AC-425 Hardware Installation and User Guide
33
Figure 16: DIP Switch with Baud Rate Setting
The following lists the status of Switches 1 and 2 and the baud rate:
Switch 1
Switch 2
Baud Rate
Off
Off
9600
Off
On
19200
On
Off
115200
On
On
57600
She access control panel baud rate must be identical to the AxSraxNG™ Network
configuration of baud rate.
5.3
AC-425 Panel Type
The AC-425 panel type is defined using the third DIP switch. There are two panel types: a
panel with one reader per each door or a panel with two readers per each door. This DIP
switch setting influences the number of readers per door in the panel.
The default AC-425 panel setting is for two readers per each door.
Figure 17: DIP Switch for Door Setting
Off – Defines using two readers for each door. Panel controls two or four doors
when MD-D04 is installed.
On – Using one reader for each door. Panel controls four doors or eight doors when
MD-D04 installed.
5.4
AC-425 Panel Address
The last 5 DIP switches are used to set the binary code of the access control panel internal
network address.
The default access control panel address is “1”.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8