4-33
Rosemount Tank Radar Rex
Chapter 4 Service
Service Manual
308012En, Ed.2
May 2013
4.1.11 HART Input
Hart Slaves are connected to Analog input 1. Connection to HART
devices requires a Multi Field Communication Card equipped with
optional HART modem.
Figure 4-10. Connection of HART slaves.
A maximum of 3 Hart slaves can be connected to the Rex gauge in
multidrop configuration.
If only on HART slave is connected, and the short address = 0, current
mode is supported.
With three HART slaves connected, short address 1-3 must be used and
the slave current is parked at 4 mA.
The 250
resistance is needed for HART-communication only.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
X12
250
Содержание TankRadar Rex DAU 2100
Страница 2: ......
Страница 3: ...www rosemount tg com Service manual Second edition Copyright May 2013 Rosemount Tank Radar AB ...
Страница 8: ...Rosemount TankRadar Rex Contents TOC 4 Service Manual 308012En Ed 2 May 2013 ...
Страница 12: ...Rosemount Tank Radar Rex Chapter 1 System Description 1 4 Service Manual 308012En Ed 2 May 2013 ...
Страница 44: ...Rosemount Tank Radar Rex Chapter 3 Device Description 3 30 Service Manual 308012En Ed 2 May 2013 ...
Страница 116: ...Rosemount Tank Radar Rex Chapter 4 Service 4 72 Service Manual 308012En Ed 2 May 2013 ...
Страница 124: ...Rosemount Tank Radar Rex Chapter 5 Calibration 5 8 Service Manual 308012En Ed 2 May 2013 ...
Страница 132: ...Rosemount Tank Radar Rex Chapter 6 Troubleshooting 6 8 Service Manual 308012En Ed 2 May 2013 ...
Страница 134: ...Rosemount Tank Radar Rex Chapter 7 Spare Parts 7 2 Service Manual 308012En Ed 2 May 2013 ...
Страница 146: ...Rosemount Tank Radar Rex Chapter 9 Technical Data 9 10 Service Manual 308012En Ed 2 May 2013 ...
Страница 152: ...Rosemount Tank Radar Rex Index 1 6 Service Manual 308012En Ed 2 May 2013 ...
Страница 153: ......