Hazardous Area Oxymitter 5000
E-2
Instruction Manual
IM-106-350C, Rev 2.2
July 2008
The block supports two forms of the PID equation: Standard and Series. You
can choose the appropriate equation using the FORM parameter. The
Standard ISA PID equation is the default selection.
To further customize the block for use in your application, you can configure
filtering, feedforward inputs, tracking inputs, setpoint and output limiting, PID
equation structures, and block output action. Table E-1 lists the PID block
parameters and their descriptions, units of measure, and index numbers, and
Figure E-1 illustrates the internal components of the PID function block.
Table E-1. PID Function Block
System Parameters
Standard Out = GAIN
e
x
x
1
r
s
1
+
d
s
d
s
1
+
1 +
F
+
Series Out = GAIN
e
x
x
1
1
r
s
+
d
s
1
x
+
d
s
1
+
F
+
Where
GAIN: proportional gain value
r: Integral action time constant (RESET parameter) in seconds
s: laplac e operator
d: derivative action time constant (RATE parameter)
fixed smoothing factor of 0.1 applied to RATE
F: feedforward control contribution from the feedforward input (FF_VALparameter)
e: error between setpoint and process variable
+
t
t
t
t
t
+
a
t
a
:
t
38740091
Parameter
Index
Number
Units
Description
ACK_OPTION
46
None
Used to set auto acknowledgment of alarms.
ALARM_HYS
47
Percent
The amount the alarm value must return to within the alarm limit before the
associated active alarm condition clears.
ALARM_SUM
45
None
The summary alarm is used for all process alarms in the block. The cause of
the alert is entered in the subcode field. The first alert to become active will
set the Active status in the Status parameter. As soon as the Unreported
status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active status, if the subcode has changed.
ALERT_KEY
04
None
The identification number of the plant unit. This information may be used in
the host for sorting alarms, etc.
ALG_TYPE
74
None
Selects filtering algorithm as Backward or Bilinear.
BAL_TIME
25
Seconds
The specified time for the internal working value of bias to return to the
operator set bias. Also used to specify the time constant at which the integral
term will move to obtain balance when the output is limited and the mode is
AUTO, CAS, or RCAS.
BIAS
66
EU of OUT_SCALE
The bias value used to calculate output for a PD type controller.
BKCAL_HYS
30
Percent
The amount the output value must change away from the its output limit
before limit status is turned off.
BKCAL_IN
27
EU of OUT_SCALE
The analog input value and status from another block’s BKCAL_OUT output
that is used for backward output tracking for bumpless transfer and to pass
limit status.
BKCAL_OUT
31
EU of PV_SCALE
The value and status required by the BKCAL_IN input of another block to
prevent reset windup and to provide bumpless transfer of closed loop control.
Содержание Oxymitter 5000
Страница 2: ......
Страница 6: ......
Страница 14: ...Hazardous Area Oxymitter 5000 iv Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 82: ...Hazardous Area Oxymitter 5000 7 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 130: ...Hazardous Area Oxymitter 5000 9 24 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 140: ...Hazardous Area Oxymitter 5000 11 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 172: ...Hazardous Area Oxymitter 5000 B 2 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 192: ...Hazardous Area Oxymitter 5000 D 14 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 210: ...Hazardous Area Oxymitter 5000 E 18 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 212: ...Instruction Manual IM 106 350C Rev 2 2 July 2008 Hazardous Area Oxymitter 5000 Index 2 ...