WARNING:
connect the gas to the oven's gas supply line using the
supplied connector (A) (see figure 12)
This appliance shall be installed in accordance whit the regulations in
force and only in a well-ventilated space. Read the instructions before
installing or using this appliance.
IMPORTANT
We recommend to check wether the appliance has been foreseen for the
kind of gas distributed. Conversion for use other gases must only be
undertaken by a qualified person. For information for use on other gases
contact your local Service Centre. The cooker must be installed by a
qualified person, conforming to local regulations. Failure to install the
appliance correctly could invalidate any manufacturers warranty and lead
to prosecution under the above quoted regulations.
Provision for Ventilation
The room containing the cooker should have an air supply in accordance
with local regulations.
Remember that the quantity of air necessary for combustion must never
be less than 2m3/h for each kW of power (see total power in kW on the
appliance data plate see fig. A ).
Gas Safety (Installation & Use) Regulations
It is the law that all gas appliances are installed by competent persons
in accordance with the current edition of the
Installation & Use
Regulations.
It is in your interest and that of safety to ensure compliance
with the law.
For UK:
This appliance must be installed by a qualified electrician / competent
person
gas safe register.
Safety may be impaired if installation is not
carried out in accordance with these instructions.
The appliance must be installed in accordance with All relevant British
Standards (latest editions).
The gas and electricity connections and any adjustments must be
made by specialised staff.
Gas Connection
Prior to installation, ensure that the local distribution conditions (nature
of the gas and gas pressure) and the adjustment conditions are compatible.
The adjustment conditions for this appliance are stated on the rating plate
which can be found on the back cover. This appliance is not designed to
be connected to a combustion products evacuation device. Particular
attention should be given to the relevant requirements regarding ventilation.
Connection to the cooker should be made with connection in accordance
with local regulations.
A special valve for routinely turning the gas supply on/off must be
installed between the gas inlet tube to the room and the hob, in order
to cut off the gas supply after cooking in the event of accidents during
cooking. This valve must be easily accessible at all times, and should
be closed during long periods of no use.
The gas tube must be routed in such a way that it is not fed through
hot areas and does not come into contact with any hot parts of the
appliance, e.g. the underside of the hob. Tube installation must be
carried out in such a way as to ensure that it runs freely and that it
cannot come into contact with or be bent by any movable parts in the
kitchen, e.g. drawers.
If this is not the case, a special pressure regulator must be fitted to
the gas supply pipe in accordance with the relevant standards.
The cooker must be connected to the gas supply pipe such that the
cooker is not subjected to any kind of stress.
In order to guarantee that the cooker works safely and has a moderate
energy consumption and long service life, you must ensure that the supply
pressure corresponds to the values given in table D.
GB
7
*
GAS CONNECTING
We recommend that the cooker circuit is rated to 13 amps.
Cable type HO5 RRF or HO5 RRF, 3 X 1.5 mm2.
Connecting the mains cable (fig. 13).
Open the mains terminal block cover as shown, unscrew screw A
the cable clamp and unscrew (not fully) the screws in the mains
terminal block L N E which secure the three wires of the mains cable
. Fit the cable and refit screw A the cable clamp.
Allow sufficient cable length for the cooker to be pulled out for cleaning,
but do not let it hang closer than 50mm (2) to the floor. The cable can
be looped if necessary, but make sure that it is not kinked or trapped
when the cooker is in position.
IMPORTANT
The wires in the mains lead are coloured in accordance with the
following code:
GREEN AND YELLOW........EARTH
BLUE....................................NEUTRAL
BROWN ...............................LIVE
REPLACEMENT OF THE CABLE (fig. 13).
In case the cable is damaged, replace it in accordance with the
following instructions:
- open the box of the supply board as described on the picture below;
- unscrew screw A fixing the cable;
- replace the cable with one of the same lenght and in accordance
with the features described on the table; switch the appliance off,
and close the gas tap
- the green-yellow earth wire must be connected to the terminal \
and it must be about 10 mm longer thean the live wires;
- the blue neutral wire must be connected to the terminal marked
with letter N;
- the live wire must be connected to the terminal marked with letter
L.
ELECTRICAL CONNECTION
This appliance must be installed by a qualified person in
accordance with the latest edition of the IEE Regulations and in
compliance with the manufacturer instructions.
*
Ensure that the voltage is the same as that stated on the rating plate.
(fig. A ).
WARNING! THIS APPLIANCE MUST BE EARTHED
If an fixed appliance is not equipped with supply cable and plug, the
power supply must be fitted with a disconnect switch in which the
distance between contacts permits total disconnection in accordance
with overvoltage category III, as required by installation regulations.
Be sure that the earth wire green/yellow is not interrupted by the
switch
Fig. 12
A
2
1
3
4
5
A
Fig. 13
N
L