader2 – Door2
Door Exit or Entry
Reader3 – Door1
Door Entry or Exit
Reader4 – Door2
Door Exit or Entry
One reader per door:
Outputs
Door1 Lock output
(OUT 1)
Door2 Lock output
(OUT 2)
Door3 Lock output
(OUT 3)
Door4 Lock output
(OUT 4)
Inputs
Door1 Request to exit
(IN 1)
Door2 Request to exit
(IN 2)
Door3 Request to exit
(IN 3)
Door4 Request to exit
(IN 4)
Readers
Reader1
(Door1 IN/OUT)
Reader2
(Door2 IN/OUT)
Reader3
(Door3 IN/OUT)
Reader4
(Door4 IN/OUT)